HomeMy WebLinkAbout20063599.tiff Weld Ceunty Planning Department GREELEY OFFICE MEMORANDUM RECEIVED O TO: Kim Ogle, Planning DATE: February 13, 2006 Peter Schei, Don Carroll, Public Works COLORADO Frank Piacentino, Building Inspection FROM: David Bauer, Public Works ..ax - SUBJECT: USR-1499, Windsor Assembly of God Church Weld County Public Works Depai Liuent has reviewed this revised drainage report for the Windsor Assembly of God Church. The Windsor Assembly of God Church 14 acre site is located on the northeast corner of the intersection of State Highway 292 and WCR 72, approximately 2 miles north of the Town of Windsor. The site is constrained by drainage ditches located along the northwest property line and the southeast property line. Proposed site improvements include a church building and parking lot, entry reatures and driveway access to WCR 72. This site has been approved for construction under a prior drainage plan; the applicant has submitted a new drainage plan to address newly identified conditions at the site. The letter submitted by the applicant's engineer (Nolte Associates, Inc. Gary Iwata, P.E.) states that the revised grading plan lowering the site by approximately 1 foot in elevation was necessitated to balance site soil volumes. The Nolte letter states that the original design engineer's (Latitude 39) detention pond outlet structure design erroneously releases the detained water at a rate higher than the 5-year storm historic rate as - required by Weld County Code. The Nolte letter states that all drainage improvements would be constructed as originally designed(by Latitude 39)with the exception of a lowering of site elevations by approximately 1 foot and with a change of the detention pond outlet structure to release at the required rate. Comments Drainage: ❑ Nolte's analysis and re-design of the revised detention outlet structure is an improvement over the previously submitted and accepted design. ❑ Nolte's re-grading design does not substantially change any of the approved proposed site improvements. ❑ The proposed detention pond outlet design and regarding design are acceptable to Weld County Public Works. ❑ Weld County will not maintain drainage facilities located on private property. ❑ The area that includes the detention pond and outlet structure shall be placed in a recorded drainage easement. ❑ Final sediment control and erosion control measures (confoiniing to the revised drainage report)stamped, signed and dated by a professional engineer licensed in the State of Colorado shall be installed prior to breaking ground. It is recommended that the detention pond be constructed first to collect site runoff and sediment during construction. ❑ Applicant is requested to re-submit 3 complete sets of stamped and signed revised drainage and grading design drawings for use by Public Works and Building Department inspectors and for the permanent project files. Recommendation ❑ Approval. i s 1addressc tep t o e row z m f 3r 4. % k45-73f � P ,a �ti ZZt Wg ply' vue fir" 1 oar e ems. ,u s C:USR-1499 file M:\PLANNING—DEVELOPMENT REVIEW\USR-Use by Special Review\USR-1499-WindsorAss.OfGod.doc 2C06-35M 35M PL I1-31 1`12 , .. , . do \\ 1 NOLTE -i--- -;s"rt TIF- -;- -e' \,' •• �ter', t __...„ 1 \\-\ f,� BEYOND ENGINEERING‘) 4 \ r-,11 �K��\Ae \ 5\\‘\ 2,0 V ? 10* ti co MEMORANDUM N -\\{ 0?)