Loading...
HomeMy WebLinkAbout851182.tiff SSINS No. : 6835 IN 85-86 UNITED STATES NUCLEAR REGULATORY COMMISSION ; � 1�v' OFFICE OF INSPECTION AND ENFORCEMENT ' N0V 91985 WASHINGTON, :, r .C. I W tELEV. COLO. IE INFORMATION NOTICE NO. 85-86: LIGHTNING STRIKES AT NUCLEAR POWER GENERATING STATIONS Addressees: All nuclear power reactor facilities holding an operating license (OL) or a construction permit (CP). Purpose: • This notice is provided to alert recipients of a potentially significant problem of reactor trips and instrument damage caused by lightning strikes. It is expected that recipients will review the information for applicability to their facilities and consider actions, if appropriate, to preclude a similar problem occurring at their facilities. However, suggestions contained in this notice do not constitute NRC requirements; therefore, no specific action or written response is required. The NRC is continuing to evaluate pertinent information. Recipients of this notice will be notified of additional information or if specific actions are required. Description of Circumstances: A number of plant trips and instrumentation problems attributable to lightning have occurred over the past 6 years. Since solid state circuitry designs are being increasingly employed in safety related systems, the impact of lightning induced line surges on those circuits is emphasized in this notice. Descrip- tions of several of the more significant events are presented below. Events involving lightning strikes of switchyards and the consequential impact on power distribution systems are not covered by this notice. However, INPO SER 76-84 covers this latter subject as well as summarizing earlier INPO documents dealing with lightning strikes at nuclear power plants. Zion Power Station Units 1 and 2 On August 17, 1979, both units tripped simultaneously during a severe lightning storm. Investigation indicated that a lightning strike in close proximity to the plant caused either a momentary surge or interruption in the ac power supply circuits to the rod control power supply cabinets. This transient tripped the overload protection devices for the dc power supply cabinet, resulting in a power interruption to the control rod stationary gripper coils, 8511010020 851182 Arimni"b5/8s IN 85-86 November 5, 1985 Page 2 of 4 which caused the rods to drop into the core. The resulting high, negative flux rate initiated the reactor trip signal . Tests verified that noise induced on the ac input to one power supply would actuate the overvoltage protection trips on the main and auxiliary power supplies. In addition to the noise spikes, one Unit 2, 24-V positive power supply was damaged by the lightning strike and had to be replaced. The following corrective actions were initiated: o The control rod system neutral was isolated from the station ground. o The overvoltage protection trip setting was changed from 27 to 29 V. o A low-pass filter was installed on the input to each 24-V positive power supply. o A volt trap (a voltage suppressor circuit designed to reduce large voltage surges and noise induced by lightning strikes) was installed across the 50-ohm motor generator neutral resistor. o A volt trap was installed across the power feed to the auxiliary power supply. o The power feed for the auxiliary power supply was changed from the 480-V system to the control rod drive (CRD) motor generators. Zion Unit 2 experienced additional reactor trips attributed to lightning on April 3 and July 16, 1980, before the above listed corrective actions were implemented. In these cases it was determined that the transient tripped the overload protection devices, as was the case in the trip of both units on August 17, 1979. However, no power supplies or other equipment were damaged during the latter two trips. Again, on December 2, 1982, Zion Unit 2 reactor tripped from 100% power during an electrical storm. It was concluded that lightning induced a disturbance in the electrical system causing a reactor trip from a generator trip. Additional lightning protection for the containment building was provided and the static wire associated with the 345-kV line was isolated from the power station structural steel. - Salem Power Station Unit 1 On June 8, 1980, the reactor tripped during an electrical storm. Lightning struck at the south penetration area of reactor containment causing a transient on seven main steam pressure transmitters. Two of these pressure transmitters were damaged and had to be replaced. The transient caused a high steam line pressure differential reactor trip signal and a safety injection signal . The licensee believes the lightning strike hit main steam vent pipes which extend above the penetration area roof and the surge was carried into the building via piping connections. IN 85-86 November 5, 1985 Page 3 of 4 Kewaunee Power Station On August 19, 1980, two of four instrument busses lost power during an electri- cal storm. This resulted in a spurious safety injection (SI) actuation signal , and the unit tripped from full power. In addition to inducing the instrumenta- tion transients, the inverter fuses were blown. These fuses were replaced, and no other evidence of equipment failure was observed. Byron Power Station Unit 1 On July 13, 1985, when