ORDINANCE NO. 119-C
IN THE MATTER OF AN AMENDMENT TO ORDINANCE NO. 119, WELD COUNTY BUILDING
CODE ORDINANCE, REVISING CERTAIN PROCEDURES, TERMS, REQUIREMENTS, AND
o U INCORPORATING BY REFERENCE CERTAIN PORTIONS OF THE UNIFORM BUILDING CODE,
m 0 1985 EDITION; UNIFORM MECHANICAL CODE, 1985 EDITION; NATIONAL ELECTRICAL
o CODE, 1984 EDITION, UNIFORM PLUMBING CODE, 1985 EDITION; UNIFORM CODE FOR
o THE ABATEMENT OF DANGEROUS BUILDINGS, 1985 EDITION; THE UNIFORM SWIMMING
4 POOL CODE, 1985 EDITION, AND APPENDICES TO ALL UNIFORM CODES.
ow
03
o a BE IT ORDAINED BY THE BOARD OF COUNTY COMMISSIONERS OF WELD COUNTY,
q COLORADO:
0
U
via WHEREAS, the Board of County Commissioners of Weld County, Colorado,
o pursuant to Colorado statute and the Weld County Home Rule Charter, is
.max
vested with the authority of administering the affairs of Weld County,
in a
co C.)
z
Colorado, and
M H
N E WHEREAS, the Board of County Commissioners has the power and authority
a
co a under the Weld County Home Rule Charter and Article 28 of Title 30 CRS, to
ow
k adopt building codes for the unincorporated areas of the County of Weld, and
mz
cov < WHEREAS, the Board of County Commissioners of Weld County, Colorado,
aadopted Ordinance No. 119, with subsequent amendments, the Weld County
Building Code Ordinance, establishing a comprehensive revision of the
M
20 co
building code requirements for the unincorporated areas of the County of
RI G+
Weld, and
WHEREAS, said Ordinance No. 119, as amended by Ordinances 119-A and
119-B, is in need of revision, updating, and clarification with regards to
procedures, terms, and requirements therein.
NOW, THEREFORE, BE IT ORDAINED by the Board of County Commissioners of
Weld County, Colorado, that said Ordinance No. 119, as amended, is amended
by the addition, revision, and renumbering of various sections, which shall
read as follows:
850707
1l . 1 tr '1_ , 1 c_,'. l - jar 1 :- - 1 i !_. .
AMEND SECTION 10.4 by:
no OV Delete "30-38-201 "and replace with" 30-28-201" Delete "1973".
0
ro O AMEND SECTION 20. 1 by:
A Delete "1982" and replace with "1985".
oW
S DELETE SECTION 20. 1.2
o fZ
4/1- 0
AMEND SECTION 20.2 by:
wDelete "1982" and replace with "1985".
yr 0
AMEND SECTION 20.2.1 by:
0
~ a Delete "1982" and replace with "1985". Add "unless the walls of the
crawlspace are insulated" to the last sentence of the text.
co u
Z AMEND SECTION 20.2.2 by:
H
� W
N E Delete "Paragraph 4" replace with "(f)".
~ a AMEND SECTION 20.4 by:
o a
Delete "1982" and replace with "1985"
Le) w
r--
re) Z AMEND SECTION 20.5 by:
N4
p, Delete "1982" and replace with "1985".
Ua
a AMEND SECTION 20.5.8 by:
N N
o m Delete "(a)" and replace with "(c)".
ri
p., AMEND SECTION 20.6 by:
Delete "1982" and replace with "1985".
RENUMBER SECTION 20.9.6.7 TO SECTION 20.9.7.
RENUMBER SECTION 20.9.6.8. TO SECTION 20.9.8.
RENUMBER SECTION 20.9.6.9 TO SECTION 20.9.9.
RENUMBER SECTION 20.9.6.10 TO SECTION 20.9.10.
RENUMBER SECTION 20.9.6.11 TO SECTION 20.9.11.
2
ADD NEW SECTION 20.10 TO READ:
o U 20. 10 Manufactured Home Installation Standards. Any
manufactured home located in or relocated within Weld
en 0 County shall meet the following installation standards.
The Building Official may authorize the use of different
materials or methods which will accomplish substantially
a
o W the same result.
0
o a 20. 10. 1 Blocking. Blocking shall be placed under each main
vt w
a manufactured home frame member for the full length of the
O manufactured home at maximum intervals of eight feet
(8') . End of piers shall not be farther than five feet
�r a (5') from the end of the manufactured home. Wood
xi railroad ties are not acceptable materials for blocking.
0
rig
rx 20. 10.2 Base. Footers shall consist of poured concrete pads a
minimum of six inches (6") thick and a minimum of sixteen
c U inches (16") by sixteen inches (16") square. Two pieces
2 of minimum #4 rebar (1/2") shall be placed in each
j direction before pouring. The bottom of the solid
E concrete base must be a minimum of twelve inches (12")
rz below undistrubed ground surface.
0z
0
20. 10.3 Piers. Piers shall be constructed of one (1) or more
Ln 1=4
eight inch (8") by eight inch (8") by sixteen inch
z (16") ("celled") concrete blocks or approved equivalent
ev materials. Said blocks shall be placed over the base in
0
such a manner that the sixteen inch (16") dimension is at
a
W g a ninety degree (90°) angle to the main frame of the
manufactured home and shall be centered on the base with
N en the cells in a vertical position.
o, en
a 0
r 0 20.10.4 Caps. Each pier shall be topped (capped) with an eight
PQ inch (8") by sixteen inch (16") by four inch (4") solid
concrete block or the equivalent.
20. 10.5 Wood Wedging. Wood wedging (shims) shall be driven
tight between each pier cap and the main frame member of
the manufactured home if necessary. No more than four
inches (4") of the thickness of a type of wood approved
by the Building Official shall be permitted. The width
of the wedge shall provide a minimum of eight (8) lineal
inches of bearing surface between the pier cap and the
main frame of the manufactured home.
