HomeMy WebLinkAbout20001299.tiff LhaaER OF TRANSMITTAL
TO: FROM: FRONT RANGE ROOFING SYSTEMS, INC.
Weld County Dept. of Purchasing P.O. BOX 2543
915 10th Street GREELEY, COLORADO 80632
Greeley, Colorado 80631 (970) 353-2322
(303) 893-3908 - Fax
ATTN: DATE: 5-4-00
REFERENCE: Marlborough Bldg
The following materials are being transmitted to you regarding the
referenced project. If you have not received the materials indicated
herein, please call our office for verification within ten days of this
transmittal; otherwise, we will assume you have received said materials
as noted. Thank you.
SHIPPED VIA: Mail ENCLOSED UNDER SEPARATE COVER
MATERIALS AS NOTED BELOW:
ITEM # DATE DESCRIPTION
1 5-4-00 FiberTite 15 year Commercial Roofing
for the Marlborough Bldg
PLEASE TAKE THE REQUESTED ACTION:
APPROVAL REVIEW AND COMMENT
NO ACTION REQUIRED FOR YOUR USE (REQUESTED)
X RETURN AS REQUESTED FOR BID DUE
OTHER ACTION/REMARKS:
Enclosed please find the original warranty and a copy. They both need
to be signed by an owner. The original is to be retained by the owner
and the signed copy needs to be mailed to Seam4n Corp. in the enclosed
envelope. Thank you! C
COPY TO: SIGNED: ( Link \ 1
C:0YlV(2,r211CenCeO. /
.')l/7�7r•fri 2000-1299
C. Cv Kv We ."Fe vv vv ., an ofoo pi,- ar . _ wi `s'/�\/
13.::' �:.R �,41''1 i... / ,• , .; 't'r ' / 251 if' >+ �.'� �:J
\�% F 1161 IITF''WAIF IEF VFNFATF ITF 9TF_ATF AiFae.NE:W VP W WriiF'9TF aVF.W /F WE''W.:VFW 41F ga ''sf 14
li
\ e St m , . o
Seaman �eaite
Corporation WARRANTY FOR COMMERCIAL ROOFING ROOFING SYSTEMS 40 a /,
W Weld County li ;ap
9,000
�V t Sodding Ovmelt'>l/ame �— area of Roofing Project
! , W
915 10th Street, Greeley CO. Torn Ghidotti ' . 24
'Budding Owner's Address Seaman Corporation Inspector 711 r
\�/iSit Marlborough Building, Greeley CO. 04—26—2000 V
I
�. Address&Location ofBuu1drng Date of Comp/tion an/Acceptance as(,. -,
>\)v�' T SEAMAN CORPORATION warrants to the owner named above ('Owner') of the building described herein that, subject ?ft t.,
'\` it..: to the Terms, Conditions, and Limitations set forth below, for a period of Fifteen (i5) years commencing with the date ,U
>. F of final inspection and acceptance. Seaman Corporation will repair any leaks in the FiberTite Roofing Systems furnished to 'w
>v+) F said commercial building attributable to Roofing Membrane provided by Seaman Corporation and/or defective T;. ,.
. workmanship provided by Seaman Corporation or its authorized FiberTite Single Ply Roof Applicator.
oU
a
Terms, Conditions & Limitations y
,
,(/;\ W I. The Roofing System must have been installed by an Authorized FiberTite Single Ply Applicator and must have been inspected and approved for y ���0. warranty by Seaman Corporation_ This warranty issuance will not relieve the installation contractor from performing additional work should final II :/
i inspection discover any failure to comply with Seaman specifications or shortcomings in workmanship. _
p� 9 2 Throughout the term of this warranty,Seaman Corporation shall be given free access to the roof of the commercial building described herein during 71 .":',/4
.77.......„,,,,p. regular business hours. 4 /
R= 3. The Owner shall obtain Seaman Corporations prior written approval before making any alterations of said roof or installing any structu-es, fixtures on e
y rt or through said roof.
