1. Remove obstacles from in front of exit doors on south side of
library.
2. Install exit signs above all exit doors in both front library and new
back room.
3. Remove thumb bolt locks from front exit doors and replace them with
lock that cannot be inadvertently locked as with panic hardware.
4. Replace locks on all other dorrs with panic hardware.
5. Repair all broken -out openings in walls and ceiling in boiler room.
6. Have boiler inspected by insurance carrier and post such certi-
cation.
7. Repair eled•rical circuit to compressor in boiler room.
8. Remove all storage from boiler room.
9. Install closer on boiler room door.
10. Install fire damper in original return air duct to furnace rorm.
11. The installation or use of an incinerator in a garage is not permitted
unless completely enclosed in a two hour fire resistive rated en-
closure extending 3 ft. above the roof line and having all openings
in the enclosure closed with class "At doors. ('Enclosure must be
masonry) The existing incinerator is declared a hazard and shall
not be used until it is made to conform to minimum safety standards.
12. Install a one -hour fire resistive rated ceiling in the garage or con-
tinue the $" masonry wall to the underside of the roof between the
ceiling joists.
13. Install handrails on the stairway in the garage.
[�
WELD CO. Ct?i•''".!QcIfNERS
(COD) GREELEV, ! '.
REV
(DATE)
Signature _
our ,;1966
OIWI10!11112!0014i51 ;
RC: boo
Title or Official Capacity
INDUSTRIAL COMMISSION OF COLORADO
SAFETY INSPECTION DIVISION, CAPITOL ANNEX
DENVER, COLORADO 80203
Dan L. Larimer field
INSPECTOR COUNTY
DATE
INSPECTION NO 13261
October 204_ 1966 UNIT Weld County Library
!Feld County Library
2<27 -23d Ave.
Greeley, Colorado
90 days
RETURN
COPY
SEE NOTE BELOW
Page 2
14. Rehan door betsan old and new library rooms so that t:!3 doer s,:ings
in the direction of egress from the nee, room.
15. The front !single door may be replaced with a window a there lG suffi-
cient width of exiting provided elsewhere.
16. The passage door between the ch L_drens reLd°_ng r c.om s%,,A.1 either be
removed or provided with hardware that cannot be lockedfrom the
reading room side.
17. All storage of excess booi<:s and readin,: 'iaterial if, the g2r: Te shall
bw ►ocd into the library and the garage shall not be used as
storage room for reading raaterial. (Books, e tc. ,norn.ily carried
inside the library vans are exempted provided the doors are kept
closed when the vans are not being loaded)