20. 10.6 Tie downs. Tie downs shall meet the following
standards:
20. 10.6.1 Ties shall consist of galvanized steel strapping
(1-1/4 x .035") with a minimum breaking strength of four
thousand seven hundred fifty pounds (4,75011) or ties
shall consist of galvanized steel cable 7/32" x 7 x 7 or
1/4" 7 x 19) with a minimum breaking strength of four
3
thousand eight hundred pounds (4,800#) . The Building
N 0 Official may approve alternate materials of equal
o strength.
'r o
U 20.10.6.2 Each frame tie shall connect the main frame of the
manufactured home to an anchor located outside the
o W opposite main frame member. A frame tie shall be located
o within two feet (2') of each end of the manufactured
o rx home. Any manufactured home fifty feet (50') or less in
4.4
length shall have a minimum of four (4) frame ties. Each
frame tie shall be tightened snug to an anchor.
O
V
d a 20.10.6.3 Ground anchors for securing the ties shall be
0 of the following types: screw augers, expanding anchors,
o concrete deadmen, or equivalents approved by the Building
An
y n
y type of ground anchor used shall have a
minimum holding power of four thousand eight hundred
ul
m U pounds (4,80011) . Ground anchors shall be placed at a
2 minimum depth of four feet (4') or at a greater depth if
w determined necessary by the Building Official.
N
20.10.6.4 When strapping or cables are connected to turn
buckles or to yoke-type fasteners and tensioning devices,
o
w connections shall be made so that the overall strength of
`^ the tie downs is not reduced. Turnbuckles shall be
en z one-half inch (1/2") galvanized steel or the equivalent
o
as approved by the Building Official. Hook-ends or
0 open-eyes are not permitted as connection devices. "Eye
U a and eye" or "draw and draw" type turnbuckles are
acceptable as connection devices. Where cable is
d utilized and looped for connection, ends shall be secured
c M with a minimum of two (2) cable clamps with the nuts
o placed on the live side of the cable. Materials and
connecting devices of equivalent strength may be utilized
upon approval by the Building Official.
20.10.7 Skirting. Skirting shall be provided around the bottom of
the manufactured home to ground level. Skirting shall be
made of a material which is approved for exterior use by
the Uniform Building Code.
20.10.8 Setbacks. Setbacks from other buildings or structures
shall be as specified in Table No. 5-A of the Uniform
Building Code. Manufactured homes shall fall within
Group R-3 in this table. Zoning setbacks are identified
on the front of the Building Permit and shall be complied
with when locating the manufactured home on the property.
20.10.9 Dwelling Unit. Every manufactured home used as a
dwelling unit shall be provided with a kitchen sink.
Every manufactured home used as a dwelling unit shall be
provided with a bathroom equipped with facilities
consisting of a water closet, lavatory, and either a
bathtub or shower. Each sink, lavatory, and either a
4
bathtub or shower shall be equipped with hot and cold
o U running water necessary for its normal operation. Every
o home shall be provided with a smoke alarm installed
0 according to the Weld County Building Code.
U
A 20. 10. 10 Installation on Basements. Units which have a floor
W o joist system approved to be put on a regular foundation
O 3 will not need to be engineered unless installed in an
o a area where we require all foundations to be engineered
mw due to soil conditions. However, rebar shall be
installed in the foundation according to County
U requirements. Units which are designed to be supported
a on four (4) rails shall submit an engineered foundation
and support system design.
r 20.10.11 Installation on Other Than Basements. Units which
have a floor joist system approved to be put on a regular
ul a
m u foundation system must be installed according to
manufacturers and County's specifications. This would
\ W consist of an outside perimeter footing and foundation
N F with support footings and a wall in the center or
concrete pads and vertical supports. The unit must be
anchored to the foundations. Units which are designed to
mao N be supported by the four (4) rails must be installed
vi w according to the enclosed standards. If the
o manufacturer's specifications call for closer spacing of
Z
N the support piers then that standard must be followed.
W g AMEND SECTION 30.2.2 TO READ:
a
Additions, Alterations or Repairs. Additions,
r-
al en alterations or repairs may be made to any building or
2 o structure without requiring the existing building or
m w structure to comply with all the requirements of this
code, provided the addition, alteration or repair
conforms to that required for a new building or
structure. Additions or alterations shall not be made to
an existing building or structure which will cause the
existing building or structure to be in violation of any
of the provisions of this code nor shall such additions
or alterations cause the existing building or structure
to become unsafe. An unsafe condition shall be deemed to
have been created if an addition or alteration will cause
the existing building or structure to become structurally
unsafe or overloaded; will not provide adequate egress in
compliance with the provisions of this code or will
obstruct existing exits; will create a fire hazard; will
reduce required fire resistance or will otherwise create
conditions dangerous to human life. Any building so
altered, which involves a change in use or occupancy,
shall not exceed the height, number of stories and area
permitted for new buildings. Any building plus new
additions shall not exceed the height, number of stories
and area specified for new buildings. Additions or
5
alterations shall not be made to an existing building or
structure when such existing building or structure is not
in full compliance with the provisions of this code
° u
o except when such addition or alteration will result in
up p the existing building or structure being no more
o hazardous based on life safety, fire safety, and
a sanitation, than before such additions or alterations are
o W undertaken.
o w Alterations or repairs to an existing building or
qstructure which are nonstructural and do not adversely
O affect any structural member or any part of the building
o or structure having required fire resistance may be made
c a with the same materials of which the building or
o structure is constructed. The installation or
w
o replacement of glass shall be as required for new
pq installations.
cNo U AMEND SECTION 30.2.3 by:
M H Delete the last sentence of the text.
� W
N E'
AMEND SECTION 30.2.8 by:
m Delete "that" in number 3 and replace with "than".
oW
n 44AMEND SECTION 30.5.3 by:
Mz
N Add the following sentence at the end of the text: The temporary
o certificate shall be valid for a certain period of time not to
v cz exceed three months and may be renewed only once by the Building
a Official.
nlC>
Mm DELETE SECTION 30.7.
ri
oo
M W DELETE SECTION 40.7.
