RE: Design and Construction Plans Review for Crow Valley Cafe
Dear Mrs. Harding:
The water treatment facility Design and Construction Plans submitted by the Colorado Rural Water
Association by way of Randy Thielemier and received on 9-28-09 for the listed above facility was
recently reviewed by Mark Thomas of the Weld County Department of Public Health and Environment in
accordance to the Colorado Primary Drinking Water Regulations and regulations adopted pursuant to
Title 25-1.5-203 C.RS., and the retail food establishment regulations pursuant to article 1.2.2(48) of the
Colorado Primary Drinking Water Regulations, stating that a retail food establishment shall provide
adequate treatment on a continuous basis and bacteriological samples analyzed at a minimum of once per
quarter and Nitrate analyzed annually or at a frequency determined by the Department.
The design of the system as submitted is hereby "approved" and is subject to approval according to the
following conditions:
1. The system as designed is for a minimum of 0.5mg/L residual chlorine and is to be maintained as
such. Realizing that residual chlorine below 0.5mg/L is inadequate. Therefore, approval is
subject to maintaining a residual chlorine as the system is designed, at or above 0.5mg/L
If you have any questions or need additional information, please call me at 970-304-6415. At this time I
want to thank you for your time and cooperation during the inspection.
Sincerely,
o
Digitally signed by
Mark Thomas
Date; 2009.10.02
1O03:54 -0600'
Mark Thomas
Chemist
Weld County Department of Public Health and Environment
cc: file copy
cc: Randy Thilemier
M:IENVIRONMENTAL HEALTH SERVICESV-AB\NON COMMUNITY GROUND WATER\2009 NCGW Inspections\Crow "alloy
Caretdesigi approval letter.docx
Dec 03 12 03:03p RUTH HARDING 303 940 4922
303 940 4922
p3
ets
• 6; Colorado Analytical
�LaDoro:C: ;2E. In:.
Report To: Ruth Harding
Company: Crow Valley Cafe, Inc.
5435 Field Ct.
Arvada CO 80002
Analytical Results
TASK NO: 120227042
Bill To: Ruth Harding
Company: Crow Valley Cafe, Inc.
5435 Field Ct.
Arvada CO 80002
L
Task No.: 120227042
Client PO: Paid Check 8199
Client Project: Crow Valley Caf�
Date Received: 2/27112
Date Reported: 2/29/12
Matrix: Water - Drinking
i
Lab Number [Customer Sample ID
120227042-01 Crow Valley Cale
Sample Date/Time 1 Test I
2/27/12 2:40 PM Total Goliform
E-Coli
Result
Absent
Absent
Method ! Date Analyzed
SM 9223
SM 9223
2128/12
2/28/12
�2 t�i pit C ?2,E { l/IGtic-�bc
cii-
iM zc lc� E� L-ksCz011
.mot- /ciao.
Abbreviations/ References:
Absent = Coafomr NW Detected
Present a Cokbnn Detected . Chlorinabon Recommended
Date Analyzed = Date Test Completed
SM +'Standard Methods for the Examination of Water and Wastewater" APHA; 19th Edition; 1995
DATA APPROVED FOR RELEASE BY
i
Page 1 oil
240 South Main Street / Brighton, CO 80601-0507 / 303-659-2313
Mailing Address: P.O. Box 507 / Brighton, CO 80601-0507 / Fax: 303-659-2315
120221042
Nov 13 12 03:41p Diane Johnson
970-356-6110 p.1
Form No
G WS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
610 Conternial BMg., 1313 Sherman St.. Denver, Colorado 90203
1303) 065-3561
RANDOLPH J. CASS
43251 HWY 392
BRIGGSDALE, CO 80611-
(970) 656-3559
REGISTRATION OF EXISTING WELL
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as Ie cause no material Injury to existing water rights. The issuance of this permit
does nol ensure that no injury will occur to another vested water right or preclude another owner of a vested wafer right from
aeeking relief In a civil court action.
2) Construction details for this exlsiing well have not been provided to IhIs orllco; therefore, it Is not Known If the eonstrudion
of this well is in compliance with the Water Wall Construction Rules, 2 CCR 402-2, The issuanco of this permit does not
relieve the wee owner of responsibility or liability In the event contem,nadon of the groundwater source results from the
construction or use of this well, nor dons the State Engineer assume any responsibility or habllhy should contamination
occur.
3) Recorded pursuant to CRS 37.92.602(5), and the policy of the State Engineer, for historical use as indicated herein. This
wee produces 15 GPM, and is used for ordinary household purposes inside one single family dwelling and for drinking and
sanitary facilities es described in CRS 37.92.G02(1)(c), in an individual commercial business. This business Is described
as a caf�. Water from this well shall not be used for any uses outside the dwelling or business building structure(s),
Including lawn or landscape irrigation, or animal watering.
