Loading...
HomeMy WebLinkAbout962076.tiff 44 MEMORANDUM Wine TO: Kerni D. Keithley, Current Planner October 8, 1996 Fr COLORADO From: Edwin D. Stoner, Lead Combination Inspector F SUBJECT: USR-1130 The Building Inspection Department has reviewed the submittal from B.F.Y. LLC concerning the warehousing pharmaceutical and food product. Based upon the information submitted this facility shall be considered a Group S, Division 1 Occupancy with the following conditions: 1. The storage of materials shall not exceed those quantities as listed in Table 3-D and 3-E of the 1994 Edition of the Uniform Building Code. 2. The Building Inspection Staff shall have access at any reasonable time to conduct an inspection of the building. Material Safety Data Sheets and the quantities of materials stored in this building shall be available to the staff at these times. If the owner is unable to comply with these conditions, the facility will be reclassified to the appropriate occupancy and the building brought into compliance with all of the requirements of this new occupancy. 962076 TABLE 3-D-EXEMPT AMOUNTS OF HAZARDOUS MATERIALS PRESENTING A PHYSICAL HAZARD I MAXIMUM QUANTITIES PER CONTROL AREAL When two units are given,values within parentheses are in cubic feet(cu.ft.)or pounds(lbs.) CONDITION STORAGE2 USE2—CLOSED SYSTEMS USE2—OPEN SYSTEMS Solid Lbs.3 Liquid Gas Solid Lbs. Liquid Gallons Gas Solid Lbs. Liquid Gallons (Cu.Ft.) Gallons3(Lbs.) Cu.Ft. (Cu.Ft.) (Lbs.) Cu.Ft. (Cu.FL) (Lbs.) x 0.4536 fork 3.785 for L x 0.4535 for k x 3.785 for L x 5.9536 for to 3.785 fort Material Class x 0.0283 for mo x 0.4536 for kg x 0.02831or m3 x 0.0283 for mg x 0.4535 lot kg x 0.0283 for m3 x 5.6283 for m x 0.45361or kg I imbustible II N.A. 12010 N.A. N.A. 120 N.A. N.A. 30 iquid4.5.6.7.8,9 111-A N.A. 33010 N.A. N.A. 330 N.A. N.A. 80 III-B N.A. 13,20010.11 N.A. N.A. 13,20011 N.A. N.A. 3,30011 1.2 Combustible fiber (loose) (IOU) N.A. - N.A. (100) N.A. N.A. (20) N.A. (baled) (1,000) N.A. N.A. (1,000) N.A. N.A. (200) N.A. 1.3 Cryogenic,flammable or oxidizing N.A. 45 N.A. N.A. 45 N.A. N.A. 10 2.1 Explosives12 110,13 (1)10,13 N.A. 1/4 (1/4) IN.A. 1/4 (I/4) 3.1 Flammable solid 1256,10 N.A. N.A. I4 N.A. N.A. 14 N.A. ' 3.2 Flammable gas (gaseous) N.A. N.A. 7506,10 N.A. N.A. 7506,10 N.A. N.A. (liquefied) N.A. 156,10 N.A. N.A. 156.10 N.A. N.A. N.A. 3.3 Flammable I-A N.A. 3010 N.A. N.A. 30 N.A. N.A. 10 Iiquid4,5.6.7,8.9 10 I-B N.A. 60 N.A. N.A. 60 N.A. N.A. 15 I-C N.A. 9010 N.A. N.A. 90 N.A. N.A. 20 Combination I-A, N.A. 12010 N.A. N.A. 120 N.A. N.A. 30 I-B,I-CI5 4.1 Organic peroxide, unclassified detonatable 110,12 (010,12 N.A. 1/412 (1/4)12 N.A. 1/412 (I/4)12 4.2 Organic peroxide I 56.10 (5)6.10 N.A. 16 (1)6 NA. 16 (1)6 II 506,10 (50)610 N.A. 506 (50)6 N.A. 106 (10)6 III 1256.10 (125)6.10 N.A. 1256 (125)6 N.A. 256 (25)6 IV 5006.10 (500)6.10 N.A. 5006 (500)6 NA. 1006 (100)6 V N.L. N.L. N.A. N.L. N.L. N.A. N.L. N.L. 4.3 Oxidizer 4 110,12 (1)10,12 N.A. 1/412 (1/4)12 N.A. 1/412 (1/4)12 N 316 106.10 (10)6.10 N.A. 26 (2)6 N.A. 26 (2)6 a. 2 2506.10 (250)6.10 N.A. 2506 (250)6 N.A. 506 (50)6 Z 1 4,0006,10 (4,000)6,10 N.A. 4,0006 (4,000)6 N.A. 1,0006 (1,000)6 DOD 4.4 Oxidizer—gas E (gaseous)6"0 N.A. N.A. 1,500 N.A. N.A. 1,500 N.A. N.A. (liquefied)6,10 N.A. 15 N.A. N.A. 15 N.A. N.A. N.A. a 5.1 Pyrophoric 410.12 (4)10,12 5010,12 112 (012 1010,12 0 0 Q 6.1 Unstable(reactive) 4 110,12 (010,12 1010,12 i/412 (1/4)12 2io,12 1/412 (1/4)12 Z 3 56.10 (5)6.10 506.10 16 (I)6 106.10 16 (1)6 0 2 506.10 (50)6.10 2506,10 506 (50)6 2506,10 106 (10)6 T 1 N.L. N.L. 7506.10 N.L. N.L. N.L. N.L. N.L. 7.1 Water reactive 3 56,10 (5)6.10 N.A. 56 (5)6 N.A. 16 (1)6 2 506.10 (50)6,10 N.A. 506 (50)6 N.A. 106 (10)6 1 12510.11 (125)10,11 N.A. 12511 (125)11 N.A. 2511 (25)1I N.A.—Not applicable. N.L.—Not limited. 'Control areas shall be separated from each other by not less than a one-hour fire-resistive occupancy separation.The number of control areas within a building used for ' retail or wholesale sales shall not exceed two.The number of control areas in buildings with other uses shall not exceed four.See Section 204. 2The aggregate quantity in use and storage shall not exceed the quantity listed for storage. 