DELETE SECTION 50.7.
DELETE SECTION 60.7.
DELETE SECTION 70.6.
DELETE SECTION 71.6.
DELETE SECTION 86.
RENUMBER REMAINING SECTIONS BEGINNING WITH SECTION 87 AND CONTINUING
THROUGH 93.3.6
6
If any section, subsection, paragraph, sentence, clause or phrase of
this Ordinance is for any reason held or decided to be invalid or
NN OO unconstitutional, such decision shall not affect the validity of the
o remaining portion. The Board of County Commissioners hereby declares
N O that it would have passed the Ordinance, and each and every section,
U subsection, paragraph, sentence, clause and phrase thereof irrespective
[a of the fact that any one or more section, subsection, paragraph,
o rj sentence, clause, or phrase might be declared to be unconstitutional and
O 3 invalid.
o a
`" The above and foregoing Ordinance No. 119-C was, on motion duly made
a
�U and seconded, adopted by the following vote on the 30th day
v.
of December, A.D. , 1985.
o
� E_L0
. BOARD OF COUNTY COMMISSIONERS
cco U ATT c T• (yi n ., WELD COUNTY, COLORADO
z INS (�
" \
M H
Wel C 9W k/�n Recorder � ;�. \ Y'1�Ll�ry�
N E and C ' e-tpA' J:cque ne John:o , Chairman
rum
��
GeneCl R. Brantner,,Pro-Tem
NNW
rn Z Approved as to form:
o
C. W. i
0
U a
r12 el/VA" Go
r r Cou y Atta ney ������
o m
rI CO Fr Yamag i /
m W
First Reading: December 2, 1985
Published: December 5, 1985, in the Johnstown Breeze
Second Reading: December 16, 1985
Published: December 19, 1985, in the Johnstown Breeze
Final Reading: December 30, 1985
Published: January 2, 1986, in the Johnstown Breeze
Effective: January 7, 1986
7
HEARING CERTIFICATION
DOCKET NO. 85-84
RE: AMENDMENTS TO BUILDING CODE ORDINANCE - FIRST READING OF ORDINANCE
#119-C
A public hearing was conducted on December 2, 1985, at 9:00 A.M. , with
the following present:
Commissioner Jacqueline Johnson, Chairman
Commissioner Gene Brantner, Pro-Tem
Commissioner C.W. Kirby - Excused
Commissioner Gordon E. Lacy
Commissioner Frank Yamaguchi
Also present:
Acting Clerk to the Board, Tommie Antuna
County Attorney, Thomas 0. David
Director of Planning Services, Chuck Cunliffe
The following business was transacted:
I hereby certify that pursuant to a notice dated October 16, 1985, and
duly published November 7, 14, 21 , and 28, 1985, in the Johnstown
Breeze, a public hearing was conducted to consider certain amendments
to the Building Code Ordinance and the first reading of Ordinance
#119—C, In the Matter of an Amendment to Ordinance No. 119, Weld County
Building Code Ordinance, Revising Certain Procedures, Terms,
Requirements, and Incorporating by Reference Certain Portions of the
Uniform Building Code, 1985 Edition; Uniform Mechanical Code, 1985
Edition; National Electrical Code, 1984 Edition; Uniform Plumbing Code,
1985 Edition; Uniform Code for the Abatement of Dangerous Buildings,
1985 Edition; the Uniform Swimming Pool Code, 1985 Edition; and
Appendices to all Uniform Codes. Chuck Cunliffe, Director of Planning
Services, explained the amendments to the Building Code Ordinance. Tom
David, County Attorney, made this matter of record. Mr. Cunliffe read
the favorable recommendation of the Planning Commission into the
record. Mr. David then read Ordinance #119—C into the record. (TAPE
CHANGE #85-103 during reading of the Ordinance.) Commissioner Lacy
moved to approve Ordinance #119-C on first reading and direct the Clerk
to the Board to have published. The motion was seconded by
Commissioner Brantner and carried unanimously.
This Certification was approved on the 4th day of December, 1985.
APPROVED:
. / , �• BOARD OF COUNTY COMMISSIONERS
ATTEST: I3 (Q,c.;¢ t;u-u„1':"u(W.&L47,-,.-,i WELD COUNTY, COLORADO
Weld County Clerk and Recorder
and Clerk to the Boa Id) J e ne Jo on, Chairman
By: 077��rt � t-7t-
eputy County Clerk Gene R. Brantner, Pro-Tem
// EXCUSED
C.W. Ki
ac
F an c Yama u
TAPE #85-102 & #85-103
DOCKET #85-84
ORDINANCE #119-C
AFFIDAVIT OF PUBLICATION
t THEJOHNSTOWNBREEZE
al. STATE OF COLORADO I
cm
I SS
COUNTY OF WELD I
mow' 1, Clyde Briggs, do solemnly swear that I
am publisher of 'l'he Johnstown Breeze.
that the same is a weekly newspaper
printed, in whole or in part, and published
in the County of Weld, State of Colorado.
and has a general circulation therein: that
said newspaper has been published
continuously and uninterruptedly in said
County of Weld for a period of more than
Jos fifty-two consecutive weeks prior to the
first publication of the annexed legal notice
N , or advertisement; that said newspaper has
been admitted to the United States mails as
second-class matter under the provisions of
- 2 the Act of March :1, Ia79, or an'.
', amendments thereof, and that said
newspaper is a weekly newspaper duly
qualified for publishing legal notices and
' advertisements within the meaning of the
" laws of the State of Colorado.
That the annexed legal notice or advertise-
ment was published in the regular and
„ entire issue of every number of said weekly
newspaper for the period of I consecu-
tive insertions; and that the first
publication of said not ire was in the issud.ol_
said newspaper dated l2-!`7 A U.9s
and that the last publication of said notice
6V was in the issue of said newspaper dated
,,,,,,aL _ • A.D. 19
Nu_:re-_.