4) Approved as the only well providing water to this business, which is on a 4.00 acre parcel. described as tot A recorded
exemption RECX12-0079, Weld County. reference attached exhibit A.
5) The average annual amount of ground water to be appropriated shall not exceed one (1) acre -fool (325,050 galons).
6) Tne date of first beneficial use, as claimed by the applicant, Is the 1950's,
7) The return flow from the use of this well must be through an individual waste water disposal system or the
non -evaporative type where the water is returned to the same stream system In which the well is located.
8) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records of all
diversions must be maintained by the welt owner (recorded et least annually) and submitted to the Division Engineer upon
request.
9) Approved for the use of en existing wall constructed under permit no 164248-A. The Issuance of this permit hereby
cancels permit no. 164248.A.
NOTICE: This permit has been approved for indoor use only. You are hereby notified that you have the right to appeal the
Issuance of this permit, by filing a written request with this office within sixty (60) days of the date of issuance, pursuant to
the State Administrative Procedures Act. (See Section 24.4.104 through 106, C.R.S.)
}
LR
WELL PERMIT NUMBER 289676
DIV. 1 WD1 DES. BASIN MD
APPROVED WELL LOCATION
WELD COUNTY
SE 1/4 SE 114 Section 20
Township 8 N Range 62 W Sixth P.M.
DISTANCES FROM SECTION LINES
150 Ft. from South Section Line
150 Ft. from East Section Line
UTM COORDINATES (Meters,Zone:13,NAD831
Easting: Northing:
APPROVED
SRS
Receipt No 3657438A
Suite Eng
DATE ISSUED 10.30.2012 XPIRATION DATE NA
Weld County Environmental Health Services Department
1555 N. 17th Avenue
Greeley, CO 80631
Phone: (970) 304-6415
Fax: (970) 304-6411
RECEIPT
November 06, 2012
Application Number: SP -1200243
App Type: Health\ Commercial\Repair\Septic
Owner Name: CASS RANDOLPH J & JUDY C
43251 HIGHWAY 392
BRIGGSDALE, CO 80611
Site Address: 37967 HWY 14
WELD, CO 80611
Rcpt M Pmt Type Pmt Method B!!! Pmt Date Amount Cashier
EHS-1200345 Paid Check 7244 11/06/2012 $850.00 MSWAIN
Total Payments: $650.00
Comments
Report ID: EHS00054v002 Page 1 oft
Print Date Time: 11/6/2012 4:08:06PM
Weld County Environmental Health Services Department
1555 N. 17th Avenue
Greeley, CO 80631
Phone: (970) 304-6415
Fax: (970) 304-6411
Web: wwxwco.weldheaRRorg
Septic Permit Application
Application Number SP -1200243
App Type: Health \ Commercial \RepairlSeptic
MARK TAYLOR
ALLES TAYLOR & DUKE LLC
3610 35TH AVE UNIT #6
EVANS, CO 80620
Owner Name: CASS RANDOLPH J & JUDY C
Parcel 054520000007-R0567086
Legal Desc: 6282 S2SE4 20 8 62 (3R)
Site Address: 37967 HWY 14
WELD, CO 80611
App Specific Info:
1/2 Bathrooms 1
3/4 Bathrooms 0
Basement Plumbing No
Full Bathrooms 0
Location Description 37967 HWY 14, BRIGGSDALE
Number of Bedrooms 0
Parcel Acres 3.57
Private Water Supply Well
Public Water Supply No
TERMS AND CONDITIONS
A permit fee, as set by separate ordiance of the Board of Weld County Commissioners, shall be required of applicants for new individual
sewage disposal systems (1505), payable at time of application, Permit fees are non-refundable; permit applications are
non -transferable. If both a building permit and an ISDS are issued for the same property end construction is not commenced prior to the
expiration date of the building permit, the ISDS permit shall expire at the same lime as the building permit. If an ISDS permit is issued for a
property that does not require a building permit, the ISDS permit shall expire one year after its issuance it construction an the septic system
has not commenced. Any change in plans or specifications after the permit has been issued invalidates the permit unless approval is
secured Iron the Health Officer or hlsrher designated agent. Expired permits can be renewed by payment of the permit fee only if:
A There has been no change to the plans end specifications of the proposed system as set out in the original application or such
change is reviewed end approved by a Division Representative.
B The surrounding land, its use or zoning has not changed so -as -to cause the original application not to be acceptable under these
regulations.
