GEOTECHNICAL ENGINEERING REPORT
PROPOSED STRUCTURE
ANDERSEN PROPERTIES-WCR 39%AND 64
GREELEY, COLORADO
NORTHERN COLORADO GEOTECH
PROJECT NO. 101-04
JULY 13, 2004
• Prepared for:
Pickett Engineering
808 8th Street
Greeley, Colorado 80631
Attn: Mr. Michael Hein
1%0\16_
Northern
Colorado
Geotech
2956 29th Street, Unit 21
Greeley, Colorado 80631
Phone: (970) 506-9244
Fax: (970) 506-9242
•
2008-2274
• S
• Northern
Colorado
Geotech
July 13, 2004 2956 29th Street, Unit 21
Greeley, Colorado 80631
Phone: (970)506-9244
Fax: (970)506-9242
Pickett Engineering
808 8th Street
Greeley, Colorado 80631
Attn: Mr. Michael Hein
Re: Geotechnical Engineering Report
Andersen Properties
Northern Colorado Geotech Project No. 101-04
Northern Colorado Geotech has completed a geotechnical engineering exploration for the proposed
structure to be located on the strip of land located near Weld County Road 39% and 64, north of
Greeley, Colorado. This study was performed in general accordance with our proposal number
P04023g dated May 19, 2004.
The subsurface soils at the site consisted of sandy lean clay and silty sand with gravel. The results
• of our field exploration and laboratory testing indicate that the soils have low expansive potential and
low load bearing capabilities.
Based on the anticipated construction and the results of our engineering exploration, it is our opinion
that the proposed structure may be supported on a spread footing foundation system. Slab on
grade may be utilized for the interior floor system.
If you have any questions concerning this report or any of our consulting services, please do not
hesitate to contact us.
Sincerely,
NORTHERN COLORADO GEOTECH
Prepared by:
Lam" f �'
Doug Leafgr .G.
President
_,.-
Reviewed by: —
Gary G. Weeks, P.E.
Vice President
• Copies to: Addressee (3)
• TABLE OF CONTENTS
Page No.
Letter of Transmittal
SCOPE 1
SITE CONDITIONS 1
PROPOSED CONSTRUCTION 1
SITE EXPLORATION 2
Laboratory Testing 2
SUBSURFACE CONDITIONS 3
Soil Conditions 3
Groundwater Conditions 3
Field Test Results 3
Laboratory Test Results 3
• DESIGN RECOMMENDATIONS 3
Foundation Design 3
Footing Foundations 4
Surface Drainage 4
Floor Slab Design and Construction 5
General Earthwork 6
Site Preparation 6
Fill Materials and Placement 6
GENERAL COMMENTS 7
ATTACHMENTS
Boring Location Plan
Logs of Borings
Laboratory Test Results
•
GEOTECHNICAL ENGINEERING REPORT
PROPOSED STRUCTURE
ANDERSEN PROPERTIES-WCR 39Y�AND 64
GREELEY, COLORADO
NORTHERN COLORADO GEOTECH
PROJECT NO. 101-04
JULY 13, 2004
SCOPE
This report contains the results of our geotechnical engineering exploration for the proposed
structure to be located near Weld County Roads 39% and 64, north of Greeley, Colorado.
This report includes descriptions of, and geotechnical engineering recommendations relative to:
• subsurface soil and bedrock conditions
• groundwater conditions
• foundation design and construction• • drainage
• floor slab design and construction
• earthwork
The recommendations contained in this report are based upon the results of field and laboratory
testing, engineering analyses, and experience with similar soil conditions, structures and our
understanding of the proposed project.
SITE CONDITIONS
The site is located at the south end of an agricultural field. Surface drainage is poor to fair to the
east and/or southeast. The property is bordered to the south by railroad tracks. Agricultural fields
are located to the north, west and east. An existing residence is located further to the east near
Weld County Road 41.
PROPOSED CONSTRUCTION
As we understand it, the project will likely consist of building a 60 foot by 40 foot slab on grade
structure near the western property boundary and determining the soil profile for a railroad spur on
the property.