:- In witness whereof I have hereunto set
r,e e .r my hand_this 20 flay of /9 e ,
A.D. 19:96—
ti
to
Y u et
C4 Publisher
C w
,..T ,w Subscribed and sworn to before me, a
y ; Notary Public in and for the County of
&,- State of Colorado, this ..4x...&. day of
• - „(.9.:... A.D. 19.ce/.::
• Notary Piddle
My eOMilii6JiMiltRi(3LtScAna'la;'1987
2 South Parish Avenue
Johnstown, CO 8C534
Breeze, Dec. 19, 1985 13
ORDINANCE NO. 119.0 relocated within Weld County shower shall be equipped with that any one or more section,
IN THE MATTER OF AN shall meet the following installa- hot and cold running water subsection, paragraph, sentence,
AMENDMENT TO ORDINANCE tion standards. The Building necessary for its normal oper- clause, or phrase might be
NO. 119, WELD COUNTY Official may authorize the use of ation. Every home shall be declared to be unconstitutional
BUILDING CODE ORDINANCE, different materials or methods provided with a smoke alarm and invalid.
REVISING CERTAIN PRO- which will accomplish sub- installed according to the Weld
CEDURES, TERMS, REQUIRE- stantially the same result. County Building Code. The above and foregoing
'MEBY No. 119-C was, on NT REFERENCE S, AND RPOCERTIAIN rdinanceNG 20.10.1 Blocking. Blocking 20.10.10 Installation on mmotion duly made and seconded,
PORTIONS OF THE UNIFORM shall be placed under each main Basements. Units which have a - adopted by the following vote on
BUILDING CODE, 1985 SDI- manufactured home frame floor joist system approved to be the --- day of ----, A.D.,
TION: UNIFORM MECHANICAL member for the full length of the put on a regular foundation will 1985.
CODE. 1985 EDITION; NA- manufactured home at maximum not need to be engineered
TONAL ELECTRICAL CODE, intervals of eight feet(8'). End of unless installed in an area where BOARD OF COUNTY
1984 EDITION, UNIFORM piers shall not be farther than we require all foundations to be COMMISSIONERS
PLUMBING CODE. 1985 five feet (5') from the end of the engineered due to soil con- WELD COUNTY,
EDITION UNIFORM CODE FOR manufactured home. Wood rail- ditions. However, rebar shall be COLORADO
THE ABATEMENT OF DANGER- road ties are not acceptable installed in the foundation
OUS BUILDINGS, 1985 EDI- materials for blocking. according to County require-
TION THE UNIFORM SWIM- ments. Units which are designed Jacqueline Johnson,
MING POOL CODE. 1985 20.10.2 Base. Footers shall to be supported on four (4) rails Chairman
EDITION. AND APPENDICES TO consist of poured concrete pads shall submit an engineered
ALL UNIFORM CODES. a minimum of six inches(6")thick foundation and support system
and a minimum of sixteen inches design. Gene R. Brantnar,
BE IT ORDAINED BY THE R.by sixteen inches(16")Pro-Tem
BOARD OF COUNTY COMMIS- square. Two pieces of minimum 20.10.11 Installation on
STONERS OF WELD COUNTY. No. 4 rebar (a") shall be placed Other Than Basements. Units
COLORADO in each direction before pouring. which have a floor foist system C. W. Kirby
The bottom of the solid concrete approved to be put on a regular
WHEREAS iris Board of base must be a minimum of foundation system must be in-
County Commissioners of Weld twelve inches (12") below undis- stalled according to manu- Gordon E. Lacy
County, Colorado. pursuant to turbed ground surface. lecturers and County's specifi-
Coloratlo statute and the Weld cations.This would consist of an
County Home Rule Charter. is 20.10.3 Piers. Piers shall be outside perimeter footing and . Frank Yamaguchi
vested with the authonty of constructed of one (1) or more foundation with support footings
administering the affairs of eld eight inch (8") by eight inch (8" and a wall in the center or ATTEST:
County, Colorado, and by sixteen inch (16 ) ("celled") concrete pads and vertical
concrete blocks or approved supports. The unit must be Wetd County Clerk
WHEREAS, the Board of equivalent materials. Said blocks anchored to the foundations. and Recorder and
shall be placed over the base in Units which are designed to be Clerk to the Board
County Commissioners has the such a manner that the sixteen sir
power and authority under the inch (16") dimension is at a must o be installed he f accour ording By:
Weld County Home Rule Charter ninety degree (90 degree) angle the enclosed standards. If the Deputy County Clerk
and Article 28 of Title 30 CRS,to to the main frame of the manufacturers specifications call
adopt building codes, for the p Approved as to form:
unincorporated areas of the manufactured home and shall be for closer spacing of the support
County of Weld, and centered on the base with the piers then that standard must be
cells in a vertical position. followed. County Attorney
WHEREAS, the Board of First Reading: December 2, 1985
20.10.4 Caps. Each pier shall AMEND SECTION 30.2.2 TO
County Commissioners of Weld be topped(capped)with an eight READ: Published: December 5, 1985, in
Eounty, Colorado, adopted inch (8") by sixteen inch(16") by
Ordinance Na 119, with subse-
quent amendments, the Weld four inch (4") solid concrete Additions, Alterations or
County Building Code Ordinance, block or the equivalent. Repairs. Additions, alterations Second Reading: December 16,
establishing a comprehensive or repairs may be made to any published: December 19, 1985,
revision of the building code 20.10.5 Wood Wedging. building or structure without
Wood wedging (shims) shall be requiring the existing building or in the Johnstown Breeze
requirements for the unlncorp- driven tight between each pier structure to comply with all the
Weld, anorated d
deas of the County of cap and the main frame member requirements of this code, Final Reading: December 30,
of the manufactured home if provided the additions, alteration 1985
necessary. No more than four or repair conforms to that Published: January 2, 1986, in
WHEREAS, said Ordinance No. inches(4") of the thickness of a required for a new building or the Johnstown Breeze
119, as amended by Ordinances g
of wood approved by the
119-A and 119-8, is in need of type structure.Additions or alterations
revision, updating, and clarifi Building
- Building Official shall be per- shall not be made to an existing Effective: January 7, 1988
mitred. The width of the wedge building or structure which will -"
cation with regards to pro-
cedures,terms,and requirements shall provide a minimum of eight cause the existing building or
therein. (8) lineal inches of bearing structure to be in violation of any
surface between the pier cap and of the provisions of this code nor
NOW, THEREFORE, BE IT the main frame of the manu- shall such additions or alter-
ORDAINED by the Board of lectured home. ations cause the existing building
County Commissioners of vsaid or structure to become unsafe.