F 0. Seaman Corporation shall have no obligation under this warranty until all bills for installation, supplies and service have been pail in full to the ft \.'4
././...,,,. .. . .. Authorized FiberTite Single Ply Roof Applicator and any material suppliers.including Seaman Corporation. 4 S
1 F 5. Owner shall give Seaman Corporation written notice at its address set forth herein not more than thirty(30)days after discovery of any leaks'n the '
tip fp Roofing System. .
p\,;r (r & if,after inspectlon by Seaman Corporation,leaks in the Roofing Membrane System are found,in good faith determination of Seaman Corporation, to 4
+% Y,' be the result of defects in the Roofing Membrane provided to the Owner by Seaman Corporation and/or the workmanship orovided be Seaman 'y l'
' ` 1117. Corporation and/or and Authorized FiberTite Single Ply Roofing System Applicator,Seaman Corporation will repair any leaks in the Roofing System at •Y'
fed its expense but in no event shall Seaman Corporation's obligation over the lifetime of the warranty exceed the Owner's original cost of the installed roof.
% R. 7.The Owner will be responsible for the cost of investigation if any leak is determined not to be covered by this Agreement. 4
%k :, U.' 8. The warranty stated herein is the SOLE AND EXCLUSIVE REMEDY for failure of the Roofing System
SEAMAN CORPORATION SHALL UNDER yz '3`
Y NO CIRCUMSTANCES BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO DAMAGES TO /Vr OTHER COMPONENTS OF THE ROOF,THE COMMERCIAL BUILDING DESCRIE3ED HEREIN OR THE CONTENTS OF SAID BUILDING . �\
1 M 0.This warranty shall not be applicable to nor shall Seaman Corporation be responsible for damage or loss caused in whole or in part by
V : 4
. natural disasters inducing, not limited to bghtning,hurricanes,tornadoes or earthquakes;vandalism,cMil dsobedience or acts of war;alteration of the roof or installation of structures. y� r 1T' fixtures or utilities on or through the roof without the prior wntten approval of Seaman Corporation as previously slated in section three(3t..settling,warping,defective condition,corrosion, .-
\\i/V{ or other failure of the structure or substrata to which the Roofing System is attached;any chemical contaminants injurious to the Roof System that have not been specifically approved by I4 \
the company via the Materials Submittal&Warranty Request form;negligence or failure by the Owner or any lessee to reasonably maintain the roof;traffic or s--:orage at materials on the I•.- r 4
1 ' ' tool,infiltration or condensation of moisture in,through,around or above the walls of the building;acts of negligence or misuse by the Owner or any othery tC Corporation,or an Authoneed FiberTite Single Ply Roof Applicator,and/or failure of any matedal or component party other than Seaman
.� bo not furnished by Seaman Corporation.
•
ilar4 /{' 'le. This agreement may be assignable to a subsequent building Owner,only if the above named owner requests in writing that Seaman Corporation y �\
consent to an assignment of this warranty to the purchaser of the building from Owner,which consent will not be unreasonably withheld. li
O.
/ L 'I1. SEAMAN CORPORATION MAKES NO WARRANTY THAT THE ROOFING SYSTEM IS MERCHANTABLE OR FIT FOR ANY PAR TICUI AR 'r
N . !r, PURPOSE, THERE BEING NO WARRANTIES, EXPRESS OR IMPLIED, WHICH EXTEND BEYOND THE FACE HEREOF. NO EMPLOyEF OR �L/
REPRESENTATIVE HAS AUTHORITY TO MAKE ANY REPRESENTATIONS OTHER THAN THOSE STATED HEREIN.1 Ir!
ay
',1/4,:.'„4. 0
l .,' v SEAMAN CORPORATION T��
- -
f r Building Owners*nature (05710* ByHs: !R X�
i a 672f7 — —
n/a +t rr
r ; R Title Dal .tit \ i;.
