• , Weld County Referral
111kJanuary 2, 2008
COLORADO
The Weld County Department of Planning Services has received the following item for review
Applicant Public Service Company Case Number USR-1647
of Colorado
Please Reply By February 2, 2008 Planner Hannah Hippely
Project A Site Specific Development Plan and a Special Review Permit for a Major Facility
of a Public Utility(electric power plant and associated gas pipeline) in the I-3
(Industrial) and A(Agricultural)Zone District.
Legal Parts of Section 3 and Section 10 of T3N, R67W of the 6th P.M . Weld County,
Colorado.
Location North of and adjacent to CR 34, and adjacent to the east and west of CR 19.5.
• Parcel Number 1209 10 000006, 1209 03 000008, and 1209 03 000021
The application is submitted to you for review and recommendation. Any comments or recommendation you
consider relevant to this request would be appreciated. Please reply by the above listed date so that we may
give full consideration to your recommendation. Any response not received before or on this date may be
deemed to be a positive response to the Department of Planning Services. If you have any further questions
regarding the application, please call the Planner associated with the request. Please note that new
information may be added to applications under review during the review process. If you desire to
examine or obtain this additional information, please call the Department of Planning Services.
Weld County Planning Commission Hearing (if applicable) February 19, 2008
❑ We have reviewed the request and find that it does/does not comply with our Comprehensive Plan
❑ We have reviewed the request and find no conflicts with our interests.
$ See attached letter.
❑ P/ease notify me of any public hearings regarding this request
Comments:
•
Signature /,C �!'�c Date Z� /O s>
• Agency ��27T�✓.���lr.�/`ts� En r
EXHIBIT
*Weld County Planning Dept 4.918 10th Street,Greeley.CO. 80631 +(9701 353-6100 ext.3540 +(970)304
2008-0729
Feb . 1 , 2';23 3 : ^?- i
• R\FVILLE .oQ
v � cRr
`,* o Platteville/Gilcrest Fire Protection District
•
February 1, 2008
Xcel Public Service Company
16805 WCR 19 '/2
Platteville, CO 80651
Re' USR-1647
To Whom It May Concern:
The following are the comments and concerns for the above stated USR. All
requirements have been taking from the 2003 IFC and the most current NFPA standards.
• I did not sec any proposed new fire hydrants either on the maps or in the
documentation. Fire lines will need to be extended from the existing system on
site to cover the new turbines. The spacing on the fire hydrants needs to he no
further than 300 feet apart,
• The new fire hydrants need to be protected. 1 have enclosed Section 312 of the
• 2003 IFC.
• Fire extinguishers will need to be supplied around the new turbines. Types, sizes,
and distances need to mirror the existing turbines on site.
• Is the fuel dispenser on the east side of the property going to be moved'? If not,
then,distances from new turbines to fuel dispenser need to be giving Might still
need to be moved if to close.
• New gas line needs to comply with NFPA 54 - Fuel Gas Code& NFPA 58 -LPG
Code.
• Electrical for the new gas line needs to comply with NFPA 70--National
Electrical Code, Articles 500& 501.
• Will NFPA 850 or 851 —Recommended Practices he used for the new turbines?
If there are any questions or concerns please contact at 970-785-2232 x 105,
Sincerely,Sincerely
Russell Kisslcr
Fire Prevention Tech.
•
303 Main Street,P.O. Box 407-Platteville,CO 80651 • 970-785-2232- Fax 970-785-0139
215 Main Street,P.O. Box 43• (Merest,Co 80623 • 970-737-2966• Fax 970-737-9006
k 9 h . ' . 2:PP 3 : A.2Pid .. , r
,�o L_: :
GENERAL PRECAUTIONS AGAINST FIRE
I
mable or combustible waste or rubbish and shall.securely lock 313.2 Group R occupancies.Vehicles powered by flammable
or otherwise secure doors,windows and other openings to pre-
ID liquids,Class JT combustible Liquids,aids,or compressed vent entry by unauthorized persons. The premises shall be qflammable
gases shall not be stored within the living space of Group R
maintained clear of waste or hazardous materials. buildings..
Exceptions:
1. Buildings or portions of buildings undergoing addi-
tions,alterations,repairs,or change of occupancy in SECTION 314
INDOOR DISPLAYS accordance with the International Building Code,
where waste is controlled and removed as required by 314.1 General. Indoor displays constructed 314.2throughwithin any occu-
Section 304.
panes shall comply with.Sections 314.2 314.4.