3The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials within a single control area of Group M Occupancies used for retail sales may exceed the exempt amounts when such areas are in compliance with the Fire Code. 4The quantities of alcoholic beverages in retail sales uses are unlimited provided the liquids are packaged in individual containers not exceeding four liters. The quantities of medicines,foodstuffs and cosmetics containing not more than 50 percent of volume of water-miscible liquids and with the remainder of the solutions not being flammable in retail sales or storage occupancies are unlimited when packaged in individual containers not exceeding four liters. 5For aerosols,see the Fire Code. 6Quantities may be increased 100 percent in sprinklered buildings.When Footnote 10 also applies,the increase for both footnotes may be applied. 7For storage and use of flammable and combustible liquids in Groups A,B.E,F,H,I,M.R.S and U Occupancies,see Sections 303.8,304.8,305.8,306.8,307.1.3 through 307.1.5,308.8,309.8,310.12,311.8 and 312.4. 6For wholesale and retail sales use,also see the Fire Code. 9Spray application of any quantity of flammable or combustible liquids shall be conducted as set forth in the Fire Code. . IOQuantities may be increased 100 percent when stored in approved storage cabinets,gas cabinets or exhausted enclosures as specified in the Fire Code.When Footnote 6 also applies,the increase for both footnotes may be applied. I'The quantities permitted in a sprinklered building are not limited. 12Permitted in sprinklered buildings only.None is allowed in unsprinklered buildings. '30ne pound of black sporting powder and 20 pounds(9 kg)of smokeless powder are permitted in sprinklered or unsprinklered buildings. -.definitions of Divisions 2 and 3 in Section 307.1. .ntaining not more than the exempt amounts of Class I-A,Class I-B or Class I-C flammable liquids. 16A maximum quantity of 200 pounds(90.7 kg)of solid or 20 gallons(75.7 L)of liquid Class 3 oxidizers may be permitted in Groups I,R and U Occupancies when such materials are necessary for maintenance purposes or operation of equipment as set forth in the Fire Code. w 0 962076 TABLE 3-E-EXEMPT AMOUNTS OF HAZARDOUS MATERIALS PRESENTING A HEALTH HAZARD ' u MAXIMUM QUANTITIES PER CONTROL AREA1.2 rn When two units are given,values within parentheses are in pounds(lbs.) STORAGES USES-OLOSED SYSTEMS USE3—OPEN SYSTEMS Liquid Liquid Liuid Galions4,5,6 Gas - Solid Gallons4.3 Gas Solid Gallons4.6 MATERIAL Solid Lbs.4.50 (Lbs.) Cu.Ft.5 Lbs.4•5 (Lbs.) Cu.Ft.5 Lbs.4.5 (Lbs.) x 3.785 for L x 3.785 for L x 3.785 for L x 0.0536 for kg x 0.4536 for kg x 0.028 for m3 x 0.4536 for kg x 0.1536 for kg x 0.028 for m3 x 0.4536 for kg x 0.4536 for kg 1. Corrosives 5,000 500 8106 5,000 500 8106 1,000 100 2. Highly toxics7 1 (I) 208 1 (I) 208 l/4 (1/4) 3. Irritants9 5,000 500 8106 5,000 500 8106 1,000 100 4. Sensitizers9 5,000 500 8106 5,000 500 8106 1,000 100 5. Other health hazards9 5,000 500 8106 5,000 500 8106 1,000 100 6. Toxics7 500 (500) 8106 500 (500) 8108 125 (125) I Control areas shall be separated from each other by not less than a one-hour fire-resistive occupancy separation.The number of control areas within a building used for retail or wholesale sales shall not exceed two.The number of control areas in buildings with other uses shall not exceed four.See Section 204. 2The quantities of medicines,foodstuffs and cosmetics,containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable,in retail sales uses are unlimited when packaged in individual containers not exceeding 4 liters. 3The aggregate quantity in use and storage shall not exceed the quantity listed for storage. 4The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid health hazard materials within a single control area of Group M Occupancies used for retail sales may exceed the.exempt amounts when such areas are in compliance with the Fire Code. 5Quantities may be increased 100 percent in sprinklered buildings.When Footnote 6 also applies,the increase for both footnotes may be applied. 6Quantities may be increased 100 percent when stored in approved storage cabinets,gas cabinets or exhausted enclosures as specified in the Fire Code.When Footnote 5 ' also applies,the increase for both footnotes may be applied. 