HomeMy WebLinkAbout20003102.tiff a DEPARTMENT OF BUILDING INSPECTION 1555 N. 17TH AVENUE GREELEY, COLORADO 80631 111 119 PHONE (970) 353-6100, EXT.3540 C FAX (970) 304-6498 9 COLORADO September 20, 2000 Mike Jones/Reach Ministries USR-1292 1. Proper building permits shall be obtained prior to any construction, demolition, or excavation. Part of the permit application process includes a complete plan review. 2. There are two buildings for the site. Item number 8 of the "Use by Special Review Questionnaire" states: "The proposed building will be raised 24" above the existing grade level. The vegetation layer of topsoil will be removed (approximately 8"). The foundation will then consist of a 16" base of 95% compacted clean dirt, a 4" layer of road base and a 4" concrete slab." The construction type of the building is not specified. The geotechnical report prepared by CDS Engineering Corporation, indicates some areas of concern regarding the possibility of ground movement and also a soil bearing capacity of only 1,000 per square foot. Therefore, the foundation will need to be designed by an engineer and be based upon the recommendation of the geotechnical report. The report recommended specific landscaping features, a perimeter drain, and an open hole inspection. Also, any fill material shall contain no rock or similar irreducible material with a maximum dimension greater than 12 inches. All fills shall be compacted to a minimum of 90 percent of maximum density (or as prescribed by the engineer). Engineering reports shall be supplied for all fill material. Any heated areas or areas containing plumbinglrequire frost protection. Our frost depth is 30". 3. Occupancy separations are required between different portions of the building containing different uses. (302.1, UBC) 4. All buildings shall maintain distances from property lines and adjacent buildings as outlined in Section 503 and Table 5-A of the UBC. 5. The design and construction of accessible buildings and building elements shall be in accordance with Chapter 11 and Appendix Chapter 11 of the UBC. Service,Teamwork, Integrity,Quality EXHIBIT 12 2000-3102 6. Electrical work shall conform to the 1999 National Electrical Code (NEC). Electrical services over 200 amps require fault current calculations, load calculations, and a one-line diagram. All electrical and plumbing work shall be done by Colorado licensed electrical and plumbing contractors. 7. Separate building permits are required for all monument signs. Signs shall adhere to Section 42 of the Weld County Zoning Ordinance and Section 2.8 of the Weld County MUD Ordinance as applicable. Engineering may be required. 8. Electrical permits shall be obtained for all electrical work. For instance, electrical permits are needed for any site lighting or irrigation equipment. 9. Complete drawings shall be submitted to the Galeton Fire District for review. 10. Additional requirements or changes may be required when building applications or plans are reviewed by the Weld County Building Inspection Department or the Fire District. Sin r ly, Dave Building Official Service,Teamwork, Integrity,Quality ° MEMORANDUM O: Kim Ogle DATE: September 25, 2000 IWeld County Planning OFROM: Sheble McConnellog eu ,Environmental Health Services • COLORADO RE: Case Number: USR-1292 NAME: Jones,Mike/Reach Ministeries Environmental Health Services has reviewed this proposal for an office & storage building for Reach Workcamps.Our Department recommends approval. The following conditions are recommended to be part of any approval: 1. All liquid and solid wastes (as defined in the Solid Wastes Disposal Sites and Facilities Act, 30-20-100, C.R.S., as amended) shall be stored and removed for final disposal in a manner that protects against surface and groundwater contamination. 2. No permanent disposal of wastes shall be permitted at this site. 3. Waste materials shall be handled, stored, and disposed in a manner that controls fugitive dust, blowing debris, and other potential nuisance conditions. 4. This facility shall adhere to the maximum permissible noise levels allowed in the Commercial Zone as delineated in 25-12-103 C.R.S., as amended. 5. Adequate toilet facilities shall be provided for the employees. 6. An individual sewage disposal system is required for the proposed facility and shall be installed according to the Weld County Individual Sewage Disposal Regulations. The septic system is required to be designed by a Colorado Registered Professional Engineer according to the Weld County Individual Sewage Disposal Regulations. 7. The facility shall utilize the existing public water supply. (North Weld Water District). SM/ske/usr 1292 Weld County Planning De,wt. 0EP 26 2000 EXHIBIT C i Da Wald County Plrnning Dept. 312- 3 2000 of S+f .3q2 ovn WG25I LIMED W SrCQ Weld County Referral September 8, 2000 Ci COLORADO g, ' The Weld County Department of Planning Services has received the following item for review: Applicant Mike Jones / Reach Case Number USR-1292 Ministries Please Reply By October 2, 2000 Planner Kim Ogle Project Commercial Use, (Office and Storage Building) in the Agricultural Zone District. Legal Lot A of RE-1028; being part of the SE4 of Section 18, Township 6 North, Range i 64 West of the 6th P.M., Weld County, Colorado.