NOTICE
The completeness of this application is conditional upon further mandatory and additional tests and reports as may be required by the Weld
County Department of Public Heafh and Environment (WCOPHE). The issuance of the permit is subject to such terms and conditions as
deemed necessary to insure compliance wilh rules and regulations adopted under article 10 title 25. CRS as amended. The applicant certfies
that the proposed system will not be located within 400 feel of a community sewage system The undersigned certifies that all statements
made, information and reports submitted herewith are, or will be, represented to be true and correct to the best of his/her knowledge and are
designed to be relied on by the WCDPHE for evaluation for purposes of issuing the permit applied for herein. Applicant further understands
that falsification or misrepresentation may result in the denial of the application or revocation of any permit granted, and in legal action or
perjury as provided � w. �)
z���+�.
Owner/Applicant / Date
Report la EHS00056v003
Print Date Time: 11/6/2012 4.05:18PM
Page 1 of 1
RECEIPT
November 06, 2012
Application Number: SP -1200242
App Type: HealtMResidential\Repair\Septic
Owner Name: CASS RANDOLPH J & JUDY C
43251 HIGHWAY 392
BRIGGSDALE, CO 80611
Site Address: 37967 HWY 14
WELD, CO 80611
Weld County Environmental Health Services Department
1555 N. 17th Avenue
Greeley, CO 80631
Phone: (970) 304-6415
Fax: (970) 304-6411
Jtcut # Pmt Type Pmt Method Ref /I Pmt Date mount Cashier
EHS-1200344 Paid Check 7244 11/06/2012 $750.00 SCERRILLO
Total Payments: $750.00
Comments
Report ID: EHS00054v002 Page 1 oft
Print Date Time- 11/6/2012 4-03.02PM
Weld County Environmental Health Services Department
1555 N. 17th Avenue
Greeley, CO 80631
Phone: (970) 304-6415
Fax: (970) 304-6411
Web: www.co.weldhealth.org
Septic Permit Application
Application Number: SP -1200242
App Type: Health\Residential\Repair\Septic
MARK TAYLOR
ALLES TAYLOR & DUKE LLC
3610 35TH AVE UNIT #6
EVANS. CO 60620
Owner Name: CASS RANDOLPH J & JUDY C
Parcel#: 054520000007-R0567086
Legal Desc: 6282 S25E4 20 8 62 (3R)
Site Address: 37967 HWY 14
WELD, CO 80611
App Specific Info:
1/2 Bathrooms 0
3/4 Bathrooms 0
Basement Plumbing No
Full Bathrooms 1
Location Description 37967 HWY 14
BRIGGSDALE CO
Number of Bedrooms 3
Parcel Acres 3.57
Private Water Supply Well
Public Water Supply No
TERMS AND CONDITIONS
A permit fee, as set by separate ordiance of the Board of Weld County Commissioners, shall be required of applicants for new individual
sewage disposal systems (ISDS), payable at time of application Permit fees are nomrefundsble; permit applications are
nontransferable If both a building permit and an ISDS are issued for the same properly and construction is not commenced prior to Me
expiration date of the building permit, the ISDS permit shall expire al the same time as the building permit If an IS05 permit is issued for e
property that does not require a building permit, the ISDS permit shall expire one year after its issuance if construction on the septic system
has not commenced Any change in plans or specifications after the permit has been issued invalidates the permit unless approval Is
secured from the Health Officer or his/her designated agent. Expired permits can be renewed by payment of the permit fee only it:
A. There has been no change in the plans and specifications of the proposed system as set out in the original application or such
change is reviewed and approved by a Division Representative.
B The surrounding land, its use or zoning hes not changed so -as -to cause the onginal application not to be acceptable under these
regulations
NOTICE
The completeness of this application is conditional upon further mandatory and additional tests and reports as may be required by the Weld
County Department of Public Health and Environment (WCDPHE). The issuance of the permit is subject to such terms and conditions as
deemed necessary to insure compliance with rules and regulations adopted under article 10 title 25, CRS as amended. The applicant ceMies
that the proposed system will not be located within 400 feet of a community sewage system. The undersigned certifies that WI statements
made, information and reports submitted herewith are, or will be, represented to be true and correct to the best of his/her knowledge and are
designed to be relied on by the WCDPHE for evaluation for purposes of issuing the permit applied for herein. Applicant further understands
that falsification or misrepresentation may result in the denial of the application or revocation of any permit granted, and in legal action or
perjury as provided by law.
X Lt;.
Owner/Applicant Q Date
Report ID: EHS00056v003
Print Date Time 11/6/2012 4'03.45PM
Page 1 of 1
f /d (j
SEPTIC PERMIT INFORMATION FORM
To obtain an I.S.D.S. permit, one must file an "application for individual Sewage Disposal System"
at the Weld County Environmental Health Services office and pay the application fee. A "repair" fee
shall be charged for the expansion, replacement, or repair of an existing system_ The following
information must be provided on the septic information form.