7For special provisions,see the Fire Code. tPermitted only when stored in approved exhausted gas cabinets,exhausted enclosures or fume hoods. CO 9lrritants,sensitizers and other health hazards do not include commonly used building materials and consumer products which are not otherwise regulated by this code. I a 2 -71 O CO C 0 Z O n O v m S • 962416 OA kite jal6 DEPARTMENT OF PLANNING SERVICES PHONE (970) 353-6100, EXT 3540 FAX (970) 352-6312 WELD COUNTY ADMINISTRATIVE OFFICES 1400 N. 17TH AVENUE O GREELEY, COLORADO 80631 • COLORADO DATE: August 28, 1996 CASE NUMBER: USR-1130 TO WHOM IT MAY CONCERN: Enclosed is an application from B.F.Y. LLC for a Site Specific Development Plan for a Special Reyiew Permit for a Delivery Company with Warehousing for Customers and Recreational Vehicle Storage. The parcel of land is described as Lot A of RE-1727, located in part of the SW4 of the NNV4 of Section 5, T1 N, R67W of the 6th P.M., Weld County, Colorado. The location of the parcel of land for which this application has been submitted is east and adjacent to Weld County Road f5, 1/4 mile south of Colorado State Highway 52. The application is submitted for your review and recommendation. Any comments or recommendation you consider relevant to this request would be appreciated. Your prompt reply will help to facilitate the processing of the application. Please reply by September 18, 1996, so that we may give full consideration to your recommendation. Please call, Kerri D. Keithley, if you have any questions. Check the appropriate boxes below and return to our address listed above. 1. We have reviewed this request and find that it does/does not comply with our Comprehensive Plan for the following reasons. 2. _ We do not have a Comprehensive Plan, but we feel this request is/is not compatible with the interest of our town for the following reasons. 3. We have reviewed the request and find no conflicts with our interests. 4. A formal recommendation is under consideration and will be submitted to you prior to 5. X Please refer to the enclosed letter. Signed: A 1\1. e ._ S\ _ t . ) . .. Agency: Date: R\ ka. C v� MOUNTAIN VIEW FIRE PROTECTION DISTRICT 9119 County Line Road Longmont, CO 80501 (303) 772.0710 or Metro (303) 666.4404 Fax (303) 651.7702 962076 `j°°"rA'ti MOUNTAIN VIEW FIRE PROTECTION DISTRICT Administrative Office: 9119 County Line Road• Longmont, CO 80501 g •:: 8 (303) 772-0710 Metro (303) 666-4404 FAX (303) 651-7702 �7EW Weld r tv n I,Ar.nnp Dept. September 5, 1996 SEP 0 9 1996 Kerri D. Keithley 4,- IVED Department of Planning Services Weld County Adminiscracion Offices 1400 N. 17th Avenue Greeley, CO 80631 RE : USR-1130 B.F.Y. LLC (SITE SPECIFIC DEVELOPMENT PLAN Delivery Company (office/warehouse & RV Storage) Dear Kerri : I have reviewed the submitted materials and before I can provide detailed information with regards to fire protection requirements, I need the following information: 1 . The drawing I received, marked USR-524 was difficult to read with regards to the measurements of the building nearest what is marked as the "existing access" . Verify the dimensions of the building I believe to be marked "shop" . Figures added to the drawing are 48' X 24" . Are these the correct figures? 2 . The drawing states "Existing building is closer to existing chain link fence" , what is the exact distance? 3 . What type of building construction are the existing buildings and what is the proposed construction type for the addition to the warehouse? 4 . Fire Flow requirements and number of hydrants needed will be determined based on items 1 through 3 . 5 . Nothing in the application reflects what will be stored in the proposed warehouse . Fire Protection requirements for this building will be determined based on this information. Has the Building Official assigned an "occupancy classification" to this building? Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7 9119 Cnty Line Rd. 10971 WCR 13 P.O.Box 575 P.O.Box 11 10911 Dobbin Run P.O.Box 666 P.O.Box 40 Longmont,CO Longmont,CO 299 Palmer Ave. 8500 Niwot Road Lafayette,CO 600 Briggs 100 So.Forest St. 60501 80504 Mead,CO 80542 Niwot,CO 80544 80026 Erie,CO 80516 �]Dacono,CO 80514 9620'• Page 2 . 