• Location 415 feet north of SH 392; west of and adjacent to WCR 51. Parcel Number 0801 18 000074 ----- The — — The application is submitted to you for review and recommendation. Any comments or recommendation you consider relevant to this request would be appreciated. Please reply by the above listed date so that we may give full consideration to your recommendation. Any response not received before or on this date may be deemed to be a positive response to the Department of Planning Services. If you have any further questions regarding the application, please call the Planner associated with the request. Weld County Planning Commission Hearing (if applicable) November 21, 2000 ❑ We have reviewed the request and find that it does/does not comply with our Comprehensive Plan ❑ We have reviewed the request and find no conflicts with our interests. ❑ See attached letter. Comments: / 1 �}-^- 8c.{. e/Y1.5 p cop O5a1 l . ()DOT C(7Y1C�.t/rkS l/� u /J4.. VJ1`C t�1 rQ k\AQ F1I J54 ,)a2 conv i'cm . eoun tnzeA5 -h) O ackunnivW if via pn5 t ereaf95 {'ne naizcc -Co{ ivApfovewtenk — Signaturet ` Date cf /O r) Agency C�J CiUoT i\ccCs5 111 +Weld County Planning Dept. :•1555 N. 17th Ave.Greeley,CO. 80631 :x(970)353-6100 ext.3540 )(970)304-6498 fax EXHIBIT 19 '4 *ktrigsrP Weld County Referral WII September 8, 2000 D C. COLORADO The Weld County Department of Planning Services has received the following item for review: Applicant Mike Jones/ Reach Case Number USR-1292 Ministries Please Reply By October 2, 2000 Planner Kim Ogle Project Commercial Use, (Office and Storage Building) in the Agricultural Zone District. Legal Lot A of RE-1028; being part of the SE4 of Section 18, Township 6 North, Range 64 West of the 6th P.M., Weld County, Colorado. Location 415 feet north of SH 392; west of and adjacent to WCR 51. P Parcel Number 0801 18 000074 The application is submitted to you for review and recommendation. Any comments or recommendation you consider relevant to this request would be appreciated. Please reply by the above listed date so that we may give full consideration to your recommendation. Any response not received before or on this date may be deemed to be a positive response to the Department of Planning Services. If you have any further questions regarding the application, please call the Planner associated with the request. Weld County Planning Commission Hearing (if applicable) November 21, 2000 ❑ We have reviewed the request and find that it does/does not comply with our Comprehensive Plan g We have reviewed the request and find no conflicts with our interests. ❑ See attached letter. Comments: ttpcn culIgNk C/NCUICh 0,101)-91 91A UIVJ mn G h ) no Cao*i O. V t ex113 I kr,WQ Pn i rd a neton `-f�hQ. Chou rt rncoM peeco i it. Signature Ri\ � �I I��}1� Date q Agency 7 1 c# Icitrvt :•Weld County Planning Dept. fi1555 N 17th Ave. eeley,CO. 80631 +(970)353-6100 ext.3540 +(970)304-6, EXHIBIT lb old County Planning Dept. MEMORANDUM ;,vj- 06 2000 E�,,, � b ITO: Kim Ogle, Planner II DATE: Ocfo e�4,, 2 � OFROM: Donald Carroll, Engineering Administrator • SUBJECT: USR-1292, Mike Jones/Reach Ministries COLORADO The Weld County Public Works Department has reviewed this proposal. This project falls under the purview of the Weld County Use by Special Review Standards. Our comments and requirements are as follows: COMMENTS: WCR 51 is designed on the Weld County Transportation Plan Map as a collector status road, which requires an 80-foot right-of-way at full build out. There is presently a 60-foot right-of-way. This road is maintained by Weld County. Pursuant to the definition of set back in the Weld County Zoning Ordinance (Ordinance 89 as amended), the required set back is measured from the future right-of-way line. REQUIREMENTS: The Weld County Public Works Department recommends approval of this application. The applicant shall reserve an additional 10-foot right-of-way adjacent to WCR 51 for future build out. The applicant shall utilize the existing access from WCR 51, as no additional accesses will be granted. Off-street parking spaces including access drives shall be surfaced with gravel, asphalt, concrete or equivalent and shall be graded to prevent drainage problems. Storm Water Drainage: Both the existing and new buildings are located approximately four feet below WCR 51. There is an irrigation ditch between the buildings and WCR 51, and no drainage will affect the County road. The applicant indicated current building drainage will flow into the adjacent hay field and disburse. The Weld County Public Works Department has no conflict with the drainage item. Parking and Circulation: The turning radius into the proposed parking lot needs to be able to accommodate two-way traffic and shall be designed in full detail. ADA Parking (van availability) nearest to door and the ADA route to the building will need to be identified on the plat. Additional overflow parking shall be indicated on the plat to accommodate full build-out parking. pc: USR-1292 �lanl Ousr.wpd EXHIBIT [ 1 Hello