COMMERCIAL PERMIT_ V RESIDENTIAL PERMIT__
NEW or REPAIR $850.00 NEW or REPAIR $750.00
VAULT PERMIT MINOR REPAIR PERMIT
NEW or REPAIR $250.00 $100.00
PARCEL NO.: 0 SVS2 0000001 _ (12 DIGIT NUMBER)
LEGAL DESCRIPTION: SECTION cRO TOWNSHIP 8 RANGE 4t _ ACRES 3,57±
SUBDIVISION
LOT BLOCK FILING
THIS INFORMATION CAN BE OBTAINED FROM THE ASSESSOR'S OFFICE AT (970) 353-3845 EXT 3650
SITE ADDRESS .3'7t '7 .✓ y /Y ,. $C • fl.s4(a�e, CO B04,!/.
DIRECTIONS TO SITE 75016,E of Tnierltc Len er >L i>/ y /j'l Mor3YZ
'VS L lo/cct/ion Nw Cernsir of -CA<es, a.
R4r-nio./ 17 ✓., i' 4t4,(_y &, t s s
MAILING ADDRESS: '!/j ZS/ _ </,,.�/ .J1JZ CITY ery /i ST Co ZIP ROIP /`
HOME PHONE: (PO) ..59,-.6.40 a WORK PHONE (970) 3'/ -SGoZ FAX ( _)
EMAIL ADDRESS:_
APPLICANT NAME:_
MAILING ADDRESS _ _ _ CITY ST ZE('
HOME PHONE: ( 1 WORK PHONE ( ) _ _ FAX ( . )_
EMAIL ADDRESS. _
DESCRIPTION OF BUILDING (EX: HOUSE, MOBILE HOME, MODULAR, SHOP, OFFICE) Ram, / 54re_
PROPERTY OWNER
IF OBTAINTNG A REPAIR PERMIT, WHAT IS BEING REPAIRED? _
NUMREF OF PERSONS
'�LMBP:R OP BEDROOMS
PASEMENTEl.WRING YESte
EATIROOMS. FULI.
PUP__ IC WAIE2 SUPPLY YE, !CI NAME -- _-
PRT,,A'E I),'ATER.SUPPLI' 9 /HO FR.I1CI::I r]'rl
IN FLOOD PLAIN AREA? _YES /N0 i✓o `u_M5Aeri
f'/ootp/t.n Map
PERCOLATION HOLES MUST BE MARKED FOR
INSPECTION OR A $50.00 FEE WILL BE CHARGED
CENSUS TRACT
P-:RMIT # c?89676,
PLEASE DRAW A MAP TO YOUR PROPERTY.
f59 tocfr" CT" (tut/fir
CAA. �1123 l�o.s{
Hwy /
AXLES TAYLOR & DUKE, LLC 3610 35TH AVE. UNIT #6
LICENSED PROFESSIONAL ENGINEERS EVANS, 80634
LICENSED PROFESSIONAL LAND SURVEYORS 970-330-0308
October 25, 2012
Mr. Trevor Jiricek
Weld County Department of Public Health & Environment
1555 North 17th Avenue
Greeley, Colorado 80631
RE: Septic Design - Randolph & Judy Cass
37967 HWY 14
Briggsdale, CO 80611
Lot "A", RECX 12-0079
Pt S '''A, SE Y , Sec 20, TSN, R62W, 6th P.M.
Retail Space (Liquor Store)
Dear Sir:
The following commercial septic design for Randolph & Judy Cass is submitted for your
review and approval.
1. I preformed a percolation test for the site on October 22, 2012 and the percolation
rate obtained was 28.80 Min./in., use 30 min./in for design, see attached
computations. The soil profile is as follows: 0" - 10" Top Soil, 10" - 26" Loam, 26"-
41" Sandy Loam with a trace of Clay, 41" - 82" Sandy Loam, light tan in color, 82" -
96" Clay, dark brown. 82" to 96" is considered as a limiting layer. No groundwater
was observed in the 8' soil profile pit.
2. From table Appendix 30-A, 0.1 gallons per SF of retail space, (Liquor Store,
assumed 800 SF) 800 * 0.1 = 80 gallons, 2 employees, 15 gallons per 8 hour shift,
(assumes 2, 8 hour shifts) 2* 15 = 30 gallons. The total waste water load (Q„"g,) is 80
gallons + 30 gallons = 110 gallons per day. Qmaz= Q„„g. * 1.5 = 110 gallons * 1.5 =
165 gallons per day.