lightning struck the Unit 1 containment, the reactor tripped from approximately 11% power because of induced voltage surges in instrument and control cables in one of four containment penetration areas. The induced voltage caused failure of four rod drive power supplies, including 1 redundant pair. The failure of the redundant supplies resulted in 10 control rods dropping into the core. A power range negative-flux-rate reactor trip resulted from the rod insertion. In addition to the reactor trip, damage occurred to 30 plant instruments. The following systems were affected by the damaged instrumentation: protection channel II, one train of the 48-volt power supply for the solid state protection system, the meteorological tower, control rod drive, and loose-parts monitoring. A review of cable routings showed that a significant common denominator existed in containment penetrations. All damaged instruments were associated with cables passing through penetrations located in one containment region. In addition to the damaged instrumentation, the lightning damaged a significant amount of security equipment. The licensee determined that an improved lightning protection system was required to prevent recurrence of a similar incident. By installing copper conductors, external to containment, from the roof mounted lightning rods directly to ground rods in the earth, a low impedance path to ground was provided for future lightning strikes. This modification is similar to the Zion modification described above. Arkansas Power Station Unit 2 On August 5, 1985, the reactor tripped from 100% power on a low departure-from- nucleate-boiling ratio (DNBR) signal as the result of a lightning strike transient induced in two of the core protection system channels. The licensee' s followup investigation revealed no damage to the plant' s electrical equipment ' or instrumentation measuring systems. IN 85-86 November 5, 1985 Page 4 of 4 No specific action or written response is required by this information notice. If you have any questions about this matter, please contact the Regional Administrator of the appropriate regional office or this office. £4threctDivisEmergency Preparedness and Engineering Response Office of Inspection and Enforcement Technical Contacts: Ray S.790-5593 y2) ov Vincent D. Thomas, IE (301) 492-4755 Attachment: List of Recently Issued IE Information Notices Attachment 1 IN 85-86 November 5, 1985 LIST OF RECENTLY ISSUED IE INFORMATION NOTICES Information Date of Notice No. Subject Issue Issued to 85-85 Systems Interaction Event 10/31/85 All power reactor Resulting In Reactor System facilities holding Safety Relief Valve Opening an OL or CP Following A Fire-Protection Deluge System Malfunction 85-84 Inadequate Inservice Testing 10/30/85 All power reactor Of Main Steam Isolation Valves facilities holding an OL or CP 85-83 Potential Failures Of General 10/30/85 All power reactor Electric PK-2 Test Blocks facilities holding an OL or CP 85-82 Diesel Generator Differen- 10/18/85 All power reactor tial Protection Relay Not facilities holding Seismically Qualified an OL or CP 85-81 Problems Resulting In 10/17/85 All power reactor Erroneously High Reading facilities holding With Panasonic 800 Series an OL or CP and Thermoluminescent Dosimeters certain material and fuel cycle licensees 85-80 Timely Declaration Of An 10/15/85 All power reactor Emergency Class Implementa- facilities holding tion Of An Emergency Plan, an OL or CP And Emergency Notifications 85-17 Possible Sticking Of ASCO 10/1/85 All power reactor Sup. 1 Solenoid Valves facilities holding an OL or CP 85-79 Inadequate Communications 9/30/85 All power reactor , Between Maintenance, facilities holding Operations, And Security an OL or CP; research Personnel and nonpower reactor facilities; fuel fabrication and processing facilities OL = Operating License CP = Construction Permit SSIN No. : 6820 OMB No. : 3150-0011 118 M: r` ..,... ..,_,S rr UNITED STATES 11711� 2' 1 NUCLEAR REGULATORY COMMISSION j1 �flV 4-9 '. OFFICE OF INSPECTION AND ENFORCEM/ WASHINGTON, D.C. 20555 t, GRELLLv, (_�.L'LO. November 5, 1985 IE BULLETIN NO. 85-02: UNDERVOLTAGE TRIP ATTACHMENTS OF WESTINGHOUSE DB-50 TYPE REACTOR TRIP BREAKERS Addressees: All power reactor licensees and appljcants. Purpose: The purposes of this bulletin are: to inform all power reactor licensees and applicants of recent reactor trip breaker reliability problems, to assure that. licensees of currently operating Westinghouse power reactor facilities that have not yet installed the automatic shunt trip modification are performing undervoltage trip attachment (UVTA) force margin testing of the reactor trip breakers (RTBs) , and to clarify the "OPERABILITY" requirements related to RTBs. Description of Circumstances On October 29, 1985, at 13: 57 EST the D. C. Cook Nuclear Station Unit No. 2 tripped from approximately 80% of full power. The reactor trip was triggered by a spurious indicated low flow condition in loop 2. The trip signal originated from the reactor coolant pump breaker contacts. Following the reactor trip condition it was immediately discovered that the reactor trip breaker associated with Train "A" reactor protection system (RPS) did not open, and the trip function was accomplished by only the "6" train RT6 (which subsequently on November 3, 1985 failed to pass the UVTA force margin test). Two of four safety-related feedwater isolation valves did not close because the actuation signal to close should have originated from contacts in the failed Train "A" circuit breaker. The remaining two feedwater isolation valves did operate properly because the train "B" reactor trip circuit breaker opened and triggered the isolation action to these two valves. Also, the feedwater regulating valve in each loop was closed by the "B" train RTB signal . Subsequent action by the licensee included quarantining the failed Train "A" reactor trip breaker. This was facilitated by opening the circuit breakers to the motor-generators. Investigation into the event by the licensee and Westinghouse attributed the failure of the Train "A" reactor trip breaker to a faulty undervoltage trip attachment (UVTA) which did not provide enough lifting force to the breaker trip bar. The breaker is identified as the Westinghouse Type DB-50. 851 1050230 tad mTq"I]SISS IEB 85-02 November 5, 1985 Page 2 of 4 Subsequent to the October 29, 1985 incident, all RTBs at the DC Cook station were tested. UVTA trip force margin testing of the Unit 2 "B" breaker on November 3, 1985 identified degradation of the margin below the 20 ounce specified margin (i .e. , the requirment for the UVTA is to exert 50 ounces of force, 30 ounces to move the trip bar and 20 ounces for margin). The significance of the degradation of the UVTA attachment of the "B" breaker, in conjunction with the failure of the "A" breaker to trip on October 29, 1985 renews concern for common mode failures that could potentially lead to an ATWS event. Background: As a result of the February 22 and 25, 1983 Salem anticipated transients without scram (ATWS) events, the NRC issued IE Bulletin 83-01 and formed a task force to assess the generic implications of these events. On March 11, 1983, Southern California Edison reported that three GE-manufactured RTBs on San Onofre Unit 2 and one on Unit 3 failed to open during testing of the UVTA. As a result of these failures, the NRC issued IE Bulletin 83-04. The task force' s actions resulted in the issuance of NUREG-1000, "Generic Implications of the ATWS Events at the Salem Nuclear Power Plant" and Generic Letter 83-28, delineating the procedural and plant changes required. Findings in NUREG-1000 were based, in part, on assurances that improved maintenance of the breakers would improve the reliability of the UVTAs to an acceptable level for the short term, after which the longer term corrective actions would be impTemented. The longer term corrective actions were directed by NRC Generic Letter 83-28. These actions had two major aspects related to the RTB/UVTAs: (1) the installation of a plant modification that provides for the automatic activation of the shunt trip coil of the RTB for any automatic reactor trip signal , and (2) reliability improvements in the RTB/UVTA based upon UVTA life testing by the vendor. The life test formed the basis for a UVTA replacement interval of 1250 cycles and a lubrication interval of 200 cycles. The recent failures at D. C. Cook Unit 2 involved RTBs that were refurbished by the vendor only 4 months previously, including the installation of new UVTAs. The Unit 2 RTB "A" (that failed on October 29, 1985) had experienced only about 75 operations on the UVTA. The Unit 2 RTB "B" (that failed on November 3, 1985) had experienced about half as many operations on the UVTA. In this short time, both UVTAs suffered a serious reduction of their trip output force. The Westinghouse specification for the DB-50 breaker specifies a minimum total force output of the UVTA to be 50 ounces. This total force output provides a force margin of 20 ounces above the maximum force required to trip the breaker. The UVTA trip force margin is measured by temporarily hanging a weight on the trip bar of the breaker and actuating ( i . e. , de-energizing) the UVTA. Many plants include a force margin test as part of the 18-month surveillance actions. If the weight is less than the UVTA margin, the UVTA will consistently trip the breaker. If the weight is greater than the UVTA margin, the UVTA will consistently not trio the breaker. If the weight approximates the UVTA margin, the UVTA IEB 85-02 November 5, 1985 Page 3 of 4 will not be consistent in its ability to trip the breaker during the test. At D.C. Cook, three tests at each weight were used to assure valid test results. Testing of RTB "A" indicated that the UVTA force margin had fallen to 5 ounces or less. Testing of the RTB "B" indicated that the UVTA force margin was no longer as great as 20 ounces. If the UVTA does not have adequate margin, it is unacceptable and requires replacement or maintenance. The root cause of the lost force margin is not known at this time; laboratory failure analysis of the failed UVTAs is being arranged. It is believed that re-lubrication may temporarily restore some of the lost force. NRC preliminary information is that 9 Westinghouse PWRs have not yet implemented the automatic shunt trip modification. As shown in the attachment, only 3 of these plants are currently operating; namely: Kewaunee, Beaver Valley Unit 1, and Turkey Point Unit 4. REQUIRED ACTIONS FOR LICENSEES