•
• Pickett Engineering
Andersen Properties
Northern Colorado Geotech Project No. 101-04
SITE EXPLORATION
A total of three test borings were drilled on June 7, 2004. The borings were drilled to approximate
depths of 15 feet at the locations shown on the Site Plan, Figure 1. All borings were advanced with
a truck-mounted drilling rig, utilizing 4-inch diameter solid stem augers.
The borings were located in the field by pacing from property lines and/or existing site features.
Relative surface elevations at the boring locations were obtained by interpolation from a
topographic map provided by King Surveyors. The accuracy of boring locations and elevations
should only be assumed to the level implied by the methods used to determine each.
Lithologic logs of each boring were recorded by an engineering geologist during the drilling
operations. At selected intervals, samples of the subsurface materials were taken by driving split-
spoon and/or ring samplers. Standard penetration measurements were recorded while driving a
split-spoon and/or ring sampler into the subsurface materials. The standard penetration test is a
useful index in estimating the density of the materials encountered.
Groundwater conditions were evaluated in each boring at the time of subsurface exploration, and
one day after the drilling.
Laboratory Testing
The samples retrieved during the subsurface exploration were returned to our laboratory for
observation by the project manager. The soils were classified in general accordance with the
Unified Soil Classification System. At that time, the field descriptions were confirmed or modified
and an applicable laboratory testing program was formulated. Boring logs were prepared and are
attached with this report.
Laboratory tests were conducted on selected samples and are presented on the boring logs and
attached laboratory test sheets. The test results were used for the geotechnical engineering
analyses, and the development of foundation and earthwork recommendations.
Selected samples were tested for the following engineering properties:
• Water Content • Atterberg Limits
• Dry Density • Percent Fines
• Consolidation • Expansion
• Compressive Strength • Resistivity
• pH
• 2
• Pickett Engineering
Andersen Properties
Northern Colorado Geotech Project No. 101-04
SUBSURFACE CONDITIONS
Soil Conditions
Soils at the site generally consisted of sandy lean clay to depths of approximately 6% to 15 feet.
The clay soils are underlain by silty sand with gravel in Test Borings 2 and 3. Summary boring logs
are attached with this report.
Groundwater Conditions
Groundwater was not observed in any test boring at the time of field exploration, nor when checked
one day after the drilling. These observations represent groundwater conditions at the time of the
field exploration, and may not be indicative of other times, or at other locations. Groundwater
conditions can be expected to fluctuate with varying seasonal and weather conditions, and other
factors.
Field Test Results
Field test results indicate that the clay soils vary from medium to stiff in consistency. The sand
soils vary from loose to medium dense in relative density.
Laboratory Test Results
Laboratory test results indicate that the soils have low expansive potential and low load bearing
capabilities.
DESIGN RECOMMENDATIONS
Foundation Design
Based on the results of our subsurface exploration and the results of the laboratory testing, it is our
opinion that a spread footing foundation system may be used for support of the proposed structure.
The footings should be placed on undisturbed soils and/or engineered fill material.
Design and construction recommendations for foundation systems and other earth connected
phases of the project are outlined below.
. 3
•
• Pickett Engineering
Andersen Properties
Northern Colorado Geotech Project No. 101-04
Footing Foundations
Based on the results of our subsurface exploration and laboratory testing, it is our opinion that a
spread footing foundation system bearing upon undisturbed soil and/or engineered fill may be used
for support of the proposed structure. The footings may be designed for a maximum bearing
pressure of 1,500 psf. The design bearing pressure applies to dead loads plus design live load
conditions. The design bearing pressure may be increased by one-third when considering total
loads that include wind or seismic conditions.
Exterior footings should be placed a minimum of 30 inches below finished grade for frost protection
and to provide confinement for the bearing soils. Finished grade is the lowest adjacent grade for
perimeter footings.
Footings should be proportioned to reduce differential foundation movement. Proportioning on the
basis of equal total movement is recommended; however, proportioning to relative constant dead-
load pressure will also reduce differential movement between adjacent footings. Total movement
resulting from the assumed structural loads is estimated to be on the order of 3/4 inch or less.