3. The existing septic tank is in poor condition.
The required septic tank size = Qmac * (30/24) = 165 gallon * 1.25 = 206.25 gallons.
Per Weld County Code, the minimum septic tank size is 1000 gallons. A new 1000
gallon septic tank is required.
4. An absorption trench system has been selected. The absorption area is determined
using the equation Atrench ch = (Qm„x*t05)/3.5 = (206.25*30°5)/3.5 = 322.765 SF. A
Quick 4 Infiltrator system is to be used, the reduction factor is 0.5. 322.765 SF *
0.5 = 161.38 SF. The number of Quick 4 Infiltrators required = 161.38 SF/ (9.2
SF/Unit) = 17.54 Units. Use 18 Quick 4 Infiltrator units in a single trench
configuration. A distribution box will be required as a change of use; (back to a
restaurant) would require an absorption trench expansion and multiple trenches
being added to the absorption system. Due to the limiting layer of Clay located at
6.8', the maximum depth of cover over the Quick 4 Infiltrators is 1.8' as measured
from the crown of the Quick 4 Infiltrator (Standard).
2012-115 Commercial
Nc! 0
, ALLES TAYLOR & DUKE, LLC 3610 35TH AVE. UNIT #6
LICENSED PROFESSIONAL ENGINEERS EVANS, 80634
C LICENSED PROFESSIONAL LAND SURVEYORS 970-330-0308
5. The absorption field and septic tank shall be constructed and installed in
accordance with Weld County Health Department regulations.
6. The absorption bed/trench shall be place a minimum of 100 feet from any existing
water well.
7. No traffic shall be permitted on the new absorption field after construction.
If you have any questions, please contact me.
Respectfully submitted,
Mark Taylor
Colorado P.E. 46065
2012-115 Commercial
i
l
SEPTIC DESIGN
RANDOLPH & JUDY CASS, 37967 HWY 14, BRIGGSDALE, CO 80611
A 1000 GALLON SEPTIC TANK IS REQUIRED, TABLE 30-2. THE EXISTING 1000 GALLON SEPTIC TANK IS NOT ADEQUATE. A
NEW 1000 GALLON SEPTIC TANK WILL BE REQUIRED.
1= 30 MIN/IN, Q = 165 GALLONS. AREA (TRENCH) =(Q * P0.5)/3.5 = (165*30^0.5)/.1.5 = 322.765 SF. QUICK 4 INFILTRATORS
REDUCTION FACTOR = 0.5, 322.765 SF * 0.5 = 161.38 SF. 161.38)9.2 = 1734 UNITS, , USE MININMUM OFI8INFILTRATOR UNITS.
THE PROPOSED ABSORPTION TRENCH SYSTEM SHALL BE CONFIGURED TO FIT THE EXISTING SITE CONDITIONS. THE
ABSORPTION TRENCH CONFIGURATION SHALL BE ONE ROW OF 18 UNITS.
SEPTIC FIELD MUST BE A MINIMUM OF 20 FEET FROM ANY OCCUPIED BUILDING, 10 FEET FROM PROPERTY
LINES, 100 FEET FROM ANY WATER WELLS AND 100 FEET FROM ANY IRRIGATION PONDS.
DRAINAGE SHALL BE SLOPED AWAY FROM ABSORPTION TRENCH SYSTEM.
503
EXISTING 100+
SEPTIC TANK
TO BE
ABANDON
L
EXISTING
ABSOR.
TRENCH
TO BE
ABAND.
ABSORPTION TRENCH
5,
5'M IN:
5'M1N.
EXISTING
PROFILE COMM.
HOLE & TRUCTURE
PROPOSED
1000 GALLON
SEPTIC TANK
4
• 6 DIST NTS
IBOX
PROVIDE
��ROOM FOR
ADDITIONAL
SEPTIC TANK
(FUTURE EXPANSION)
WATER WELL
HWY 14 (ROW 100') PAVED
Typical TRENCH SYSTEM CONFIGURATION
6' min. -
UNDISTURBED SOIL
ABSORPTION TRENCH
6' min. —
UNDISTURBED SOIL
ABSORPTION TRENCH
PERC TEST
MIN/IN
1 0-1/4"
2 0-1/2"
3 0.11/16"
4 0-11/16"
5 0-3/16"
6 0-13/16"
AVE = 28.800 MIN
IN
USE 30 MIN/IN
FOR DESIGN
' -1--- MAX
1.0' MINIMUM
COVER
\\ //^\\
i 1 1
I5 1.5' 6' MIN.
I I- ----1
X- SECTION - NTS
EXISTING GROUND
q
LIMITING
NO GROUND LAYER
WATER AT 8'
2012-115 COMM.