314.2 Fixtures and displays.Fixtures and displays of goods
2. Seasonally occupied buildings.
311.4 Removal of hazardous materials. Persons owning or for sale to the public shall be arranved so as to maintain free. '
dihaving charge or control of a vacant building containing haz- ' "ter 1 and unobstructed access to exits as required by
I ardous materials regulated by Chapter 27shall comply with the (naptcr10.
facility closure requirements of Section 2701,6. 314.3 Highly combustible goods.The display of highly com-
bustible goods,including but not limited to/reworks,flamma-
ble or combustible liquids, liquefied flammable gases,
SECTION 312 oxidizing materials,pyroxylin plastics and agricultural goods,
VEHICLE IMPACT PROTECTION in main exit access aisles,corridors,covered malls,or within 5
312.1 General. Vehicle impact protection required by this feet(1524 Si)of entrances to exits and exterior exit doors i.s
code shall be provided by posts that comply with Section 312.2 prohibited when a free involving such goods would rapidly pre-
vent by other approved physical barriers that comply with Sec- vent or obstruct egress.
[ion 312.3. 314.4 Vehicles.Liquid- or gas-fueled vehicles, boats or other
312.2 Posts.Guard posts shall comply with all of the following mowrerslt shall not be located indoors except as follows
requirements:
1 Batteries are disconnected.
1 Constructed of steel not less than 4 inches(102 trim)in 2. Fuel in fuel tanks does not exceed one-quarter tank or 5
diameter:and concrete filled.. gallons(19 L) (whichever is least).
2. Spaced not more than 4 feet(1219 mm)between posts on 3 Fuel tattles and fill openings are closed and scaled to pre-
center. vent tampering.
3. Set not less than 3 feet(914 nun)dcx;p in a concrete foot- 4. Vehicles,boats or other mntcrcr'afr equipment are not fu-
ing of not less than 15-inch(381 rum)diameter. elect or dc.fueled within the building
4.. Set with the top of the postsnot lcss'than 3 feet(914 men)
abovep:ound.
SECTION 315
5. Located not less than 3 feet(9I4 mm)from thepmteeted MISCELLANEOUS COMBUSTIBLE
object. MATERIALS STORAGE
312.3 Other barriers.Physical barriers shall be a minimum of 315.1 General. Storage, use and handling of•miscellaneous
36 inches(914 nun)in height and shall resist a force of 12,000 pounds(53 375 N)applied 36 inches(914 combustible materials shall be in accordance with this section
rum)above the adja- A permit shall be obtained i
cent ground surface n accordance with Section 105.6.
31.5.2 Storage in buildings.Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
SECTION 313 heaters or heating devices by distance or shiclding.so that igni-
FUELED EQUIPMENT tion cannot occur
313.1 Fueled equipment Fueled equipment,including but not 315.2.1 Ceiling clearance. Storage shall be maintained 2
limited to motorcycles,mopeds,lawn-care equipment and por-
table cooking equipment, shall not be stored, operated or re-
paired areas of buildings or a minimum of 1 S inches(457areas nun) ld-
pair'ed within a building.161
low sprinkler head deflectors in sprinkleruf of build-
ings.
ngs.
1 Buildings 315.2.2 Means of egress. Combustible materials shall not
or rooms constructed for such use in decor- he stored in exits or exit enclosures..
4 dance with the International Building Code..
2. Where allowed315.2.3 Equipment rooms.Combustible material shall not
by Section 313 or 314, be stored
313.1.1 Removal.The fire code official is authorized to re- equipmentm boiler rooms, mechanical crocus or electrical
rooms.
uire removal of fueled equipment fromlocations where the
315.2.4 Attic, under-Door and concealed spaces. Attic,
presence of such equipment is determined by the lire code
official to he bazar-does. under-floor and concealed spaces used for storage of com-
bustible materials shall he protected on the storage side as
30-
2003INTERNATIONAL ARE CODE®
rr .
Weld County Planning Department
GREELEY OFFICE
FF0 04 ?MR
• Memorand evEw
TO: Hannah Hi el , Department of Planning Services
I Hippely, P
' € DATE: January 29, 2008
COLORADO FROM: Lauren Light, Environmental Health Services
SUBJECT: USR-1647 Public Service Company of
Colorado (electric power plant and
associated gas pipeline)
Environmental Health Services has reviewed this proposal for a major facility of a public utility
(electric power plant and associated gas pipeline).