6 . The Fire District uses the Knox Company as the provider for key boxes and padlocks which are used only for fire department access to the premises . Knox Box models 3200 or 4400 are satisfactory unless it' s determined that a storage cabinet will be necessary for hazardous materials information. A heavy duty padlock will be necessary for the gate access to the proposed RV Storage lot . Applicant will need to complete the Knox order form and attach payment and return to the Fire District in order that an "authorized signature" can be affixed to the application, which will then be mailed. Applicant will need to notify the Fire District when installation of the knox box is completed. (Fire Protection Development Standards, Appendix IX) . If you have any questions, please give me a call . Sincerely, William N. Bailey Fire Prevention Manager Fire Marshal planrvw. cor\USR-1130 1 APPENDIX IX MOUNTAIN VIEW FIRE PROTECTION DISTRICT LOCK BOX INFORMATION SECTION I PURPOSE 1 . 1 The purpose of this procedure is to set a standard within the authority of the Mountain View Fire Protection District regarding Lock Boxes. SECTION II WHERE REQUIRED/TYPE REQUIRED i2 . 1 Any building, except a one or two family dwelling which has a local fire alarm or monitored fire alarm system shall provide a lock box for fire department access. 2 . 2 Any building, except a one or two family dwelling which has a fire protection system, that when activated sounds an alarm, whether local or monitored shall provide a lock box for fire department access. 1 2 . 3 All new or remodeled buildings . 2 . 4 All businesses falling under the requirement of SARA Title III , UFC Sections 79 or 80 , will be required to install and maintain a lock box large enough to house the HMDS . Businesses housing a sufficient quantity of hazardous materials to represent a hazard to the public or to firefighting, in the opinion of the Chief or his designate, may be required to install such a lock box. a. This box will be located near the main entrance, or at another location approved by the Fire Marshal prior to installation . The box must be visible and must have the address numbers , and unit numbers , if applicable, stenciled on the box . The recommended height of installation is eight feet above the grade. b. A copy of the HMDS book will be delivered to 01 the Mountain View Fire Protection District at : c/o Fire Marshal 700 Weaver Park Road Longmont, CO 80501 1 962076 POI c. It is the responsibility of the business owner/ occupant to maintain both copies of the HMDS . 2.5 Any building may be required to install a lock box where unusual hazards or difficult fire department access exists. 2 . 6 Lock boxes manufactured by The Knox Company are approved for installation within the Mountain View - Fire Protection District. The Fire District will recommend the model for specific needs . SECTION III CONTENTS 3 . 1 The lock box shall contain a current list of emergency contacts to notify when the lock box is opened. Such list shall include telephone numbers. 3 .2 The lock box shall contain the appropriate keys to allow fire district personnel access to the building. 3 . 3 Each key shall be tagged indicating the area of MIME access for that key. IMI Li N N M 962076 DEPARTMENT OF PLANNING SERVICES I PHONE (970) 353-6100, EXT.3540 FAX (970) 352-6312 eil WELD COUNTY ADMINISTRATIVE OFFICES 1400 N. 17TH AVENUE COLORADO GREELEY, COLORADO 80631 September 26, 1996 William Bailey Mountain View Fire Protection District 9119 County Line Road Longmont, Co. 80501 Subject: USR-1130, B.F.Y, LLC Site Specific Development Plan Dear Mr. Bailey: Enclosed is a letter that I received from Robert Heil, one of the applicants for USR-1130. This letter is in response to the referral that I received from your department. Please review this letter and let me know any recommendations or concerns that your district may have in regards to this case. If you have any questions or need additional information, feel free to contact me or the applicant. Thank you. Sincerely, Kern D. Keithley Current Planner enclosure 962076 September 24. 9yt'11 1C County Planning Deat Kerri D. Keithley 2 Department of Planning Services SEP 6 1996 Weld County Administration 0ffices _; 1400 N. 17th Avenue • ,s .'Mit "° Greeley, Co . 