Nov C2 12 10:27a Diane Johnson
970-356-6110 p.1
Form No
GWS-25
APPLI CANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
ere Centennial Bldg. 1313 Sherman St., Denver, Colersae 80203
taco) 866-3501
RANDOLPH J. CASS
43251 HWY 392
BRIGGSDALE, CO 80611-
(970) 656-3559
REGISTRATION OF EXISTING WELL
r
LR
WELL PERMIT NUMBER 289676
DIV. 1 WO 1 DES. BASIN MO
APPROVED WELL LOCATION
WELD COUNTY
SE 1/4 SE 1/4 Section 20
Township 8 N Range 62 W Sixth P.M.
DISTANCES FROM SECTION LINES
150 Ft. from South Section Line
150 Ft. from East Section Line
UTM COORDINATES (Meters,Zone: t 3,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This vial shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not ensure that no injury will occur to another vested water right or preclude another ownor of o seated water right from
seeking relief in a civil court action.
2) Construction details for this existing well have not been provided to this office; therefore, it is not known It the construction
of this well is in compliance with the Water Well Construction Rules. 2 CCR 402-2. The issuance of this permit does not
relieve the well owner of responsibility or liability in the event contaminadon of the groundwater source results from the
cons huc1ion or use of this well, nor does the State Engineer assume any responsibility or liability should contamination
occur.
3) Recorded pursuant to CRS 37-92.602(5), and the policy of the Slate Engineer. for historical use es Indicated herein. This
well produces 15 GPM, and is used for ordinary household purposes Inside one single family dwelling and for drinking and
sanitary facilities es described in CRS 37.92.602(1)(c), in an individual commercial business. This business is described
as a cafe. Water from this well shall not be usod for any uses outside the dwelling or business building structure(s),
including lawn or landscape irrigation, or animal watering.
4) Approved as the only well providing water to this business, which is on a 4.00 acre parcel, described as lot A, recorded
exemption RECX124079, Weld County, reference attached exhibit A.
5) The average annual amount of ground water to be appropriated shall not exceed one (1) acre-foot (325,850 gallons).
6) The date of first beneficial use, as claimed by the applicant, is the 1950's.
7) The return flow from the use of this well must be through an individual waste water disposal system of the
non -evaporative type where the water is returned to the same stream system in which the well is located.
8) A totalizing Bow meter must be installed on Ns well and maintained In good working order. Permanent records of all
diversions must be maintained by the well owner (recorded at least annually) and submitted to the Division Engineer upon
request_
9) Approved for the use of en existing well constructed under permit no. 104240-A. The issuance of this permit hereby
cancels permit no. 104248-A.
NOTICE: This permit has been approved for Indoor use only, you are hereby notified that you have the right to appeal the
issuance of this permit, by filing a written request with this office within sixty (60) days of the date of issuance, pursuant to
the State Administrative Procedures Act. (See Section 24-4404 through 106, C R.S.)
APPROVED
SRB
‘Receipt No.3657438A
Slate frightcEt�
DATE ISSUED 10.30.2012 EXPIRATION DATE AA
WLORADO
an ORA DO
SEPTIC PERMIT INFORMATION FORM 1
To obtain an I.S.D.S. permit, one must file an "application for Individual Sewage Disposal System"
at the Weld County Environmental Health Services office and pay the application fee. A "repair" fee
shall be charged for the expansion, replacement, er repair of an existing system. The following
information must be provided on the septic information form.
COMMERCIAL PERMIT
NEW or REPAIR $850.00
VAULT PERMIT
NEW or REPAIR $250.00
RESIDENTIAL PERMIT V_
NEW or REPAIR $750.00
MINOR REPAIR PERMIT
$100.00
PARCEL NO.: 05t,/- 2 OOO00O7 _ (12 DIGIT NUMBER)
LEGAL DESCRIPTION: SECTION 20 TOWNSHIP 8 RANGE to Z ACRES ,3,574
SUBDIVISION
LOT BLOCK FILING
THIS INFORMATION CAN BE OBTAINED FROM THE ASSESSOR'S OFFICE AT (970) 353-3845 EXT 3650
SITE ADDRESS _3 7 9491 F7//�' 15 y 8s-? �ysdale. Co 8064
DIRECTIONS TO SITE' 750'Llad OIL Ina≤ -/ ,4'&y./f t# ' 3y2 an
'72I Loea./:ern ft -O? use_ ora- stile e/' <<nee.,
�y /V
PROPERTY OWNER: /3nc{o// j. JAY C. La 55 _
MAILING ADDRESS: _.13 ZS/ }!w�/ .3f2 _ CITY ,t5/11p,stak ST_CO ZIP BO4e Z/
HOME PHONE: (9;GJ 381-54'67 WORK PHONE (770 ) 38/ -Soot. FAX ( )_
EMAIL ADDRESS:
APPLICANT NAME:
MAILING ADDRESS: CITY
HOME PHONE: ( ) WORK PHONE ( j_
EMAIL ADDRESS:
_ ST ZIP
FAX( )
DESCRIPTION OF BUILDING (EX: HOUSE, MOBILE HOME, MODULAR, SHOP, OFFICE)
IF OBTAINING A REPAIR PERMIT, WHAT IS BEING REPAIRED? _ _
Au, e.