Water
Potable water is supplied by Central Weld Water District.
• Sewage
Sewage provisions are provided by two aerated lagoons, the discharge is permitted under
Colorado Wastewater Discharge Permit number— CO-0001121. Septic permit # SP-9600408
is utilized for the office building. This system was designed for up to 40 people and is
therefore adequate. There is also a vault system serving the laboratory building. It is
unknown if this vault is permitted.
The plant is currently permitted, through Weld County Department of Planning Services, via
USR-1063. This request will allow the continuing use of the plant and the installation of two
additional natural gas turbines and the associated gas pipeline.
We have no objections to the proposal, however, we do recommend that the following
conditions be part of any approval:
We recommend that the following requirements be met prior to allowing the plat to be
recorded:
1. The applicant shall amend the existing Emission Permit (APEN) for modification in the
operation if the Colorado Department of Public Health and Environment determines
that such a modification represents a significant change in emissions or production.
Alternately, the applicant can provide evidence from CDPH&E that a modification is not
required.
• 2. The applicant shall submit evidence of a Colorado Discharge Permit System (CDPS)
from the Water Quality Control Division of the Colorado Department of Health and
Environment for any proposed discharge into State Waterways. The CDPS that was
submitted with the application expired January 31, 2007. A copy of the draft permit is
acceptable.
3. The existing Colorado Discharge Permit System (CDPS) must be amended for the
increased operation if the Water Quality Control Division of the Colorado Department
of Public Health & Environment determines that such a modification represents a
significant change in the discharge. Alternately, the applicant can provide evidence
from CDPH&E that a modification is not required.
4. In the event that 1 or more acres are disturbed during the construction and
development of this site, the applicant shall obtain a stormwater discharge
permit from the Water Quality Control Division of the Colorado Department of
Public Health and Environment.
5. The applicant shall provide evidence that the facility has an adequate potable water
supply. (A letter from Central Weld Water District is sufficient).
6. All septic systems located on the property shall have appropriate permits from the Weld
County Department of Public Health & Environment. The applicant shall provide
evidence of septic permit for the vault system. If the existing septic system is not
currently permitted through the Weld County Department of Public Health &
Environment an I.S.D.S. Evaluation will be required prior to the issuance of the required
septic permit. The septic system shall be reviewed by a Colorado Registered
Professional Engineer. The review shall consist of observation of the system and a
technical review describing the systems ability to handle the proposed hydraulic load.
• The review shall be submitted to the Environmental Health Services Division of the Weld
County Department of Public Health and Environment. In the event the system is found
to be inadequate, the system must be brought into compliance with current I.S.D.S.
regulations.
We recommend that the following requirements be incorporated into the permit as a
condition that must be met one month prior to construction activities:
1. The applicant shall submit evidence of a Colorado Discharge Permit System or CDPS
permit from the Colorado Department of Public Health and Environment (CDPH&E),
Water Quality Control Division, to cover stormwater discharges from construction sites
(5 CCR-1002-61) Alternately, the applicant can provide evidence from CDPH&E that
they are not subject to the CDPS requirements. (New rule effective 3/2/2001).
We recommend that the following requirements be incorporated into the permit as
development standards:
1. All liquid and solid wastes (as defined in the Solid Wastes Disposal Sites and Facilities
Act, 30-20-100.5, C.R.S., as amended) shall be stored and removed for final disposal
in a manner that protects against surface and groundwater contamination.
2. No permanent disposal of wastes shall be permitted at this site. This is not meant to
• include those wastes specifically excluded from the definition of a solid waste in the
Solid Wastes Disposal Sites and Facilities Act, 30-20-100.5, C.R.S., as amended.
3. Waste materials shall be handled, stored, and disposed in a manner that controls
fugitive dust, blowing debris, and other potential nuisance conditions.
4. This facility shall adhere to the maximum permissible noise levels allowed in the
•
Industrial Zone as delineated in 25-12-103 C.R.S., as amended.
5. Any septic system located on the property must comply with all provisions of the Weld
County Code, pertaining to Individual Sewage Disposal Systems.
6. If applicable, the applicant shall obtain and maintain compliance with a stormwater
discharge permit from the Colorado Department of Public Health & Environment,
Water Quality Control Division.
7. Fugitive dust shall be controlled on this site.
8. Adequate hand washing and toilet facilities shall be provided for employees and
visitors.