County, Colorado, that dad. 20.10.6 Tie downs. .Tie An unsafe condition shall be
Ordinance No. 119, as amended downs shall meet the following deemed to have been created if
is amended by the addition, standards: - .. an addition or alteration will
revision, and renumbering of pause the existing building or
various sections,which shall read 20:10.6.1 Ties shall consist of strum,. to become structurally
as follows:AMEND SECTION galvanized steel strapping(1"k x unsafe or overloaded; will not
10.4 by: .035") with a minimum breaking provide adequate egress in
strength of four Delete "30-38.201" and re- hundred fifty thousand,7po pounndsds s seven
e) or compliance with the provisions of
place with "30-28-201" Delete ties shall consist of galvanized this code or will obstruct existing
"1973." steel cable 7/32"x 7 x 7 or 1,"7 exits; will create a fire hazard;
x 19) with a minimum breaking will reduce required fire re-
AMEND SECTION 20.1 by: strength of tour thousand eight sistance or will otherwise create
Delete"1982"and replace with hundred pounds'(4,800*). The conditions dangerous to human
"1985" Building Official may approve life. Any building so altered,
alternate materials of equal which involves a change in use
DELETE SECTION 20.1.2 strength. or occupancy, shall not exceed
the height,number of stories and
AMEND SECTION 20.2 by: 20.10.6.2 Each frame tie shall area permitted for new buildings.
connect the main frame of the Any building plus new additions
Delete"1982"and replace with manufactured home to an anchor shall not exceed the height,
"1985." located outside the opposite number of stories and area
main frame member. A frame tie specified for new buildings.
AMEND SECTION 20.2.1 by: shall be located within two feet Additions or alterations shall not
Delete"1982"and replace with (2') of each end of the manu- be made to an existing building
"1985." Add "unless the walls of factured home. Any menu- or structure when such existing
the crawlspace are insulated" to lectured home fifty feet (50') or building or structure is not in full
the last sentence of the text. less in length shall have a compliance with the provisions of
minimum of four (4) frame ties. this code except when such
AMEND SECTION 20.2.2 by: Each frame tie shall be tightened addition or alteration will result in
snug to an anchor. the existing building or structure
Delete "Paragraph 4" replace being no more hazardous based
with "(f)". '20.10.6.3 Ground anchors for on life safety, fire safety, and
securing the ties shall be of the sanitation, than before such
AMEND SECTION 20.4 by: following types: screw augers, additions or alterations are
expanding anchors, concrete undertaken.
Delete"1982"and replace with deadmen, or equivalents
"1985" approved by the Building Official. Alterations or repairs to an
Any type of ground anchor used existing building or structure
AMEND SECTION 20.5 by: shall have a minimum holding which are nonstructural and do
power of four thousand eight not adversely affect any
Delete"1982"and replace.with hundred pounds (4,800*). structural member or any part of
"1985". Ground anchors'shall be placed' the building or structure having
at a minimum depth of four feet required fire resistance may be
AMEND SECTION 20.5.8 by: 14) or at a greater depth if made with the same materials of
determined necessary by the which the building or structure is
Delete "(a)" and replace with Building Official. constructed. The installation or
replacement of glass 20.10.6.4 When strapping or required for new installations.ll be ae
AMEND SECTION 20.6 by: cables are connected to turn
buckles or to yoke-type fasteners AMEND SECTION 30.2.3 by:
Delete"1962"and replace with and tensioning devices, con-
.'1 D85. nections shall be made so that Delete the last sentence of the
the overall strength of the tie text.
RENUMBER SECTION downs is not reduced. Turn- -
20.9.6.7 TO SECTION 20.9.7. buckles shall be one-half inch AMEND SECTION 30.2.6 by:
(1/2") galvanized steel or the
RENUMBER SECTION equivalent as approved by the Delete "that" in number 3 and
'
20.9.6.8.TO SECTION 20.9.8. Building Official. Hook-ends or replace with "than".
open-eyes are not permitted as
RENUMBER SECTION connection devices. "Eye and AMEND SECTION 30.5.3 by:
20.9.6.9 TO SECTION 20.9.9. eye" or "draw and draw" type
turnbuckles are acceptable as Add the following sentence at
RENUMBER SECTION connection devices.Where cable is the end of the text: The tempor-
20.9.6.10 TO SECTION utilized and looped for con- ary certificate shall be valid for a
20.9.10. nection, ends shall be secured certain period of time not to
with a minimum of two (2) cable exceed three months and may be
RENUMBER SECTION clamps with the nuts placed on renewed only opce= by the
20.9.6.11 TO SECTION the live side of the cable. Building Official.
20.9.11. Materials and connecting devices
of equivalent strength may be DELETE SECTION 30.7.
ADD NEW SECTION 20.10 TO utilized upon approval by the
READ: Building Official. DELETE SECTION 40.7.
20.10 Manufactured Nome 20.10.7 Skirting. Skirting DELETE SECTION 50.7.
Installation Standards. Any shall be provided around the
manufactured home located in or bottom of the manufactured DELETE SECTION 60.7.
home to ground level. Skirting .