80631 NED 7''we 1 Re : USR-1130 B.F.Y. LLC Dear Kerri : This letter is in response to Fire Marshal William N . Bailey ' s letter dated September 5 . 1996 . The following responses match the numbers in Mr . Bailey ' s letter: 1 . The building in question measures 48 ' x 24 ' . 2 . The distance from the building in question and the road side fence is 31 ' and the distance from this same building and the fence that runs through the yard is 59 ' . 3 . The office building is wood frame and the warehouse building is wood frame with steel siding . 4 . We are not sure of fire flow requirements but we under- stand there are a couple of hydrants in close proximity to the yard. 5 . In response to the actual storage of materials in the warehouse , usually any materials that are stored only stay in the warehouse a couple of days . These materials are generally a pharmaceutical or food product . We do not store any household hazardous waste . hazardous or flammable materials . 6 . We are quite willing to purchase and install a Knox box once we receive our USR. We would like more information on these boxes including purchase costs . Please advise if further information is required. Sincerely, R. L. Heil 962076 Mouetvti MOUNTAIN VIEW FIRE PROTECTION DISTRICT P e Administrative Office: 9119 County Line Road •Longmont, CO 80501 8 (303) 772-0710 Metro (303) 666-4404 FAX (303) 651-7702 v,e„ Weld County Planning Dept. September 27, 1996 OCT 0 1 1996 Ms . Kerri D. Keithley V E D Department of Planning Services Weld County Administration Offices 1400 N. 17th Avenue Greeley, CO 80631 RE: R.L. Heil letter to you dated Sept. 24, 1996 Dear Kerri : Thank you for sending a copy of the above letter. I have enclosed a Knox Company application form for the purchase of the Knox Box. Models 3200 or 4400 would satisfy the requirements of the fire district . Applicant needs to complete the application, attach payment in the form of a check to the Knox Company, and return both to my office . I will affix an authorized signature and mail the items to the Knox Company. The key box and hardware will be shipped directly to the applicants address . After installation, applicant needs to arrange with my office, a time for staff to obtain access keys to the office and warehouse buildings, which will then be placed in the key box, at which time the key box will be secured and ready for fire department use when necessary. This afternoon I did drive Weld County Road 15, South from Highway 52 and could not locate a fire hydrant along this roadway. If there is a hydrant serving this area, the fire district has no record of it . Mr. Heil needs to confirm his information with regards to two hydrants being available to serve the property. If this can' t be done, Mr. Heil needs to pursue the installation of a fire hydrant after site determination is approved by the fire district . A fire flow of 1, 500 gallons per minute at 20 pounds per square in needs to be available to this site . Mr. Heil needs to provide the fire district with a letter from the Central-Weld Water District indicating that the fire flow is available . Also, please advise Mr. Heil that the above ground fuel tank located in the South West corner of the property needs to be removed. The Uniform Fire Code adopted by the Fire District does not allow this type of fuel storage tank. Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7 9119 Cnty Line Rd. 10971 WCR 13 P.O.Box 575 P.O.Box 11 10911 Dobbin Run P.O.Box 666 P.O.Box 40 Longmont,CO Longmont,CO 299 Palmer Ave. 8500 Niwot Road Lafayette,CO 600 Briggs 100 So.Forest St. 80501 80504 Mead,CO 80542 Niwot,CO 80544 80026 Erie,CO 80516 Dacono,CO 80514 962076 Page 2 . I was not aware that Kangaroo Express was already doing business at this location, can you confirm that an Occupancy Permit has been issued. Also, can you provide me with the occupancy classification of the buildings as determined by your Chief Building Official? If there are any questions, please give me a call and thanks for your assistance in this matter! Sincerely, j iYAKb-w--� 14 ` 7-4s-01_ William N. Bailey Fire Prevention Manager Fire Marshal cc : USR-1130 B.F.Y. LLC file planrvw. cor\usr1130 .wc 962076 09/30/96 13:28 27303 651 7702 MTN VIEW