Differential movement should be on the order of 1/2 to 3/4 of the estimated total movement.
• Additional foundation movements could occur if water from any source infiltrates the foundation
soils; therefore, proper drainage should be provided in the final design and during construction.
Foundations and masonry walls should be reinforced as necessary to reduce the potential for
distress caused by differential foundation movement. The use of joints at openings or other
discontinuities in masonry walls is recommended.
Foundation excavations should be observed by Northern Colorado Geotech. If the soil conditions
encountered differ significantly from those presented in this report, supplemental recommendations
may be required.
Surface Drainage
Positive drainage should be provided during construction and maintained throughout the life of the
proposed project. Infiltration of water into utility or foundation excavations must be prevented
during construction. Planters and other surface features which could retain water in areas adjacent
to the building or pavements should be sealed or eliminated. In areas where sidewalks or paving
do not immediately adjoin the structure, we recommend that protective slopes be provided with a
minimum grade of approximately 5 percent for at least 10 feet from perimeter walls. Backfill
• 4
• Pickett Engineering
Andersen Properties
Northern Colorado Geotech Project No. 101-04
against footings, exterior walls, and in utility and sprinkler line trenches should be well compacted
and free of all construction debris to reduce the possibility of moisture infiltration.
Downspouts, roof drains or scuppers should discharge into splash blocks or extensions when the
ground surface beneath such features is not protected by exterior slabs or paving. Sprinkler
systems should not be installed within 5 feet of foundation walls. Landscaped irrigation adjacent to
the foundation system should be minimized or eliminated.
Floor Slab Design and Construction
Some differential movement of slab-on-grade floor systems is possible should the subgrade soils
become elevated in moisture content. To reduce potential slab movements, the subgrade soils
should be prepared as outlined in the earthwork section of this report.
Additional floor slab design and construction recommendations are as follows:
• Positive separations and/or isolation joints should be provided between slabs and all
foundations, columns or utility lines to allow independent movement.
• • Control joints should be provided in slabs to control the location and extent of
cracking.
• Interior trench backfill placed beneath slabs should be compacted in accordance
with recommended specifications outlined below.
• In areas subjected to normal loading, a minimum 4-inch layer of sand, clean-graded
gravel or aggregate base course should be placed beneath interior slabs.
• Floor slabs should not be constructed on frozen subgrade.
Exterior slabs-on-grade, exterior architectural features, and utilities founded on, or in backfill may
experience some movement due to the volume change of the backfill. Potential movement could
be reduced by:
• minimizing moisture increases in the backfill
• controlling moisture-density during placement of backfill
• using designs which allow vertical movement between the exterior features and
adjoining structural elements
• 5
• Pickett Engineering
Andersen Properties
Northern Colorado Geotech Project No. 101-04
• placing effective control joints on relatively close centers
General Earthwork
All earthwork on the project should be observed and evaluated by Northern Colorado
Geotech. The evaluation of earthwork should include observation and, testing of
engineered fill, subgrade preparation, foundation bearing soils, and other geotechnical
conditions exposed during the construction of the project.
Site Preparation
Strip and remove existing vegetation, debris, and other deleterious materials from proposed
building and pavement areas. All exposed surfaces should be free of mounds and
depressions which could prevent uniform compaction.
Stripped materials consisting of vegetation and organic materials should be wasted from the
site, or used to revegetate landscaped areas or exposed slopes after completion of grading
operations.
• If unexpected fills or underground facilities are encountered, such features should be
removed and the excavation thoroughly cleaned prior to backfill placement and/or
construction.
It is anticipated that excavations for the proposed construction can be accomplished with
conventional earthmoving equipment.
The individual contractor(s) is responsible for designing and constructing stable, temporary
excavations as required to maintain stability of both the excavation sides and bottom. All
excavations should be sloped or shored in the interest of safety following local, and federal
regulations, including current OSHA excavation and trench safety standards.
Fill Materials and Placement
All exposed areas which will receive fill should be scarified to a minimum depth of eight
inches, conditioned to near optimum moisture content, and compacted.