_ ''t 4
7n>.::.,<: V' Warranty Exclusions p
F n/a Note Roofing installations for personal,family or household X�;.
purposes ARE NOT WARRANTED HEREUNDER. i
9 — . ';4
P/ IZ Warranty Inclusions y
Serial No. 2000440 S }
\ 1000 VENTURE BLVD.'WOOSTER, OH 44691 I a b
.:',•::,.. it 31tr-a4k Ate:Atli Al .4.k.-41& 91& iite sit I1& 91& 9rF69fk;9/k,s s&.SEk,M 94:Mk st11:9ik;sa i ilk:41Rr8 ,,:,-)AN
et
Seaman Corporation
Innovative Customer Solutions through Fiber and Polymer Technology
1000 VENTURE BLVD. • WOOSTER, OHIO 44691 • TELEPHONE(330)262-1 I I I • FAX(330)263-6950
TO: FiberTite Applicators
FROM: Jerry Beall
RE: FiberTite Warranty
Congratulations of the completion of another FiberTite® Single-Ply Roof System.
Please find enclosed the warranty for the FiberTite System.
You will find the original warranty and two copies. One copy is for your records;
one copy and the original warranty are to be signed by the building owner. The
building owner should retain the original and send the signed copy to Seaman
Corporation for our records.
I have enclosed a self-addressed envelope for your convenience in returning our
copy. I would like to thank you in advance for your cooperation and help with the
completion of the warranty.
Sere ,
Jerry Beall
Technical Service Manager
JB/jrg
Enclosures
® FiberTite Is a registered trademark of Seaman Corporation
We are an Equal Opportunity Employer, M/F/H/V.'
Seaman Corporation
Fiber Tite
ROOFING SYSTEMS
MANUFACTURER OF FIBERTITE SINGLE PLY ROOF
1000 VENTURE BLVD. • WOOSTER, OHIO 44691 • TELEPHONE 800-927-8578 • FAX (330)263-6950
FIBERTITE® ROOFING SYSTEMS
ROOF MAINTENANCE PROGRAM
TO: The Building Engineering and/or Maintenance Department
The FiberTite Single-ply Roof System has been engineered and installed to service your building for many years to come The
Seaman Corporation manufactured membrane consists of a puncture and abrasion resistant fabric with an ethylene inter-polymer
(EIP)coating that can withstand harsh weathering and environmental hazards that most roof coverings are Incapable of enduring.
However, to obtain optimum performance from your FiberTite roof, it is important to establish a regular maintenance schedule
to insure that your building roof is free of any conditions that can cause unnecessary injury to the roof deck, leading to expensive
repairs and possible damage to the building interior.
One of the first and best rules to follow in protecting your roof is to establish a policy of keeping unauthorized people off your
roof and to minimize the number of service personnel trips on your roof. Put locks on all doors leading to your roof as well as
post a sign that disallows entrance to unauthorized personnel.
We have enclosed pressure sensitive labels that should also be posted on your roof exit doors and refers to the slippery nature
of the FiberTite Single-ply Roof when it becomes wet from rain, snow, or ice conditions. Proper safety shoes should be worn
if it is imperative that roof top work be accomplished under these weather conditions.
It you have a busy roof, i.e., one with much foot traffic, you should install walkways on the roof. This action will minimize the
opportunity of any unnecessary damage to the FiberTite membrane.
The major items to check for during a roof maintenance inspection are: punctures in the membrane sheet; open seams at the
membrane overlaps and at the roof penetrations (soil stacks, curbs, platforms, etc.) as well as the parapet walls and/or edge
details(use a blunt instrument,such as a screw driver, to inspect seam integrity);caulking at the termination bars,surface mounted
reglet and pitch pan sealants, any loose fasteners and nails, both on the roof field itself as well as on the wall and edge details
and check to assure that drains and gutters are unclogged and that there is no water ponding on the roof that requires remedial
action.
It is important to consider the roof covering whenever you should add new products and or processes to your building operation
that will allow for chemical contaminant venting onto your roof. For that reason we have listed below the chemicals that can cause
harm to the FiberTite roof covering, especially if left ponding for several months. It is equally important to determine the com-
patibility of the roof system should the building be used for any purpose other than what was ongoing or planned when the roof
covering system was selected and installed. This important fact is often overlooked when a building is converted for a new
purpose. Any installation of new roof top equipment, such as air conditioning equipment and the like, requires the service of
a FiberTite contractor to install new fleshings and the like to assure that no harm is caused to the integrity of the roof covering.