\-`c E►-d • Dave Bauer & Frank Piancentino DATE : February 10, 2006 Weld County FROM : Gary Iwata PROJ # : DVB0204 Nolte Associates, Inc. SUBJECT : Windsor Assembly of God Church Nolte Associates, Inc. was hired by Colorado Commercial Developers to revise the grading for the Windsor Assembly of God Church. The approved plans dated September 29, 2005 were designed by Latitude 39 of Denver, Colorado . Upon initial grading of the site, the contractor, Colorado Commercial Development, was short dirt when following the grading plan as proposed by Latitude 39 . Nolte Associates, Inc. was instructed to keep the design of the site the same but lower the building and parking lot so that there would not be a shortage of dirt. The building was lowered by 0. 6 feet while the parking lot was generally lowered by 1 . 0 foot. Lowering of these portions of the site required that the profile for the entrance to the church from Weld County Road #72 be altered and that the proposed detention pond be lowered. These changes can be seen on the following sheets which have been resubmitted to Weld County: Sheet 5 of 13 "Grading" Sheets 6 and 7 of 13 "Fine Grading" Sheet 10 of 13 "Water Plan" (The elevation of the proposed fire hydrant has been updated. ) Sheet 11 of 13 "Storm Sewer and Detention Pond" Sheet 12 of 13 "Storm Sewer and Detention Details" The volume of the proposed detention pond has remained the same as was designed by Latitude 39 . However, it is the opinion of Nolte Associates, Inc. that the release structure for the detention pond was incorrectly designed by Latitude 39 . As it was designed, the pond will not release the Water Quality Volume in 40 hours as recommended by Urban Drainage and Flood Control District. Additionally, the pond will drain much faster than the allowable 5 -year pre- development flow rate. Sheet 12 of 13 "Storm Sewer and Detention Details" shows the outlet structure as it has been re-designed. The orifice plate to drain the water quality volume of the pond now has more holes of a larger size. This has been designed using Figure 5 "WQCV Outlet Orifice Perforation Sizing" in UDFCD Criteria Manual Volume 3 . A 0 . 5 foot wide rectangular weir has been added to the release structure to allow the pond to drain at the allowable 5 -year pre-development release rate of 2 . 07 cfs. A steel orifice plate has been added to the entrance of n:\dvb0204\documents\memos\drainage_memo-windsor.doc MEMORANDUM (cont.) Page 2 the outlet pipe to restrict the flow out of the pond to the 5 -year pre-development release rate. This orifice plate was designed using Figure ST-6 "Hydraulic Properties of Pipe Flow" in UDFCD Criteria Manual Volume 1 . Please contact us with any questions regarding the resubmittal of these construction plans . Gary Iwata, PE Nolte Associates, Inc. 8000 South Chester Street, Suite 200 Centennial, CO 80112 Office 303 . 220. 6400 Fax 303 .220. 9001 I FEE 1 ao 3 2006 /+ WELD COUNTY PUBLIC WORKS DEPT n:\dvb0204\documents\memos\drainage_memo-windsor. doc RAINAGE CRITERIA MANUAL (V. 1) STREETS/INLETS/STORM SEWERS LO\I\ Sof ( 55n(1 6ki 4 oa chtveA-1 rb 0a Cup Values of f and n 11 n 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 1.0 1 i n,f Variable with Depth `k\\ 0.9 ----n,f Constant / \ 1 ---- Independent of n,f . / i 0.8 ---� t Darcy-Weisbach r i b 0.7 Friction Factor, f, f f/, rz 0.6 Discharge, 8 s Ill Hydraulic Radius, R 0.5 � Mannin4' '!;'_ . 0.4 �le00 � . ' —� Area, A 0.2 ' --.,At-t___41....._ .