FIRE PD 7%02 -iAL-s-i- -- ----- APill. °'r MOUNTAIN VIEW FIRE=PROTECTION DI$TRIOT :. ' Adminu6afrve otFice. —_ i 9119 County Line Road•Longmont,CO 80501 C e ea (303)772-0710 Metro(303)6684404 FAX(303)651-7702 September 30, 1996 Mr. Pat Persichino Director of General Services Weld County 1400 N. 17th Avenue Greeley, CO 80631 RE: Plan Reviews for Fire Protection Requirements Dear Pat: Some issues have surfaced that I wanted to visit with you about and hopefully you can assist. The first is a referral received from the Planning Department on September 9, 1995 regarding USR-1130 (B.F.y. LLC) . It's tay understanding that they purchased existing buildings, one an office and another to be used as a warehouse. My response to the referral included some questions I needed answers on and another item dealt with fire hydrant requirements_ It wasn't until I returned a phone r11 to one of the. business owners, that I realized they were already occupying the buildings, without the fire district's requirements in place_ My second concern surfaced today, when I was told of two projects in the county that the fire district wasn't aware of. The first in a new storage unit complex under construction on Weld County Road 3, just North of Colorado Highway 7_- The party mentioning it to me thought a company by the name of Lyle Construction may be the owner. This project is going in without the fire district's opportunity to evaluate fire protection requirements. The second one that was brought to my attention is located East of I-25 on Weld County Road 38 and use to be known as Country View Day Care. I was told that the building is undergoing remodeling for the purpose of apartment rentals- Again, the fire district hasn't been advised of this project. I hope that you'll look into the above, and let me know whether building permits were issued and how the notification process can be improved. Thanks so much for your assistance in this matter! S•ijerely, William N. Bailey _ Fire Prevention Manager planxvw.cor\weldOlltr Skean f Slaw 5Wion2 S[e5o,r4 Statico 5Simian Malian] 9119 City Line Rd. VC]WCR13 P.O.B0f525 P.O.Bac11 10911 DalAin Putt P.O.Boz858 PA tat ma Longmont.CO larrinCrg.CO 2a9 Pamir Ave. RSWNWR Road Canes;CO GM 815111 91504 Mead.CO 55542 NSmL COB W ai095 ..CO eccn00 x.For9254 Erie.CO 50545 .COW Basta 09/30/96 12:33 TX/RX N0.51 2 2 II 6 sounnw MOUNTAIN VIEW FIRE PROTECTION DISTRICT Administrative Office: 9119 County Line Road •Longmont, CO 80501 E •� `IL��' 8 (303) 772-0710 Metro (303) 666-4404 FAX (303) 651-7702 VIEW bounty refining Dept October 3 , 1996 ACT O ' 1996 Ms . Kerri D. Keithley Department of Planning Services Weld County Administration Offices 1400 N. 17th Avenue Greeley, CO 80631 RE: USR-1130 KANGAROO EXPRESS Dear Kerri : I just wanted to let you know that I had another discussion with Bob Heil this a.m. with regards to our requirement for a plan review fee deposit and the urgency of submitting same. His response was that he would visit with Exploration Oil first . I advised him that no additional plan review work or associated communication would occur until the deposit has been received. There-fore, the information you've requested has been put on hold. Don' t hesitate to give me a call if you have any questions . Sincerely, William N. Bailey Fire Prevention Manager Fire Marshal planrvw. cor\usr-1130 .wc Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7 9119 Cnty Line Rd. 10971 WCR 13 P.O.Box 575 P.O.Box 11 10911 Dobbin Run P.O.Box 666 P.O.Box 40 Longmont,CO Longmont,CO 299 Palmer Ave. 8500 Niwot Road Lafayette,CO 600 Briggs 100 So.Forest St. 80501 80504 Mead,CO 80542 Niwot,CO 80544 80026 Erie,CO 80516 Dacono,CO 80514 962076 `"°°"r"'" MOUNTAIN VIEW FIRE PROTECTION DISTRICT F fu.x Administrative Office: 9119 County Line Road •Longmont, CO 80501 g J e (303) 772-0710 Metro (303) 666-4404 FAX (303) 651-7702 NEW October 14 , 1996 Ms . Kerri D. Keithley Department of Planning Services Weld County Administration Offices 1400 N. 17th Avenue Greeley, CO 80631 RE: USR-1130 B.F.Y. LLC (SITE SPECIFIC DEVELOPMENT PLAN) Dear Kerri : Please find enclosed a copy of the letter I asked the above to submit with regards to the outcome of my meeting with the three company representatives on October 