September 15, 1965
REPORT OF INSPECTION
DATE OF INSPECTION 9/2/65 J. A. Carlson
INSPECTOR
LOCATION , Premises of Assured, 922 - 9th St., Greeley, Colorado
Kewanee Fire Tube Scotch Marine Boiler No. 1/Colo. 3338-S
Inspected internally and externally.
Corrosion in the form of scattered pitting was observed on the internal
surfaces. This corrosion was active and one tube had actually pitted
through and will have to have repairs. Since the hole in the tube is
quite near the tube sheet, it is quite possible that the hole can be
closed by means of fusion welding and, if so, this is satisfactory.
To prevent further deterioration due to corrosive action of the internal
surfaces, we recommend that a boiler compound be used in accordance with
the suppliers recommendations.
It is our enderstanding that this will be done.
The condition outlined was discussed with Mr. Clementz, Custodian, at
the time of inspection.