�� x .... x 0.1 0 11 0 , 0.1 0.2 0.t 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 o.I ,1 Hydraulic Elements �f Qf , A' , and R, FIGURE ST-6 Hydraulic Properties of Pipe Flow Forn Culix-(k i - 10" '( ai-- 1 170 , iA\)J= a833.c00, Tw.L-18 cs..yo[(o,l*p.)t imerkad=ye'..0.yo) &c: (, (au..s...) 1^ e.. - 424-4_ 4 Q , 9.0-4/c„ . 0. ,24 1J ,c cote dto= 0.4 O3V-eie `D= la„ (3= o 4CIa") d = 6" ° 1a"2cP Culvert Calculator Report 12" Pond Release Solve For:Discharge Culvert Summary Allowable HW Elevation 4,839.60 ft Headwater Depth/Height 3.30 Computed Headwater Elevation 4,839.60 ft Discharge 6.39 cfs N. Inlet Control HW Elev. 4,839.60 ft Tailwater Elevation 4,836.40 ft y Outlet Control HW Elev. 4,839.40 ft Control Type Inlet Control Grades Upstream Invert 4,836.30 ft Downstream Invert 4,836.00 ft Length 27.00 ft Constructed Slope 0.011111 ft/ft Hydraulic Profile Profile CompositeM2PressureProfile Depth,Downstream 0.96 ft Slope Type Mild Normal Depth N/A ft Flow Regime Subcritical Critical Depth 0.96 ft Velocity Downstream 8.23 ft/s Critical Slope 0.028158 ft/ft Section Section Shape Circular Mannings Coefficient 0.013 Section Material Concrete Span 1.00 ft Section Size 12 inch Rise 1.00 ft Number Sections 1 Outlet Control Properties Outlet Control HW Elev. 4,839.40 ft Upstream Velocity Head 1.03 ft Ke 0.50 Entrance Loss 0.51 ft Inlet Control Properties Inlet Control HW Elev. 4,839.60 ft Flow Control Submerged Inlet Type Square edge w/headwall Area Full 0.8 ft2 K 0.00980 HDS 5 Chart 1 M 2.00000 HDS 5 Scale 1 C 0.03980 Equation Form 1 Y 0.67000 n:\dvb0204\documents\drainage\outlet pipe.cvm Nolte Associates Inc CulvertMaster v3.1 [03.01.003.00] 02/08/06 10:56:03,eOvBentley Systems, Inc. Haestad Methods Solution Center Watertown,CT 06795 USA +1-203-755-1666 Page 1 of 1 1 , JOB NO.DVB0204 Windsor Assembly of God Church 2/7/2006 9:08 AM Water Quality Outlet Sizing(Dry Pond) Northwest Detention Pond WOCV: *Required Area Per Row(a): 3,217 ft3 0.4 in2 0.07 acre-ft Depth at Outlet: **Number/Size of Holes per Row: 1.30 ft 4 Rows of 1 Holes at ll/16"Dia. *From UDFCD Figure EDB-3"Water Quality Outlet Sizing-Dry Extended Basin w/a 40-Hour Drain Time of the Capture Volume" nomograph equation. Where a=WQCV/K40,K41=(0.013DWQ2)+(0.22DWQ)-0.10 **From"Fig.5 WCQV Oulet Orifice Perforation Sizing" NOLTE ASSOCIATES N::IDVB02041Documents\Drainage1 WQSizing.xls Orifice Plate Perforation Sizing Circular Perforation Sizing Chart may be applied to orifice plate or vertical pipe outlet. Hole Dia Hole Dia Min. Sc Area per Row (sq in) (in) * (in) (in) n=1 n=2 n=3 1/4 0.250 1 0.05 0.10 0.15 5/16 0.313 2 0.08 0.15 0.23 3/8 0.375 2 0.11 0.22 0.33 7/16 0.438 2 0.15 0.30 0.45 1/2 0.500 2 0.20 0.39 0.59 9/16 0.563 3 0.25 0.50 0.75 5/8 0.625 3 0.31 0.61 0.92 P. 11/16 r 0.688 3 0,37 j 0.74 1.11 4 3 0.750 3 0.44 0.88 1.33 13/16 0.813 3 0.52 1.04 1.56 7/8 0.875 3 0.60 1.20 1.80 15/16 0.938 3 0.69 1.38 2.07 1 1.000 4 0.79 1.57 2.36 1 1/16 1.063 4 0.89 1.77 2.66 1 1/8 1.125 4 0.99 1.99 2.98 1 3/16 1.188 4 1.11 2.22 3.32 1 1/4 1.250 4 1.23 2.45 3.68 1 5/16 1.313 4 1.35 2.71 4.06 1 3/8 1.375 4 1.48 2.97 4.45 1 7/16 1.438 4 1.62 3.25 4.87 1 1/2 1.500 4 1.77 3.53 5.30 1 9/16 1.563 4 1.92 3.83 5.75 1 5/8 1.625 4 2.07 4.15 6.22 1 11/16 1.688 4 2.24 4.47 6.71 1 3/4 1.750 4 2.41 4.81 7.22 1 13/16 1.813 4 2.58 5.16 7.74 1 7/8 1.875 4 2.76 5.52 8.28 1 15/16 1.938 4 2.95 5.90 8.84 2 2.000 4 3.14 6.28 9.42 n = Number of columns of perforations Minimum steel plate thickness 1/4 '' 5/16 3/8 '' * Designer may interpolate to the nearest 32nd inch to better match the required area, if desired. Rectangular Perforation Sizing