AFFIDAVITOF PUBLICATION
THE JOHNSTOWN BREEZE
6 STATE 01 COLORADO 1
Ss
ORDINANCE NO. 119-C Delete "30-38-201" and re- COUNTY OF WELD 1
IN THE • MATTER OF AN place with "30-28.201" Delete
AMENDMENT TO ORDINANCE •'1973." I, Clyde Briggs, do solemnly swear that I
NO. 119, WELD COUNTY am publisher of The Johnstown Breeze:
CODE ORDINANCE,- SECTION 20.1 by:
REVISING CERTAIN PRO- Delete"1982"and replace with that the same is a weekly newspaper
.CEDURES, TERMS, REQUIRE- "1985." printed, in whole or in part, and published
MENTS, AND INCORPORATING DELETE SECTION 20.1.2 in the County of Weld, State of Colorado,
BY • REFERENCE The
UNIFORM
PORTIONS OF THE UNIFORM BUILDING CODE, 1985 AMEND SECTION 20.2 by: and has a general circulation therein; Ilia(
C UNIFORM DITCHANEELII•ICAi said newspaper has been published
CODE, 1985 EDITION; NA- Delete"1882"and replace with
TIONAL ELECTRICAL CODE, . "1985." ' - continuously anduninterruptedly in said
1984 EDITION UNIFORM " County of Weld for a period of more than
CODE, 1985 SECTION 20.2.1 bys
EDITION; UNIFORM CODE FOR Delete"1982"and replace with fifty-two consecutive weeks prior to the
THE ABATEMENT OF DANGER- "1985."Add"unless the walls of first publication of the annexed legal Hot OUS ,BUILDINGS 1985 EDI- the crawispace are Insulated" to
TION; THE' UNIFORM SWIM-, the last sentence of the text or advertisement; that said newspaper has
MING POOL CODE, 1985 been admitted to the United States mails as
EDITION, AND APPENDICES TO SECTION•20.2.2 Dm
ALL UNIFORM CODES second-class matter under the provisions 1,1
BE IT ORDAINED OT BY M
with Delete "Paragraph 4" replace the Act of March 3, 1879, 'Jr ; ii\
OFF WELD COMMIS-
SIONERS SECTION 20.4 by: amendments thereof, and that said
OF WELD COUNTY, -
COLORADO: newspaper is a weekly newspaper dole
Delete"1982"and replace with
WHEREAS, the Board of "1985" qualified for publishing legal notices and
County Commissioners of Weld SECTION 20.5 by: advertisements within the meaning of the
County, Colorado, pursuant to
Colorado statute and the-Weld laws of the State of Colorado.
County Home Rule Charter; is „t Delete"1982"and replace with That the annexed legal notice or advertise
-
administering with the authority of
the affairs of Weld SECTION 20.5.8 by: meat was published in the regular andCounty, Colorado, and
entire issue of every number of said weekly
WHEREAS,
ha Delete "(a)" and replace with
the Board of .tcp•, newspaper for the period of / c'onsec'u-
pouery Commissioners s the
power and authority under the live insertions; and that the first
Weld County Home Rule Charter SECTION sos by: publication of said notice was in the issu:yd_
and adopt Article 28 of cde 30 for t the
on building atd codes c Delete replace with 5111(1 ❑ewspa per dated/2/c' A l). 1r
unincorporated areas of the
County of Weld, and and that the last publication of said notice
RENUMSER SECTION was in the issue of said newspaper dated
WHEREAS, the Board of •
20.0.6.7 TO SECTION 20.0.7.
County Commissioners of Weld SECTION A.D. 19
County, Colorado, adopted 20.9.6.6.TO SECTION 20.9.8 In witness whereof I have hereunto set
qut Ordinance riNd, 119, with t subelde- sECTIOI my hand-ihis /,3 day of O ec-.
Count amendments, tie .Weld RENUMBER
County Building Code Ordinance, 20.0.6.0 TO SECTION 20.0.9 A.D. 1935
eatNion.,np_, a wmprehensive
revlslop„pf the ybuilding,code RENUMBER SECTOOI
reated amts 101 the unincorp- 20.0.0.10 TO SECTIOI
orated areas of the County.of 20.0.10,
Weld, and
said Ordinance Ao. 20.0.6.11RENUMSIR sEbnq ....... PublisherIt9'as:Amended byyr Ordinances 20.9.11.
TO SECTOq
119-A and 1t9-S, hi'In need of
revision, updating; and• clarlfl- ADO NEW SECTION 20.10 TA
cation .with regards to pro- READScaduce Subscribed and sworn to before me, :1
theein` tarm4andrequirements 20.10 Nanahotured Nouns Notary Public in and for the County of
Installation Standen''. Any
NOW THERyyEFORE, BE IT ,0��,c1 Wel State of Colored his .../3. day of
CCoRunntty�CommblesIthe
ers of Weld k l4R Y � ^T .. .<.. A.1). 19
County, Colorado, that said
Ordinance No. 119,as amended,
is amended by the addition, _
revision, and renumbering of r4/2-7--ce‘V<�% L� ?zC-cam
various section!,which shall read Nol::rc Politic
follows: SECTION
10.9 by:
My commission expires
:.y Cc runs nr, Lxpne: Juno a4, 1i8?
f4-mu -. 'far:sl'. Ave,nce
...... io ,ric,.w:., li e4./...14
relocated within Weld County shower shall be equipped with that any one or more section,
shall meet the following installs- of and cold running water subsection, paragraph, sentence,
Lion standards. The Building necessary for its normal oper • clause, or phrase might be,..
Official may authorize the use of ation Every home shall be declared to be unconstitutional
different materials or methods provided with. a smoke alarm and Invalid.
which will accomplish sub- installed according to the Weld "
stantially the same result. County Building Code. . .The. above and foregoing
Ordinance No. 119-C was, on
• 20.10.1 Blocking. Blocking 20.10.10 Installation on • motion duly made and seconded, 'y
shall be placed under each main Basements. Units which have a adopted by the following vote on
.` manufactured home frame floor joist system approved to be the -- day of ----, A.D.,3,
member for the full length of the put on a regular foundation will 1985. a
manufactured home at maximum - not .need to be engineered
intervals of eight feet(8'). End of unless Installed In an area where • BOARD OF COUNTY"
piers shall not be farther than we require all foundations to be COMMISSIONERS -,
- five feet (5') from the end of the engineered due to soil con- WELD COUNTY,
manufactured home. Wood rail- dihons. However, rebar shall be COLORADO
road ties are not acceptable installed in the foundation
materials for blocking. according to County require- '
manta Units which are designed Jacqueline Johnson,
20.10.2 Base. Footers shall to be supported on four(4) rails Chairman
consist of poured concrete pads shall submit an engineered
a minimum of six inches(6")thick foundation and support system .