9. A permanent, adequate water supply shall be provided for drinking and sanitary
purposes. (Central Weld Water District)
10.Portable toilets and bottled water for drinking and sanitary purposes may be utilized
during the construction of the project.
.
• Weld County Referral
January 2, 2008
111 D C.
l - 3 2008
COLORADO
The Weld County Department of Planning Services has received the following item for review:
Applicant Public Service Company Case Number USR-1647
of Colorado
Please Reply By February 2, 2008 Planner Hannah Hippely
Project A Site Specific Development Plan and a Special Review Permit for a Major Facility
of a Public Utility(electric power plant and associated gas pipeline) in the 1-3
(Industrial)and A(Agricultural)Zone District.
Legal Parts of Section 3 and Section 10 of T3N, R67W of the 6th P.M., Weld County,
Colorado.
Location North of and adjacent to CR 34, and adjacent to the east and west of CR 19.5.
• Parcel Number 1209 10 000006, 1209 03 000008, and 1209 03 000021
The application is submitted to you for review and recommendation. Any comments or recommendation you
consider relevant to this request would be appreciated. Please reply by the above listed date so that we may
give full consideration to your recommendation. Any response not received before or on this date may be
deemed to be a positive response to the Department of Planning Services. If you have any further questions
regarding the application, please call the Planner associated with the request. Please note that new
information may be added to applications under review during the review process. If you desire to
examine or obtain this additional information, please call the Department of Planning Services.
Weld County Planning Commission Hearing (if applicable) February 19, 2008
❑ We have reviewed the request and find that it does/does not comply with our Comprehensive Plan
❑ �We have reviewed the request and find no conflicts with our interests.
a' See attached letter.
Please notify me of any public hearings regarding this request.
Comments:
Signature �� Date � (17:-
Agency 6/1}/<(. j4%')) S
(•weld County Planning Dept. G918 10th Street, Greeley,CO.80631 ❖(970)353-6100 ext.3540 G(970)304-6498 fax
kiLFWeld County Planning Department
GREELEY OFFICE
MEMORANDUM °� a 'n�s
RECEIVED
ikTO: Hannah Hippely, Planning Department DATE: January 28, 2008
FROM: David Snyder, E.I., Public Works f�
COLORADO SUBJECT: USR-1647, Public Service Company of Colorado
The Weld County Public Works Department has reviewed this proposal. Our comments and requirements are
as follows:
COMMENTS:
Weld County Road Classification Plan (FHU): (June 2002)
WCR 19.5 is a collector road and requires an 80-foot right-of-way at full build out. There is presently a 60-foot
right-of-way. This road is maintained by Weld County. Pursuant to the definition of SETBACK in the Weld
County Zoning (23-1-90), the required setback is measured from the future right-of-way line.
REQUIREMENTS:
Direct access from a public road will be limited to one (1) per legal parcel, except as further limited or restricted
by zoning or subdivision regulations. Additional accesses may be approved by the Department of Public
orks or the Board of County Commissioners. This policy shall apply to all new and existing accesses within
e unincorporated areas of the County. Properties within municipalities or other counties which access
County roads are subject to this policy.
A 40' radius is required on all accesses to public roads for accesses designed to accommodate truck traffic. {A
minimum effective turning radius of forty (40) feet shall be used for accesses intended to accommodate truck
traffic. (Weld County Codification Ordinance 2000-1)} Sec. 8-2-40 B. Road access design standards.
The USR area IS NOT in a Special Flood Hazard Area (SFHA) as determined by the Federal Emergency
Management Agency (FEMA).
Please provide all drainage/stormwater calculations for the proposed pond. Please provide calculations
showing the existing stormwater system capacities are able to handle the additional loading from the proposed
turbines.
Applicant must get all required Weld County permits for working in Weld County Rights-of-Way, for any
temporary road closures, etc. pertaining to this project.