Only one column of rectangular perforations allowed. Rectangular Min. Steel Hole Width Thickness Rectangular Height = 2 inches 5" 1/4 " Required Area per Row (sq in) 6" 1/4 " Rectangular Width. (inches) = 7" 5/32 " 2" 8" 5/16 " 9" 11/32 " 10" 3/8 „ >10" 1/2 " Urban Drainage and Figure 5 ' Flood Control District WQCV Outlet Orifice Drainage Criteria Manual (V.3) Perforation Sizing File: Details.dwg 'Design Procedure Form --Extended Detention Basin:(EDB) -Sedimentation Facility Sheet 1 of 3 Designer: DMH Company: Nolte Associates Date: February 7,2006 Project: Windsor Assembly of God Church Location: Windsor,Colorado-Weld County 1. Basin Storage Volume la= 24.00 % A)Tributary Area's Imperviousness Ratio(i=la/100) i= 0,24 B) Contributing Watershed Area(Area) Area= 6.33 acres C) Water Quality Capture Volume(WQCV) WQCV= 0.13 watershed inches (WQCV=1.0'(0.91'1'-1.19'1`+0.78"I)) D) Design Volume:Vol=(WQCV/12)*Area*1.2 Vol= "0.0830 `acre-feet 2. Outlet Works A) Outlet Type(Check One) X Orifice Plate Perforated Riser Pipe Other: B) Depth at Outlet Above Lowest Perforation(H) H= 1.30 feet C) Recommended Maximum Outlet Area per Row,(AO) A0= 0.3;: square inches D) Perforation Dimensions: i) Circular Perforation Diameter or D= '0,625"4:inches ii)2"Height Rectangular Perforation Width W= inches E) Number of Columns(nc,See Table 6a-1 For Maximum) nc= 1; number F) Actual Design Outlet Area per Row(A.3) A0= 0.3 square inches G) Number of Rows(nr) nr= 4,?:: number H) Total Outlet Area(Ao,) Ao,= 1.2 square inches 3. Trash Rack A) Needed Open Area:A,=0.5"(Figure 7 Value)'A", A,= 43 square inches B) Type of Outlet Opening(Check One) ` X ;,<2"Diameter Round 2"High Rectangular Other: C) For 2",or Smaller,Round Opening(Ref.: Figure 6a): i) Width of Trash Rack and Concrete Opening(Woo„0) from Table 6a-1 Woo== 3 !. a inches ii) Height of Trash Rack Screen(HTR) H TR= 46 inches USDCM Vol 3 BMP Design Forms v2.05(20050912).xls,EDB 2/7/2006, 12:45 PM Design.Procedure Farm Extended Detention Basin"(EDB) 5edgnentatton Factltty Sheet 2 of 3 Designer: DMH Company: Nolte Associates Date: February 7,2006 Project: Windsor Assembly of God Church Location: Windsor,Colorado-Weld County iii) Type of Screen(Based on Depth H),Describe if"Other" X S.S.#93 VEE Wire(US Filter) Other: iv) Screen Opening Slot Dimension,Describe if"Other" X :?''0.139"(US Filter) Other: v) Spacing of Support Rod(O.C.) 0;75'"e" inches Type and Size of Support Rod(Ref.:Table 6a-2) #156 VEE vi) Type and Size of Holding Frame(Ref.: Table 6a-2) 3/8 in.x 1.0 in.flat bar D) For 2"High Rectangular Opening(Refer to Figure 6b): I) Width of Rectangular Opening(W) W= :'':inches ii) Width of Perforated Plate Opening(W,,,,„c=W+12") W „c_ inches iii) Width of Trashrack Opening(Wopen1 g)from Table 6b-1 Wuoe„ne= inches iv) Height of Trash Rack Screen(HTR) HTR= , inches v) Type of Screen(based on depth H)(Describe if"Other") Klemp'M KPP Series Aluminum Other: vi) Cross-bar Spacing(Based on Table 6b-1,Klemp'M KPP 3{inches Grating). Describe if"Other" Other: vii) Minimum Bearing Bar Size(Klemp'M Series,Table 6b-2) (Based on depth of WQCV surcharge) 4. Detention Basin length to width ratio ( ) 5 Pre-sedimentation Forebay Basin-Enter design values A) Volume(no less than 5%of Design Volume from 1 D) acre-feet B) Surface Area acres C) Connector Pipe Diameter inches (Size to drain this volume in 5-minutes under inlet control) D) Paved/Hard Bottom and Sides yes/no USDCM Vol 3 BMP Design Forms v2.05(20050912).xls,EDB 