11 . The conditions as stated in their letter are true and accurate. If you have any questions, please let me know. Also, I' ll look forward to hearing from you as to the outcome of this USR. Sincerely, William N. Bailey Fire Prevention Manager Fire Marshal cc B. F.Y. LLC file Larry Swisher, Owner/Partner, B. F.Y. LLC Weld County Planning Dept. OCT 16 1996 Y 4n4 planrvw.cor\usr1130 .wc Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7 9119 Cnty Line Rd. 10971 WCR 13 P.O.Box 575 P.O.Box 11 10911 Dobbin Run P.O.Box 666 P.O.Box 40 Longmont,CO Longmont,CO 299 Palmer Ave. 8500 Niwot Road Lafayette.CO 600 Briggs 100 So.Forest St. 80501 80504 Mead,CO 80542 Niwot,CO 80544 80026 Erie,CO 80516 Dacono,CO 80514 962076 44A:)-- v 962076 6 f DEPARTMENT OF PLANNING SERVICES I PHONE (970) 353-6100, EXT 3540 ig FAX (970) 352-6312 WELD COUNTY ADMINISTRATIVE OFFICES C. 1400 N. 17TH AVENUE GREELE Y, COLORADO 80631 COLORADO DATE: August 28, 1996 CASE NUMBER: USR-1130 TO WHOM IT MAY CONCERN: Enclosed is an application from B.F.Y. LLC for a Site Specific Development Plan for a Special Reyiew Permit for a Delivery Company with Warehousing for Customers and Recreational Vehicle Storage. The parcel of land is described as Lot A of RE-1727, located in part of the SW4 of the NW4 of Section 5, T1 N, R67W of the 6th P.M., Weld County, Colorado. The location of the parcel of land for which this application has been submitted is east and adjacent to Weld County Road 15, 1/4 mile south of Colorado State Highway 52. The application is submitted for your review and recommendation. Any comments or recommendation you consider relevant to this request would be appreciated. Your prompt reply will help to facilitate the processing of the application. Please reply by September 18, 1996, so that we may give full consideration to your recommendation. Please call, Kerri D. Keithley, if you have any questions. Check the appropriate boxes below and return to our address listed above. 1. We have reviewed this request and find that it does/does not comply with our Comprehensive Plan for the following reasons. 2. We do not have a Comprehensive Plan, but we feel this request is/is not compatible with the interest of our town for the following reasons. 3. We have reviewed the request and find no conflicts with our interests. 4. A formal recommendation is under consideration and will be submitted to you prior to 5. of Please refer to the enclosed letter. ' g • Signed: 41144.11241144.11208-11-talia Agency: e(,t M.l,t,(,„ VvJO R i 1� Date: I - ( 0 - (to 962076 mEmoRAnDum Eli 9€ Kerri Keithley, Current Planner September 11, 1996 To Date COLORADO Don Carroll, Project Coordinator alb From Subject: USR-1130, B.F.Y., LLC The Weld County Public Works Department has reviewed this proposed; the following comments are recommended to be a part of any approval: 1. WCR 15 is being upgraded and paved. This funding for construction has been acquired through a grant applied for by the County and the Town of Dacono. 2. The applicant needs to place a 15" CMP x 30'minimum culvert at the entrance. Please refer to Appendix B, Road Access, Sheet No. 1, Commercial Access Standards for culvert installation and turning radiuses under Ordinance 180 of the Weld County Public Works Department policies. Please see attached sheet. 3. The operator will be responsible for dust control on site. The following dust control agents are approved for use by the Weld County Health Department: a. Portable water or natural ground water b. Magnesium chloride c. Calcium chloride cc: Commissioner Hall USR-1130 plant Weld County Planning DePt. SEP 12 199®6 RECEIVED 962076 APPENDIX "B" APPENDIX "B" - ROAD ACCESS ACCESS SKETCH #1 COMMERCIAL ACCESS ROAD STANDARDS. Y. aM E:GATE HOSE COURSE COUNTY N(INCOVER OOR INEroNMENUATIOYS ROAD PAVEMENT - SHOULDER I\ DOWN GRADIENT 9.OPE FOR / / LINE___—FLOW LIh NININIIM OF l0 /! Si>yTyi`tyTyT�),: R�`iyy``i`>`>``v y0i0i YYY`3)`>)/r3> iy`)QUO i t,`i0i\y/t //�/VTyT�/��i /�>\��`�Ni^ ��/%\/���� n/ /\�T�//%/�v/>Vy��?��/NiNi� Ty,`� ,����iyT`//$ / /\ \7/i\T�/)5%/\/\�yT�/ \ \5Ty / /% ✓� r �/Tp✓T//`/TrT �?�YT/�rTYT/T��T�TYT�/`� �`� �/� y�y�y�yT`i�/`��O�jy�4//\/\5/!