NUMBER OF PERSONS NUMBER OF BEDROOMS J22
BASEMENT PLUMBING YES
BATHROOMS: FULL _ _'/ '/,
PUBLIC WATER SUPPLY YES /0 NAME
--
PIUVAIL WAFER SUPPLY / NO WELL /CISTERN
IN FLOOD PLAIN AREA? YES /NO W6 Pa 6AsAro�
"%ad p‘, , n Map
PERCOLATION HOLES MUST BE MARKED FOR
INSPECTION OR A $50.00 FEE WILL BE CHARGED
CENSUS TRACT
PERMITN 0789 676
PLEASE DRAW A MAP TO YOUR PROPERTY.
6,5
ALLES TAYLOR & DUKE, LLC 3610 35TH AVE UNIT 96
LICENSED PROFESSIONAL ENGINEERS EVANS, 80639
LICENSED PROFESSIONAL LAND SURVEYORS 970-330-0308
October 22, 2012
Mr. Trevor Jiricek
Weld County Department of Public Health & Environment
1555 North 17th Avenue
Greeley, Colorado 80631
RE: Septic Design - Randolph & Judy Cass
37967 HWY 14
Briggsdale, CO 80611
Lot "A", RECX 12-0079
Pt S '/1, SE 1/4 , Sec 20, T8N, R62W, 6th P.M.
Residential (3 Bedroom House)
Dear Sir:
The following septic design for Randolph & Judy Cass is submitted for your review and approval.
1. I preformed a percolation test for the site on October 22, 2012 and the percolation rate
obtained was 15.16 Min./in., use 20 min./in for design, see attached computations. The
soil profile is as follows: 0" - 11" Top Soil, 11" - 31" Sandy Loam, 31"- 45" sandy silt and
black clay, 45" - 63" Sandy Silt with a Trace of clay, 63"-96" Sand/Sandy Loam. No limiting
layer in the soil to be used for absorption trench was observed and no groundwater was
observed in the soil profile pit.
2. For a three (3) bedroom house, 287 SF of trench absorption, Table 30-2, is required for each
bedroom. The required square footage of absorption trench is 861 SF, 3 * 287 = 861 SF.
Quick 4 Infiltrators will be used at the site, reduction factor = 0.5, 861 * 0.5 = 430.5 SF, and
a minimum of 47 Quick 4 Infiltrators will be used, 430.5 /9.2 = 46.8 units, use a
minimum of 47 infiltrator units. The absorption trench configuration shall be built to fit the
existing site conditions.
3. The existing 1000 gallon septic tank is in poor condition. A new 1000 gallon septic will be
required per Table 30-1.
4. The absorption field and septic tank shall be constructed and installed in accordance with
Weld County Health Department regulations.
5. The absorption bed/trench shall be place a minimum of 100 feet from any existing water
well.
6. No traffic shall be permitted on the new absorption field after construction.
If you have any questions, please contact me.
Respectfully submitted,
Mark Taylor c, --
Colorado P.E. 46065
2012-115 Residential
SEPTIC DESIGN
RANDOLPH & JUDY CASS, 37967 HWY 14, BRIGGSDALE, CO 80611
A THREE (3) BEDROOM DWELLING. A 1000 GALLON SEPTIC TANK IS REQUJRED,TABLE 30-2. THE EXISTING 1000 GALLON
SEPTIC TANK IS NOT ADEQUATE. A NEW 1000 GALLON SEPTIC TANK WILL BE REQUIRED.
20 MIN/IN = 287 SQ. FT./BEDROOM (TRENCH) 3' 287 = 861 SQ. FT. QUICK 4 INFILTRATOR SYSTEM, REDUCETION FACTOR =
0.5, 861 ' 0.5 = 430.5 SF. 430.5/9.2 = 46.8 UNITS, USE MININMUM OF 47 UNITS.
THE PROPOSED ABSORPTION TRENCH SYSTEM SHALL BE CONFIGURED TO FIT THE EXISTING SITE CONDMONS. THE
ABSORPTION TRENCH CONFIGURATION SHALL BE TWO ROWS OF 16 UNITS AND ONE ROW OF 15 OR CONFIGURED TO FIT
THE AVAILABLE AREA WITH AN EQUAL NUMBER OF INFILTRATOR UNITS IN EACH TRENCH.