The applicant must take into consideration storm water quantity capture and provide accordingly for best
management practices.
pc: USR-1647
M:\PLANNING—DEVELOPMENT REVIEW\USR-Use By Special Review\USR-1647.DOC
•
• WELD COUNTY ROAD ACCESS INFORMATION SHEET
Weld County Department of Public Works
111 H Street, P.O. Box 758, Greeley, Colorado 80632
Phone: (970 )356-4000, Ext. 3750 Fax: (970) 304-6497
Road File #: Date:
RE # : Other Case #:
1. Applicant Name Public Service Company of Colorado Phone 303-571-6985
Address 550 15th Street, Suite 700 City Denver State CO Zip 80202
2. Address or Location of Access 16805 CR 19-1/2, Platteville, Colorado 80651
Section 10 Township 3N Range 67W Subdivision NA Block NA Lot NA
Weld County Road #: 19-1/2 Side of Road Fast Distance from nearest intersection
3. Is there an existing access(es)to the property? Yes X No #of Accesses 2
4. Proposed Use:
❑ Permanent ❑ Residential/Agricultural ❑ Industrial
❑ Temporary ❑ Subdivision ❑ Commercial ® Other Construction access
on existing service roads
5. Site Sketch
Legend for Access Description:
AG
= Agricultural
RES = Residential
O&G = Oil&Gas
• D.R. = Ditch Road
= House
CI = Shed A
A = Proposed Access
A = Existing Access
rn
Nr - GCD iAJSTCaJ<1
x
..... ........ .........
OFFICE USE ONLY:
Road ADT
Date Accidents Date
Road ADT Date Accidents Date
Drainage Requirement Culvert Size Length
Special Conditions
❑ Installation Authorized ❑ Information Insufficient
Reviewed By: Title:
CERTIFICATE OF CONVEYANCES WELD COUNTY
• STATE OF COLORADO DEPARTMENT OF PLANNING SERVICES
COUNTY OF WELD
-10-
•
Weld County Referral
WARt
January 2, 2008
COLORADO
The Weld County Department of Planning Services has received the following item for review:
Applicant Public Service Company Case Number USR-1647
of Colorado
Please Reply By February 2, 2008 Planner Hannah Hippely
Project A Site Specific Development Plan and a Special Review Permit for a Major Facility
of a Public Utility(electric power plant and associated gas pipeline) in the 1-3
(Industrial) and A (Agricultural)Zone District.
Legal Parts of Section 3 and Section 10 of T3N, R67W of the 6th P.M., Weld County,
Colorado.
Location North of and adjacent to CR 34, and adjacent to the east and west of CR 19.5.
• Parcel Number 1209 10 000006, 1209 03 000008, and 1209 03 000021
The application is submitted to you for review and recommendation. Any comments or recommendation you
consider relevant to this request would be appreciated. Please reply by the above listed date so that we may
give full consideration to your recommendation. Any response not received before or on this date may be
deemed to be a positive response to the Department of Planning Services. If you have any further questions
regarding the application, please call the Planner associated with the request. Please note that new
information may be added to applications under review during the review process. If you desire to
examine or obtain this additional information, please call the Department of Planning Services.
Weld County Planning Commission Hearing (if applicable) February 19, 2008
❑ We have reviewed the request and find that it does/does not comply with our Comprehensive Plan
❑ We have reviewed the request and find no conflicts with our interests.
_See attached letter.
O Please notify me of any public hearings regarding this request.
Comments:
Signature clAfri O Date G
• Agency udeej1 ` cfrvilearylcri
❖Weld County Planning Dept. ❖918 10th Street, Greeley, CO.80631 O(970)353-6100 ext.3540 O(970)304-6498 fax
DEPARTMENT OF PLANNINSERVICES
• teit
Kitiirez
BUILDING INSPECTION NORTH OFFICE
918 10th GREELEY, COLORADO 80631
PHONE (970) 353-6100, EXT.3540
FAX (970)304-6498
OUTH WEST OFFICE
4209 24.5 LONGMONT CO 80504
COLORADO PHONE (720)6524210 ext. 8730
FAX(720)-65-4210
January 17, 2008
Applicant: Public Service of Colorado
Site Specific Development Plan and Special Review Permit for a installation of Two Simple-Cycle
Gas Turbine Generator located in the 1-3 and A (Agricultural) Zoned District.
USR-1647
Description: Installation of 2 Gas Turbine Generators
There are 13 historical Building permits attached to the three parcels listed All have been finaled
1. A building permit shall be obtained prior to the construction of any structure.
0 2. A plan review is required for each building for which a building permit is required. Plans shall
include a floor plan. Plans for new structures shall bear the wet stamp of a Colorado registered
Architect or Engineer. Two complete sets of plans are required when applying for each permit.
Include a Code Analysis Data sheet provided by the Weld County Building Department with
each Building permits application. Building plans shall also be submitted to Platte/Gilchrest Fire
Protection District.