The placement of soils on the site should be observed by Northern Colorado Geotech. The
fill should be assessed for suitability of use in the proposed fill and tested for placement
including compaction percentage and moisture content.
• 6
•
Pickett Engineering
• Andersen Properties
Northern Colorado Geotech Project No. 101-04
Engineered fill should be placed and compacted in horizontal lifts, using equipment and
procedures that will produce recommended moisture contents and densities throughout the
lift. Recommended compaction criteria for engineered fill materials are as follows:
Clean on-site soils or approved imported materials may be used as fill material.
Imported soils (if required) should conform to the following:
Percent fines by weight
Gradation (ASTM C136)
6" 100
3" 70-100
No. 4 Sieve 50-100
No. 200 Sieve 60 (max)
• Liquid Limit 30 (max)
• Plasticity Index 15 (max)
• Minimum Percent
Material ASTM D698)
Scarified subgrade soils 95
On-site and imported fill soils:
Beneath foundations 95
Beneath slabs 95
On-site or imported clay soils should be compacted within a moisture content range of 2
percent below, to 2 percent above optimum. Granular soils should be compacted within a
moisture range of 3 percent below to 3 percent above optimum unless modified by the
project geotechnical engineer.
GENERAL COMMENTS
The analysis and recommendations presented in this report are based upon data obtained from
borings performed to obtain representative subsurface conditions at the site. Variations in the soil
• 7
• Pickett Engineering
Andersen Properties
Northern Colorado Geotech Project No. 101-04
between borings will occur. Northern Colorado Geotech should be present during construction to
observe the excavation and construction procedures and confirm or modify our recommendations.
The scope of services for this project does not include either specifically or by implication any
environmental assessment of the site.
This report has been prepared in accordance with generally accepted geotechnical engineering
practices in this area at this time. No warranties, either express or implied, are intended or made.
•
•
• 8
i • !
RAILROAD AlMal
IIIIIIo.l''
RAILROAD SWITCH �� .
RAILROAD SWITCH RAILROAD _
ELECTRIC TRANSFORMER
ELECTRIC
TRANSFORMER
411
ONo.3
''— � D ���� � FENCE
�� •_ GAS WELL EQUIPMENT BORING LOCATION PLAN
��-�- ANDERSEN PROPERTY
WCRe4 AND 33 1/2
15'VER GREELEY,COLORADO
FOR MICHAEL HEIN
4®,CMP DUKE ENERGY WRIT
LE�CBOXDGE Northern P'as°N°' 1D1-04
TOP ELEV.4690.9 GAS MARKER ON POST �O�Of2dO sok v=200'
Geotech DS: 7-7-04,
28502BIh 8tre54311111
UnR27
a v, �BOB31 Ri°dMr DML
alwnx (870 5065244
_ Fer {870;5065242 Rua,. 'I .
• II
LOG OF BORING No. 1 Sheet 1 of 1
• CLIENT ARCHITECT/ENGINEER
Pickett Engineering
SITE Weld County Roads 391/2 and 64 PROJECT
' Greeley, Colorado Andersen Properties
SAMPLES TESTS o(7
m
ur Be a w z
X 10
O _
F N Z> W l0 ZW I-ZLL
U .-W o! j0 W Z L.0
�Oz
a x 3J WW W KW N C os oi=cW)
CC CI_ �? a o¢ �U ¢� Ogg
Approx. Surface Elev.: 4706.0 ft. a o m z z ?? 2 o a x� a o_a
6"TOPSOIL l':i. 4 1 SS 18 17
0.5 4705.5 -1
SANDY LEAN CLAY
Brown to tan, moist, edium to stiff • —
s 2 RS 12 21 104 2,500 3,600
ohm-cm
5—
• /�f -
. 10 3 SS 12 19
10-
1-1 8 4 SS 12 25
15.0 4691.0%/y// t5 �V1
BOTTOM OF BORING
• WATER LEVEL OBSERVATIONS Northern AVGoradoSTARTED 6l1/04 FINISHED 6/7/04
wL None wDeotech DRILL co. Drilling Eng DRILL RIG CME-55
a WL None A.B. 2956 29th Street,Unit 21 LOGGED BY DEC APPROVED DML
O. Greeley,Colorado 80631
When Checked 1 Day A.B. Phone: 970-506-9244 NCG PROJECT NO. t 01-D4
S Fax: 970-506-9242
LOG OF BORING No. 2 Sheet 1 of 1
• CLIENT ARCHITECT/ENGINEER
Pickett Engineering
SITE Weld County Roads 39%and 64 PROJECT
Greeley,Colorado Andersen Properties
SAMPLES TESTS 0 r7
N
K BR - n W z
--
_ = cb ) id m ≥O H W WW - OZ
KW O F
CI w O 2> > 0- ' O >U ¢0 5N¢
Approx.Surface Elev.: 4696.0 ft. o0 m z z ?? in D. =I- 5 a.