/;CS/k/` NOTE: MIN. PIPE DIAMETER IS I5. CROSS-SECTION LARGER SIZES MAY BE NEEDED TO MEET DRAINAGE REQUIREMENTS. A-A • O. 24 MIN _ V VV Fe. MIN 21 I /D I \7 COMMERCIAL 8 MIN. ACCESS ' ROAD CONCRETE HEADWALL NOTE: LIGHT COMMERCIAL 24' MIN PRECAST OR CAST IN PLACE 20' RADIUS I 40 I._F. OF I5 DIA. CULVERT OR AS REQUIRED 1 A ,CONCRETE HEADWALL HI// '1 r j FLOW LINE A 40' RADIUS GRAVEL OR PAVED SURFACE \\ AS REQUIRED. SHOULDER PAVEMENT A j no WELD COUNTY ROAD o 1 PLAN VIEW t___..-- A NOTE'. ADDITIONAL WIDENING GE COUNTY ROAD TURNING LANES MAD DE REQUIRED. B-I 2419818 8-1472 P-559 12/21/94 02:34P PG 34 OF 46 941002 962076 Weld County Planning De Ag '& fE1ORAfDUM OCT 0 1 1996 ���'��• Kerri D. Keithley it. �" Weld County Planning Sept er 9 To Date <: rb COLORADO Trevor Jiricek, Supervisor, Environmental Protection Servic From Subject Case Number: USR-1130 Name: B.F.Y. LLC PT SW4 OF NW4 of Section 5, Township 1 North, Range 67 West Environmental Protection Services has reviewed this proposal; the following conditions are recommended to be part of any approval: 1. All liquid and solid wastes shall be stored and removed for final disposal in a manner that protects against surface and groundwater contamination. 2. No permanent disposal of wastes shall be permitted at this site. 3. Waste materials shall be handled, stored, and disposed in a manner that controls fugitive dust, blowing debris, and other potential nuisance conditions. 4. Fugitive dust shall be controlled on this site. 5. The maximum permissible noise level shall not exceed the, commercial limit of 60 db(A) , as measured according to 25-12-102, Colorado Revised Statutes. 6. The existing septic system shall be reviewed by a Colorado Regulated Professional Engineer. The review shall consist of observation of the system and a technical review in order to determine if the system is adequately sized and constructed to handle the proposed hydraulic load. The review shall be submitted to the Environmental Protection Service Division of the Weld County Health Department. In the event the system is not found to be adequate, the system shall be repaired or enlarged in accordance with Weld County I.S.D.S. Regulations. TJ/vh.1108 962O"x'6 FIELD CHECK �y FILING NUMBER: USR-1130 DATE OF INSPECTION: /G-�' - / 6 APPLICANT'S NAME: B.F.Y. LLC CURRENT PLANNER: Kerri D. Keithley REQUEST: Site Specific Development Plan for a Special Review Permit for a Delivery Company with Warehousing for Customers and Recreational Vehicle Storage LEGAL DESCRIPTION: Lot A of RE-1727, located in part of the SW4 of the NW4 of Section 5, Ti N, R67W of the 6th P.M., Weld County, Colorado LOCATION: East and adjacent to Weld County Road 15, 1/4 mile south of Colorado State Highway 52 LAND USE: N �9 _ JAI EQ — Jf aj s O rsc, w QLLCe ZONING: N A(Agricultural) E A(Agricultural) S A(Agricultural) W A(Agricultural) COMMENTS: p etie— A4-13 J-cam 962076 2/98 12:50 '$`S0S _M TN 7702 __ .. .. PD .. . . " " '- L - _ . N VIEW FIRE apoz ;.. __ . .w kr '_<. . `- .MOUNTAIN VIEW FIRE PROTECTION DISTRICT .` .:. p®� Aa Office:'PY� 3119 County'line Road-Longmont,CO 80501 eta (303)772-0710 iloiro(303)666-4404 FAX(303)651-rro2 ..: +.i.S_,r r•. --ram . ''- . - ._ - f • _. _ _ • - •• "€996 • -. Bo1i Heil • _ -- Kanga?oohs- _ • :-vacono;e= 514 _ ,_ b 80 _ DeefM�_r a '' __ A walk_ -through of the facility located at 70:WCR 55 bas faulted in a change of the _ - - _.-._.-.__ .:._.. _ 57 - - ' ': �- - eats Chief�� Ba1�ag had'vui>s�ly made: Based:on my review, 1 fond drat. ai___:,_ _ .- ' will not be needed_ My on1 conceni wou13 stoiagctalk as well as a fire darn, system, Y e. be Iri the storage facilrO,.paII°tz�d ° be maintained a floor level. • ShonldyouliaVe any guestionsnr comments,Oleasefeel£eee:to contact me_ . r .... .. lvlark A.la rle- -- .4ctmg;Finc3vfaal . ML dce Weld—. CaGmtY Plannin . At • • - Jc111t1hriaVra,Coldwell Rm?ke 9.Da xe keit}1ley,STeld_Co .-m. - N - NO 1996 —�tla.a _ Siam s-. . ddgn5 - ffi® pi p - - SWim2 ' - Pfl 0911 tt. - 1 natal Fan r.O.scaa PA-Qa4O - 9NOfl9l & -Ad 109n M16i 13 9P fl' A'. .- BSOO'a'.c*Mad - .. We/am9.CO KO Sa]55 100 Si elest St. - lcr:�nfiw,m lmpAp14C0 .: - �9vr ewraw-- .. ',art+-m emlc 0.800' 80'514 ' -_-- - -• uue.eoeose2 -._.._.wwa.cae05ct_.__.;_ -- -- —_ -- - °Drat —.. � - ... - — - 11/12/96 11:35 TX/RX N0.541$6rIOVAI L12 II Hello