and a minimum of sixteen Inches design. Gene R. Brentner,
(16") by sixteen Inches (16") Pro-Tem
square. Two-pieces of minimum 20.10.1T Installation on -
No. 4 rebar ('h") shall be placed Other Than.Bassments. Units
in each direction before pouring. which have a floor joist system C. W. Kirby
The bottom of the solid concrete approved to be put on a regular
pass must be a minimum of foundation system must be in-
twelve Inches (12") below undis- stalled according to manu- Gordon E. Lacy
turbed ground surface. facturers and County's specifi-
cations, This would consist of an •
20.10.9 Piers. Piers shall be outside perimeter footing and Frank Yamaguchi
constructed of one (1) or more foundation with support footings ATTEST:
eight Inch (8") by eight inch (8") . and a wall in the center or
by sixteen inch (16") ("celled") concrete pads and vertical Weld concrete blocks or approved supports. The unit must beCounty Clerk ..
and Recorder and equivalent materials. Said blocks anchored to the foundations.
' shall.be placed over the base in Units which are designed to be , Clerk to the Board
such a manner that the sixteen supported by the four (4) rails By;
inch (16") dimension is at a must be installed' according to
ninety degree.(90 degree) angle the enclosed standards. If the Deputy County Clerk
to the main frame of the manufacturer's specifications call 'Approved.as to form:
manufactured home and shall be for closer spacing of the support
centered on the base with the piers then that standard must be
cells in a vertical position. followed. County Attorney
20.10.4 Caps. Each pier shall AMEND SECTION 30.2.2 TO First Reading; December 2, 1985
be topped(capped)with an eight READ: Published: December 5, 1985, in
Inch (8") by sixteen inch(16") by -the Johnstown Breeze
four .inch (4") solid concrete Additions, Alterations or Second Reading:block or the equivalent. Repairs. 'Additions, alterationsg: December 16,
1985
or repairs may be made to any Published: December 19, 1985,
20.10.5 Wood Wedging. building or structure without
Wood wedging (shims) shall be requiring the existing building or in the Johnstown Breeze
driven tight between each pier structure to comply with all the
• cap and the main frame member requirements of this code, Final Reading: December 30,
of the manufactured home if provided the additions, alteration•
1985
necessary.. No more than four or repair conforms to that Published: January 2, 1986, in
- inches (4") of the thickness of a required for a new building or the Johnstown Breeze
type of wood approved by the structure.Additions or alterations
Building Official shall be per- shall not be made to an existing Effective: January 7, 1986
mitted. The width of the wedge building or structure which will
shall provide a minimum of eight cause the existing building or -
(8) lineal Inches of bearing structure to be in violation of any
surface between the pier cap and of the provisions of this code nor
the main frame of the menu- shall such additions or alter-
factured home. ations cause the existing building
20.10.6' Tie downs. Tie or structure to become unsafe.
An unsafe condition shall be,
downs shall meet the following deemed to'have been created if
standards: . an addition or' alteration All
cause the existing building or
20:10.8.1 Ties shall consist of structure to become structurally
galvani
zed
steelstrapping
minimum (1-1/ x —unsafe or overloaded; will not
'strength of.fourthousand seven :Provid,: adequate egress in
hundred fifty pounds(4,750#) or compliance with the provisions of
ties:,shall consist'of galvanized. this code or will obstruct existing
steel cable 7/32"x 7 x 7 or'K'7 exits; will create-a fire hazard; . -
x 19) With at minimum break) 9t-i.,:elstance•or will hl reduce required
otherwiselre re-
create
(*yhtrength tof four i(4,800 QNe , Conditions� dangerous.to human
-Building..pounds
(ma 00 1) rove''life. hy. building so altered, -
y'approve
which Involve a.change.In use
alternate materials of equal or occupancy shall not exceed,:
strength. ' the height,number of stories and:
20.10.6.2 Each frame tie shall area permitted for new buildings.
connect the main frame of the Any building plus new-additions
manufactured home to an anchor shall not exceed the height,
located outside. the opposite number 'of stories and area
main frame member. A frame tie specified for .new buildings.
shall,be located within two feet Additions or alterations shall not
�2') of each end of the manu- be made to an existing building
actured home. Any menu- or structure when such existing
factured home fifty feet (50') or building or structure is-not in full
less in length shall have' a compliance with the provisions of
minimum of four (4) frame ties. this code except when such
Each frame tie shall be tightenad addition or alteration will result in
snug to an anchor. the existing building or structure
•
'being no more hazardous based
20.10.6.3 Ground anchors for on life safety, fire safety, and
securing the ties shall be of the sanitation, than before such
following types: screw augers, additions or alterations are
expanding. anchors, concrete undertaken.
deadmen, • ' or equivalents
approved by the Building Official. Alterations ons or repairs to an
Any type of ground anchor used existing building or structure
shall have a minimum holding which are nonstructural and do
power of.'four thousand eight not adversely affect any
hundred ' pounds (4,800#). structural member or any part of
Ground anchors shall be placed the building or structure having
at a minimum depth of four feet required fire resistance may be
(4') or at a greater depth If made with.the same materials of
determined necessary by the which the building or structure is
Building Official. constructed. The installation or
replacement of glass shall be as
20.10.0.4 When strapping or required for new Installations.
cables are connected to turn,
buckles or to yoke-type fasteners SECTION 30.2.3 by:
and tensioning devices, con-
nections shall be made so that Delete the last sentence of the
the overall strength of the tie text
downs is not reduced. Turn-
buckles shall be one-half inch AMEND SECTION 30.2.6 by:
('h") galvanized steel or the
equivalent as approved by the Delete "that" in number 3 and
Building Official. Hook-ends or ' replace with "than". .
open-eyes are not permitted as
connection devices, "Eye and AMEND SECTION 30.8.3 by:
eye" or "draw and draw" type
turnbuckles area acceptable as Add the following sentence at
connection devices Where cable is the end of the text: The tempor-
utllized• and looped 'for con- ary certificate shalt be valid for a
nection, ends shall be secured ' 'certain period of time not to
with a minimum of two (2) cable exceed three months and may be
clamps with the nuts placed on renewed only once by the
the live side of the cable. Building Official
Materials and connecting devices
of equivalent strength may be - DELETE SECTION 30.7.
utilized upon approval by the
Building Official. _ DELETE SECTION 40.7.