OF CURRENTLY OPERATING WESTINGHOUSE PWR FACILITIES THAT HAVE NOT YET IMPLEMENTED THE ACTUATION OF RTB SHUNT TRIB COIL ON ALL AUTOMATIC REACTOR-TRIP SIGNALS 1. Perform a test of the UVTA of each RTB that is in service to determine that adequate force margin exists, as soon as practical , but not to exceed 7 days of receipt of this bulletin. With a weight of 20 ounces attached to the trip bar, the UVTA by itself must trip the RTB three times in succession. This test shall be performed with the UVTA and breaker in "as found" conditions, prior to any lubrication or other maintenance. Any occurrence of a force margin less than 20 ounces defines an unacceptable UVTA. 2. Modify the monthly test procedure for the Reactor Protection System to add conducting the UVTA force margin test, prior to any lubrication or adjustment of the UVTA, for each RTB that is in service. This test is normally conducted on one RTB each month, i. e. , two months between tests on the same RTB. If an RTB fails the UVTA force margin test, the redundant RTB is to be similarly tested within 8 hours. This procedural modification should be in place for the next such test after receipt of this bulletin • and remain in force, until the automatic shunt trip modification is fully implemented. 3. Provide written instructions to the plant operating staff, within 7 days of receipt of this bulletin, requiring that: (a) The content of this bulletin be reviewed by each licensed operator at the start of his/her next duty shift. (b) A reactor trip breaker shall be declared INOPERABLE, if the UVTA either does not successfully pass the force margin test or otherwise may not be capable of performing its intended safety function. (c) Plant operation with either RTB INOPERABLE shall continue only as provided for in the plant Technical Specifications. IEB 85-02 November 5, 1985 Page 4 of 4 (d) The NRC is to be notified via the emergency notification system within 4 hours of any RTB being declared inoperable. 4. Provide a written report to the NRC within 30 days of receipt of this bulletin, which discusses the specific actions taken pursuant to this bulletin and the results thereof. Should a licensee determine that any action requested by this bulletin jeopardizes overall plant safety, the NRC should be notified of that fact and provided with appropriate justification for not implementing the requested action. Such notification shall be made within 7 days of receipt of this bulletin. The written reports shall be submitted to the appropriate Regional Administrator under oath or affirmation under provisions of Section 182a, Atomic Energy Act of 1954, as amended. Also, the original copy of the cover letters and a copy of the reports shall be transmitted to the U. S. Nuclear Regulatory Commission, Document Control Desk, Washington, DC 20555 for reproduction and distribution. This request for information was approved by the Office of Management and Budget under a blanket clearance number 3150-0011. Comments on burden and duplication may be directed to the Office of Management and Budget, Reports Management, Room 3208, New Executive Office Building, Washington, D. C. 20503. If you have any questions regarding this matter, please contact the Regional Administrator of the appropriate NRC Regional Office of one of the technical contacts listed below. /4^James Taylor, Director offic f Inspection and Enforcement Technical Contacts: J. T. Beard, NRR (301) 492-7465 V. Thomas , IE (301) 492-4755 Attachments: 1. Facilities Without Automatic Shunt Trip Installed 2. List of Recently Issued IE Bulletins Attachment 1 IEB 85-02 November 5, 1985 Page 1 of 1 FACILITIES WITHOUT AUTOMATIC SHUNT TRIP INSTALLED FACILITY REMARKS 1. .Kewaunee Install in February 1986 2. Beaver Valley Install in May 1986 3. Turkey Point 4 Install in January 1986 4. Sequoyah 2 Currently 5/D; install Spring 1986 startup 5. Sequoyah 1 Currently S/D; will install before startup 6. North Anna 1 Currently 5/D; will install before startup 7. Byron 1 Currently S/D; will install before startup 8. Zion 2 Currently S/D; will install before startup 9. Cook 2 Will install prior to startup Attachment 2 IEB 85-02 November 5, 1985 LIST OF RECENTLY ISSUED IE BULLETINS Bulletin Date of No. Subject Issue Issued to 85-01 Steam Binding of Auxiliary 10/30/85 All nuclear power Feedwater Pumps facility licensees and CP holders. 84-03 Refueling Cavity Water Seal 8/24/84 All power reactor facilities holding an OL or CP except Fort St. Vrain 84-02 Failures Of General Electric 3/12/84 All power reactor Type HFA Relays In Use In facilities holding Class 1E Safety System an OL or CP 84-01 Cracks In Boiling Water 2/3/84 All BWR facilities Reactor Mark I Containment with Mark I contain- Vent Headers ment and currently in cold shutdown with an OL for Action and All other BWRs with an OL or CP for information 83-08 Electrical Circuit Breakers 12/28/83 All power reactor With An Undervoltage Trip facilities holding Feature In Use In Safety- an OL or CP Related Applications Other Than The Reactor Trip System 83-07 Apparently Fraudulent 12/09/83 Same as IEB 83-07 Sup. 2 Products Sold By Ray Miller, Inc_ 83-07 Apparently Fraudulent 10/26/83 Same as IEB 83-07 Sup. 1 Products Sold By Ray Miller, Inc. OL = Operating License CP = Construction Permit Hello