6"TOPSOIL :*.i 7 1 SS 18 15 '
0.5 4695.5:.%: j
j
BANDY LEAN CLAY I
Brown to tan, moist, medium to stiff
j —
8 2 RS 12 13 115 5,000 33/16/67
, 5-
• 7.0 4689.0///// -
SILTY SAND WITH GRAVEL
•
Tan, moist, medium dense ,+ 19 3 SS 12 5
1
10-
22 4 SS 12 2
15.0 4681.0 15 lA
BOTTOM OF BORING
• WATER LEVEL OBSERVATIONS Northern�olorado STARTED 6/7/04 FINISHED 6/7/04
WL None W.D. Geotech DRILL CO. Drilling Eng DRILL RIG C I
ME-55
a WL None A.B. 2956 29th Street,Unit 21 LOGGED BY DBC APPROVED DML
o Greeley,Colorado 80631
o• When Checked 1 Day A.B. Phone: 970-506-9244
970-506-9242 NCG PROJECT NO. 101-04
Fax:
• lit
LOG OF BORING No. 3 Sheet 1 of 1
CLIENT ARCHITECT/ENGINEER
•
Pickett Engineering
SITE Weld County Roads 391/2 and 64 PROJECT
Greeley, Colorado Andersen Properties
SAMPLES TESTS
0 in
0 in— cc ae n iii w z
iu
o LL :7,-
O0 w ?0 D w aw rl0z
a =
� CO W Ew y a 02 a~uJ
CC W OJ� D a ore 0— KU ¢K CaygE
Approx. Surface Elev.: 4695.0 ft. o a m z z ?z 2 o a =i- o.a
0.5 6"TOPSOIL 4694.5:a Via, I 8 1 SS 18 20
SANDY LEAN CLAY �
�
Brown to tan, moist, medium to stiff —
7 2 RS 12 21 110 2,000 pH 7.2
s-
11) 6.5 4688.5� _
SILTY SAND WITH GRAVEL
Tan, moist,loose to medium dense —
—( 6 3 SS 12 14
10-
1 IV1 14 4 SS 12 3
-
15.0 4680.0 15
BOTTOM OFBORING
• WATER LEVEL OBSERVATIONS AC..orthern STARTED 617/04 FINISHED 6/7/04
Colorado
WL None W.D. Geotech DRILL CO. Drilling Eng DRILL RIG CME-55
u• WL None A.B. 2956 29th Street,Unit 21 LOGGED BY DBC APPROVED DML
4 Greeley,Colorado 80631
• When Checked 1 Day A.B. Phone: 970-506-9244 NCG PROJECT NO. 101-04
— Fax: 970-506-9242
0 Ill
3 1 — I — ,
• H
I
-2 —.
i
-1
1
e
1
z 1
c
co
Li
• 3 1
4 -
•
51 l i 10
0.1 1
STRESS,ksf
Specimen Identification Classification 1 Yd MC%
• 1 3.0 Sandy Lean Clay 104 20
-
• _
CONSOLIDATION TEST
Northern 2956 29th Street,unit 21 Client: Pickett Engineering Number: 101-04
Colorado Greeley,Colorado 60631
Phone: 970506-9244 Project: Andersen Properties
r Geotech Fax: 970-506-9242
Location: Weld County Roads 39%and 64 -
Hello