20.10.7 Skirting. Skirting DELETE SECTION 50.7.
shall be provided around the
bottom of the manufactured DELETE SECTION 60.7.
home to ground level. Skirting
shall be made of a material which DELETE SECTION 70.6.
is approved for exterior use by
the Uniform Building Code. SECTION. 'I.6.
NOTICE .f PUBLIC NEARING
, - Docket Number 85-84
The Board of County Com-
C lorado, wit of Welda public AFFIDAVIT OF PUBLICATION
,.�ySring at or about 9:00 A.M.on
'S9TWtdsy, December 2; 1985, in
s a- County Commissioners'
mr3Ginty Room, ial enter,Weld THE JOHNSTOWN BREEZE
aMe8rMy Centennial C Floon, 915
10th Street, Greeley, Coloredo, STATE OF COLORADO i
-4e7?the purpose of amending the ,. y,�,-
Weld County• Building Code I SS
• Ordinance as summarized below: COUNTY OF WELD i
AMINO SECTION 10.4 tot I, Clyde Briggs, do solemnly swear that I
Correct',typographialerror in am publisher of The Johnstown Breeze;
the text that the same is a weekly newspaper
AMEND micron 10.1 toe AMEND SECTION 30::.3 ben .. printed, in whole or in part, and published
text° the last sentence of
the in the County of Weld, State of Colorado,
Incorporate by reference the
1985 edition of the Uniform SECTION a0.9.S by: and has a general circulation therein; that
Building Code. said newspaper has been published
DELETE SECTION 10.1.9 - and ere e with
ing hat" in number S continuously and uninterruptedly in said
SECTION 10.2 to: AMEND SECTION 30.5.3 by: County of Weld for a period of more than
Incorporate by reference the fifty-two consecutive weeks prior to the
1985 edition of the Uniform ' atAdding the following sentence first publication of the annexed legal notice
Mechanical Code. , temporary the end certificate
the text: The
ert in period
shot be or advertisement; that said newspaper has
AMEND SECTION 20.2.1 bye 1. not to for
three months and been admitted to the United States mails as
Deleting "1982" and replace I' may be renewed only once by second-class matter under the provisions of
with 1985," And "unless the p-
the Building Official.
wells of the sete are A the Act of March 3, 1879, or any
insulated"to the last sentence of DELETE SECTION 30.7.
me text amendments thereof, and that said
AMEND SECTION 20.2.2 by: DELETE SECTION 40.7. •
Anewspaper is a weekly newspaper duly
Deleting Paragraph 4" and I'DELETZ SECTION 50.7. qualified for publishing legal notices and
replace with if)."
AMEND SECTION 20.4 to: DELETE SECTION 50.7. advertisements within the meaning of the
incorporate by reference. the ' DELETE SECTION 70.5. laws of the State of Colorado.
1985 edition of the Uniform That the annexed legal notice or advertise-
Plumbing Code. DELETE SECTION 71.0. ment was published in the regular and
AMEND SECTION 20.5 to: - DELETE SECTION 85. entire issue of every number of S.1 id weekly
Incorporate by reference the RENUMBER REMAINING newspaper for the period of n; consecu-
1986 edition of the Uniform I SECTIONS BEGINNING I9ITN LIVE insertions; and that the first
Code for Abatement of Danger- i SECTION 07 AND CONTINU-
i ous Buildings. I ING THROUGH 93.3.0 publication of said notice was in the issue of
Amend ...anon 20.5.8 to: said newspaper dated .../.7.. A.O. lb Cr
All persons in any" manner �F
Correct a typographical error in interested in the proposed and that the last publics ion of said notice
amendments to the Weld County
the text. - Building Code ordinance are was in the issue of said newspaper dated
SECTION 20.5 to: requested to attend and may be (( „ A.D. 19.`d. .
heard.
Incorporate by reference, the n witness where I have hereunto set
' 1985Materiels pertaining to the 1
Swimming edition of the Uniform proposed amendments are my he nr{ I11S t flay' of ...Y,.6:�..........,
Pool Code. available for public inspection in A.D. 19.:1:5.
RENUMBER SECTION the office of the Clerk to the
20.0.0.7 TO SECTION 20.9.7. Board of County Commissioners,
Third Floor, Weld County Can-
RENUMBER SECTION tennial Center, 915 10th Street,
20.9.5.5.TO SECTION 20.9.5. Greeley, Colorado, Colorado,
Monday through Friday,8:00 A.M. ,C611177Publisher
RENUMBER SECTION to 5:00 P.M.
20.9.5.9 TO SECTION 20.0.9. BOARD OF COUNTY
SECTION COMMISSIONERS
20.0.5.10 TO SECTION. Subscribed and sworn to before me, a
20.0. BY: MARY ANN
10. FEUERSTEIN Notary Public in and for thp, unty of'
RENUMBER SECTION COUNTY CLERK AND WC Id, State of Colora 0, this .... ..... day of
20.9.9.11 TO SECTION , RECORDER AND ER THE CLERK BOERK : '�' A.D. 19 i
20.9.11.
ADD NEW SECTION 20.10 to: BY: Mary Reiff, Deputy — .
Adopt minimum installation DATED: October 16, 1985 �%�R-F,;t-t,� 7:..,,„, :`-eti v=+.-
standards. for manufactured
homes. PUBLISHED: November 7, 14, a,. 1//11 P15�t✓n n'< Notar}'Public.