3. Buildings shall conform to the requirements of the various codes adopted at the time of
permit application. Currently the following has been adopted by Weld County: 2006
International Building Code; 2006 International Mechanical Code; 2006 International Plumbing
Code; 2006 International Fuel Gas Code; and the 2005 National Electrical Code and Chapter 29
of the Weld County Code.
4. Building height shall be measured in accordance with the 2006 International Building Code for the
purpose of determining the maximum building size and height for various uses and types of
construction and to determine compliance with 2006 International Building Code..
5. All building plans shall be submitted to the Platteville/Gilchrest Fire District for review and
approval prior to issue of Building Permits.
Please contact me for any further information regarding this project.
Sincer
a�arl �a
Piacentino
• Plans Examiner
Weld County Building Inspection Dept.
SIAlE OF COLORADO
0iFACE OF THE STATE ENGINEER Weld County Planning Department
vision of Water Resources oc•co<
epartment of Natural Resources GREELEY OFFICE ee ,,t
�r �$i
1313 Sherman Street, Room 818 JAN. 1 0 .CJ.. '
Denver, Colorado 80203 '/81_4
Phone 303-866-3581 RECEIVED
FAX 303-866-3589
Bill Ritter,
Jr.
http-.//www.water,state.co.us Governor
Harris D.Sherman
January 4, 2008 Executive Director
Hannah Hippely Dick Wolfe,P.E.
Weld County Planning Dept. State Engineer
918 101h Street
Greeley, CO 80631
Re: USR-1647 — Public Service Company of Colorado ("Applicant") — Site Specific
Development Plan and a Special Review Permit for a Major Facility of a Public Utility
Dear Ms. Hippely:
This referral does not appear to qualify as a "subdivision" as defined in Section 30-28-
101(10)(a), C.R.S. Therefore, pursuant to the State Engineer's March 4, 2005 memorandum to
county planning directors, this office will only perform a cursory review of the referral information and
provide comments. The comments do not address the adequacy of the water supply plan for this
project or the ability of the water supply plan to satisfy any County regulations or requirements. In
addition,the comments provided herein cannot be used to guarantee a viable water supply
• plan or infrastructure, the issuance of a well permit, or the physical availability of water.
According to the referral information the operation will be served by the Central Weld County
Water District("District") and Applicant's wells 11 and 12. The referral information also states that
Applicant's wells 3, 4, 9 and 10 may also be used. Our office has no comments regarding the
District's ability to serve the commercial operation.
The applicant currently has a court approved augmentation plan for well 10 (permit no. 14522-
RR) and well 11 (permit no. 14521-RR) and an approved substitute water supply plan for well 3
(permit no. 18904-TR), well 4 (permit no. 18904-UR), well 8 (permit no. 20480-SR) and well 9 (permit
no. 16860-RR). It appears based on the attached well permits that these are the wells that the
applicant will be using to serve the power plant. According to the records available in the State
Engineer's office it does not appear that the Applicant's well no. 12 (permit no. 2584-F based on the
applicant's court decree) is currently augmented. Therefore such well cannot be used until such time
as a court approved augmentation plan is approved.
Should you have any questions in this matter, please contact Joanna Williams of this office.
Sincerely,
Kevin G. Rein, P.E.
Chief of Water Supply
KGR/JMW
•
lein
• rstWeld County Referral
January 2, 2008
C.
COLORADO
The Weld County Department of Planning Services has received the following item for review:
Applicant Public Service Company Case Number USR-1647
of Colorado
Please Reply By February 2, 2008 Planner Hannah Hippely
Project A Site Specific Development Plan and a Special Review Permit for a Major Facility
of a Public Utility(electric power plant and associated gas pipeline) in the 1-3
(Industrial) and A(Agricultural)Zone District.
Legal Parts of Section 3 and Section 10 of T3N, R67W of the 6th P.M., Weld County,
Colorado.
Location North of and adjacent to CR 34, and adjacent to the east and west of CR 19.5.
• Parcel Number 1209 10 000006, 1209 03 000008, and 1209 03 000021
The application is submitted to you for review and recommendation. Any comments or recommendation you
consider relevant to this request would be appreciated. Please reply by the above listed date so that we may
give full consideration to your recommendation. Any response not received before or on this date may be
deemed to be a positive response to the Department of Planning Services. If you have any further questions
regarding the application, please call the Planner associated with the request. Please note that new
information may be added to applications under review during the review process. If you desire to
examine or obtain this additional information, please call the Department of Planning Services.