You should discuss with your local authorized FiberTite roofing contractor a maintenance service contract which allows for
professional annual inspections and immediate corrective action for any potential roof damaging problems. Your authorized FiberTite
contractor has been selected because of his thorough knowledge of roof top technology and full service professional abil.ties
solving and eliminating roof damaging problems. Contact your FiberTite representative or FiberTite Technical Service Depart-
ment for any assistance in locating these authorized contractors or for any questions about FiberTite Roofing System you need
answered.
Harmful chemicals if left standing on FiberTite for a prolonged period of time:
Acetic Acid Aromatic Hydrocarbons Asphalt Materials
Benzene Chiorox Cooking Oil above 1400F.
Ethyl Acetate Furfural Gasoline
Methyl Ethyl Ketone (MEK) Nitric Acid Paint Thinners
Phenol Phosphoric Acid 750/0 Phthalate Plasticiser Above 2000F
Solvent Degreasers Toluene Zylene
=iberTite is a registered trademark of Seaman Corporation
Seaman Corporation
Fiber Tite
ROOFING SYSTEM
MANUFACTURER OF FIBERTITE SINGLE PLY ROOF
• 1000 VENTURE BLVD. • WOOSTER,OHIO 44691 • TELEPHONE 800-927-8578 • FAX(330)263-6950
Web Site:Please visit us at www.seamancorp.com
PARTIAL CHEMICAL REAGENT LIST
COMPATIBLE WITH FIBERTITE® MEMBRANE
Ammonium Phosphate Kerosene
Ammonium Sulphate Magnesium Chloride
Antifreeze (Ethylene Glycol) Magnesium Hydroxide
Animal Oil Methyl Alcohol
ASTM Fuel A Mineral Spirits
ASTM Oil #2 Naptha
Calcium Chloride Solutions Lactic Acid
Calcium Hydroxide Phosphoric Acid (50%) (100%)
20% Chlorine Solution Potassium Chloride
Clorox Potassium Sulphate
Conc. Ammonium Hydroxide Raw Linseed Oil
Corn Oil SAE-30 Oil
Crude Oil Salt Water
Diesel Fuel Sea Water
Ethyl Alcohol Sodium Acetate Solutions
Fertilizer Solution Sodium Bisulphate Solutions
#2 Fuel Oil Sodium Hydroxide (60%)
#6 Fuel Oil Sodium Phosphate
Glycerin Sulfuric Acid (50%)
Hydraulic Fluid 50% Tanic Acid
Hydorchloric Acid (50%) Transformer Oil
Hydrofluoric Acid (5%) Transformer Oil (PCB)
Hydrofluoric Acid (50%) Turpentine
Hydrofluosilicic Acid (30%) Urea Formaldehyde
Ivory Soap Vegetable Oil
JP-4 Jet Fuel Zinc Chloride
The above compatibility list must be conditioned by chemical concentrate percentage and
temperature. For example, if animal fats are vented through the stack at high temperatures,
2OO0F, the membrane may be scorched and damaged. Please send to our attention any
specific data pertinent to your needs for us to analyze.
FiberTite is a registered trademark of Seaman Corporation
ROOFING SYSTEMS
Patent No.4,546,589
ACCESS RESTRICTED TO AUTHORIZED PERSONNEL
PLEASE OBSERVE THE FOLLOWING PRECAUTION
STAY ON WALKWAYS WHEN PROVIDED
ROOF IS SLIPPERY WHEN WET
NO SMOKING
PROTECT THE MEMBRANE SHOULD EXTENSIVE ACTIVITY BE RE
PLEASE NOTIFY THE OWNER SHOULD ACCIDENTAL DAMAGE C
PLEASE NOTIFY THE OWNER SHOULD ANY DAMAGE BE OBE
FOR WARRANTY SERVICE CONTACT:
SEAMAN CORPORATION
FIBERTITE CUSTOMER SERVICE
800 / 927-8578