SEPTIC HELD MUST BE A MINIMUM OF 20 FEET FROM ANY OCCUPIED BUILDING, 10 FEET FROM PROPERTY
LINES, 100 FEET FROM ANY WATER WELLS AND 100 FEET FROM ANY IRRIGATION PONDS,
DRAINAGE SHALL BE SLOPED AWAY FROM ABSORPTION TRENCH SYSTEM.
NTS
ABSORPTION TRENCH
DIST
BOX
EXISTING PROFILE
1000 GALLON HOLE
SEPTIC TANK
TO BE
ABANDON 5T
30
5'MIN.
14't
27' PROPOSE'
1000 GALLON
SEPTIC TANK
WATER WELL
HWY 14 (ROW 100') PAVED
Typical TRENCH SYSTEM CONFIGURATION
6' min. -
0
y
2
6
O_
0
r7
6' min.
ABSORPTION TRENCH
50t
PERC TEST
MIN/IN
1 1-1/4"
2 1-1/8"
3 1-1/8"
4 1-0"
5 0-7/8"
6 0-9/16"
AVE = 15.158MIN
IN
USE 20 MIN/IN
FOR DESIGN
2' MAX
1.0' MINIMUM
COVER
4'
1 � 1
1.5' I 1.5' Imo- 6' MIN. -TI
X- SECTION - NTS
EXISTING GROUND
NO GROUND
WATER AT 8'
2012-115 RES
Nov 02 12 10:27a Diane Johnson
070-356-6110 p.1
Form No,
GWS-25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
ens Centennial Bldg 1313 Snormen St., Denver, Colorado 80203
(203) 866-3501
RANDOLPH J. CASS
43251 HWY 392
BRIGGSDALE, CO 80611-
(970) 656-3559
REGISTRATION OF EXISTING WELL
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this perms
does not ensure that no injury wilt occur to another vested water right or preclude another owner of a veoted water right from
seeking relief In a civil court action.
2) Construction details for this exlsr;ng welt have not been provided to this office: therefore, it is not known If the construction
of this well is in compliance with the Waler Well Construction Rules, 2 CCR 402-2. The issuance of this permit does not
relieve the well owner of responsibility or liability in the event contamination Otte groundwater source results tram the
construction or use of this well, nor dyes the State Engineer assume any responsibility or liability shotsd contamination
occur.
3) Recorded pursuant to CRS 37-92-602(5), and the policy of the State Engineer, for historical use es indicated herein. This
well produces 15 GPM, and is used for ordinary household purposes Inside one single family dwelling and for drinking and
sanitary facilities as described in CRS 37-92-602(1)(c), in an individual commercial business. This business is described
es a caf�. Water from this well shall not be used for any uses outside the dwelling or business building struclure(s),
including lawn or landscape irrigation, or animal watering.
4) Approved as the only well providing water to this business, which is on a 4.00 acre parcel, described as lot A. recorded
exemption RECX12-0(179, Weld County, reference attached exhibit A.
5) The average annual amount of ground water to be appropriated shall not exceed one (1) acre -loot (325,850 gallons).
6) The date of first beneficial use. as claimed by the applicant, is the 1950's.
7) The return flow from the use of this well must be through an individual waste water disposal system of the
non -evaporative type where the water is returned to the same stream system In which the well is located.
a; A totalizing flow meter must be installed on this well and maintained In good working order. Permanent records of all
diversions must be maintained by the wet owner (recorded at least annually) and submitted to the Division Engineer upon
request.
9) Approved for the use of an existing well constructed under permit no. 164248-A. The issuance of this permit hereby
cancels permit no. 164248-A.
NOTICE: This permit has been approved for Indoor use only, you are hereby notified that you have the right to appeal the
Issuance of this permit, by filing a written request with this office within sixty (60) days of the date of issuance, pursuant to
the State Administrative Procedures Act. (See Section 24-4.104 through 106, C R.S.)
LR
r
WELL PERMIT NUMBER 289676
DIV. 1 WD 1 DES, BASIN MD
APPROVED WELL LOCATION
WELD COUNTY
SE 1/4 SE 1/4 Section 20
Township 6 N Range 62 W Sixth P.M.
DISTANCES FROM SECTION LINES
150 Ft. from South Section Line
150 Ft. from East Section Line
UTM COORDINATES (Metere.Zone:13,NADe31
Ea sting: Northing:
APPROVED -
SRB
State EnpNte
,ReceiptNo.3657438A
DATE ISSUED
ByJ
10.30.2012 XPIRATION DATE NA
Hello