Weld County Planning Commission Hearing (if applicable) February 19, 2008
❑ We have reviewed the request and find that it does/does not comply with our Comprehensive Plan
❑ We have reviewed the request and find no conflicts with our interests.
See attached letter.
❑ Please notify me of any public hearings regarding this request.
Comments:
Signature Date 1,
• Agency p- , i-/sN
❖Weld County Planning Dept. ❖918 10th Street, Greeley,CO.80631 ❖(970)353-6100 ext.3540 +(970)304-6498 fax
• MEMORANDUM
TWIIDc DA: Hannah ATE: January 2,i 200e08, Planner
COLORADO
FROM: Kim Ogle, Planning Manager•
SUBJECT: Public Service of Colorado
John Lupo, Applicant's Representative
Landscape Referral - USR-1647
The Department of Planning Services reviewed the above referenced Use by Special Review
documentation and drawings and offers the following comments:
The Use by Special Review Plat shall be prepared in accordance with Section 23-2-260.D and
21-3-330 of the Weld County Code. In addition to these requirements, the plat scale shall be
1" = 20 feet, with the Vicinity Map delineated at a scale of 1" = 2000 feet. Further, it is
requested that a Legend of Symbols be employed to call out the specific equipment associated
with this facility. The text on the submitted plat is difficult to read given the font selected.
This application shall be in compliance with Section 23-3-350 and is address in the following
comments, as applicable.
Section 23-3-350 addresses the Design Standards applicable to this proposed facility.
Per Section 23-3-350.B, the applicant shall delineate all areas associated with outdoor storage.
These areas shall be screened from adjacent properties and public rights-of-way. The applicant
shall delineate an opaque visual screen on all sides of the property to mitigate the potential
negative impact and aesthetic concerns on surrounding properties, specifically during
construction of the two Peaker Generating Units.
Section 23-3-350.G addresses the Required Landscape areas. The USR Plat has not identified
areas for landscape treatment. Given the type of facility, Staff will not request a Landscape
Plan for this facility. Staff does request that all areas disturbed by construction activities
including pipeline placement be drilled with an appropriate seed mix to limit the potential on-site
erosionary processes. The seed mix, prepared by a professional/consultant seed company or
government agency shall be submitted for review and approval prior to recording the USR Plat.
Section 23-3-350.H addresses the issue of trash collection areas. Areas used for storage or
trash collection shall be screened from adjacent public rights-of-way and adjacent properties.
These areas shall be designed and used in a manner that will prevent wind or animal scattered
trash. This fence enclosure structure shall be delineated on the USR Plat.
Section 23-3-360 addresses Operation Standards. The applicant shall address the issue of
noise, air quality, water quality, radiation and radioactive material, heat light, and property
maintenance.
• Section 23-3-360.A addresses noise. The Department of Public Health and Environment will
regulate the maximum permissible noise levels allowed for this facility. Further, the application
materials state the existing facility operates twenty-four hours each day, seven days per week
each calendar year.
• Section 23-3-360.F addresses the issue of on-site lighting, including security lighting if
applicable, this section, states "any lighting ... shall be designed, located and operated in such a
manner as to meet the following standards: sources of light shall be shielded so that beams or
rays of light will not shine directly onto adjacent properties...." Staff shall require a Lighting Plan
be submitted for review and approval prior to recording the USR Plat.
Section 23-3-360.G addresses property maintenance. Should noxious weeds exist on the
property or become established as a result of the proposed development the applicant/
landowner shall be responsible for controlling the noxious weeds, pursuant to Chapter 15,
Articles I and II of the Weld County Code.
All other operation standards will be addressed by other referral agencies as warranted.
The applicant shall delineate all on-site signs. The signs shall adhere to Article IV, Division 2 of
the Weld County Code. Further, the location of the signs shall be delineated on the USR Plat.
All structures, including signs, on site must obtain the appropriate building permits.
The applicant shall enter into an Improvements Agreement according to policy regarding
collateral for improvements and post adequate collateral for all transportation and non-
transportation components as required. The Department of Public Works will address
additional requirements as warranted. Should the Improvements Agreement be required for this
facility, the agreement and form of collateral shall be reviewed by County Staff and accepted by
the Board of County Commissioners prior to recording the USR plat.
•
End Memorandum