2/7/2006, 12:45 PM „ Note: Vertical WQCV Trash Racks are shown in Figures 6, 6—a, and 6—b for suggested standardized outlet design. Adverse—Slope Trash Rack design may be used for non—standardized designs, but must meet minimum design criteria. Structural Steel Channel _ Stainless Steel Bolts Formed Into Concrete. WConc. or Intermittent Welds, See Figures 6—a, 6—b A See Figures 6—a, 6—b — —� *- 705-- _ c 3 3 3 O ° H 7 � - Varies 2'-0" o 3 O to 6'-0" ° O O ° 0 J ° - B • B D o 2'-4" (minimum) A- WQCV Trash Racks: Elevation 1. Well—screen trash racks shall be stainless steel and shall be attached by intermittant welds along the edge of the mounting frame. 2. Bar grate trash racks shall be aluminum and shall be bolted using stainless steel hardware. 3. Trash Rack widths are for specified trash rack material. Finer well—screen or mesh size than specified is acceptable, however, trash rack dimensions need to be adjusted for materials having a different open area/gross area ratio (R value) 4. Structural design of trash rack shall be based on full hydrostatic head with zero head downstream of the rack. Overflow Trash Racks: 1. All trash racks shall be mounted using stainless steel hardware and provided with hinged and lockable or boltable access panels. 2. Trash racks shall be stainless steel, aluminum, or steel. Steel trash racks shall be hot dip galvanized and may be hot powder painted after galvanizing. 3. Trash Racks shall be designed such that the diagonal dimension of each opening is smaller than the diameter of the outlet pipe. 4. Structural design of trash rack shall be based on full hydrostatic head with zero head downstream of the rack. Urban Drainage and Figure 6 Flood Control District Suggested WQCV Outlet Standardized Drainage Criteria Manual (V.3) Trash Rack Design Flle: Details.dwg JOB NUMBER DVB0204 Windsor Assembly of God Church 2/10/2006 7:53 AM DETENTION POND A - VOLUME PRISMOIDAL METHOD POND VOLUME=1/3(A1+A2+(A1*A2)^0.5)*D DETENTION POND INCREM CUMM. CUMM. ELEV AREA VOLUME VOLUME VOLUME SQ FT CU FT CU FT ACRE-FT 4836.50 0 0 0 0.00 4837.00 1,050 175 175 0.00 WQCV 4837.50 3,847 1,151 1,326 0.03 4837.80 6,366 1,516 2,842 0.07 4837.85 6,847 330 3,173 0.07 4838.00 9,461 1,218 4,390 0.10 4838.50 12,158 5,391 9,781 0.22 100 YR DET 4839.00 16,594 7,159 16,941 0.39 4839.50 17,787 8,593 25,534 0.59 4839.60 18,054 1,792 27,326 0.63 4840.00 18,731 17,652 34,592 0.79 100 YR F.B. 4840.60 19,629 11,507 46,099 1.06 N:IDVB0204IDocuments IDrainagelPond-Sizing.xls Weld County Planning Department C;4EELEy OFFICE 41;1JA A 0 5 2006 RECEIVED _ MEMORANDUM TO: Kim Ogle, Planning Services DATE: January 4, 2006 Wlig FROM: Donald Carroll, Engineering Administrator • jilt COLORADO SUBJECT: USR 1499, Windsor Assembly of God Church The applicant's engineer and contractor are requesting that the elevation of the site be lowered one foot to accommodate balancing dirt work quantities on site. REQUIREMENTS: The requirements are as follows: All existing elevations associated with the parking lot drainage, retention pond and release, and pipe elevations shall all be lowered one foot. The existing grade of WCR 72 should match the elevation then taper downward to the parking lot and church building. All other affected agencies such as Building Inspection and the Health Department should clear on this proposal. pc: Latitude 39 (fax 303-451-7567) Tracy Dyer, Inspection USR-1499 M:\PLANNING-DEVELOPMENT REVIEW\USR-Use by Special Review\USR-1499-C.doc Hello